CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
5–45
process control. A minimum of 20 V applied must exist on all voltage inputs before this
feature will operate.
•
POWER FACTOR LEAD 1(2) PICKUP
: When a leading power factor equals or exceeds
the level set by this setpoint, a Power Factor Lead 1(2) condition will occur.
•
POWER FACTOR LEAD 1(2) DROPOUT
: When a leading power factor drops below this
level, the Power Factor Lead 1(2) condition will drop out.
•
POWER FACTOR LEAD 1(2) DELAY
: If the power factor equals or exceeds the
POWER
FACTOR LEAD 1(2) PICKUP
setpoint value and remains this way for the time delay
programmed in this setpoint, a Power Factor Lead 1(2) condition will occur.
If the power factor drops below the
POWER FACTOR LEAD 1(2) DROPOUT
setpoint value, the
power factor lead 1(2) condition will drop out. If the
POWER FACTOR LEAD 1(2) RELAY
setpoint is set to “Alarm”, the alarm relay will deactivate and the
POWER FACTOR LEAD
1(2) ALARM
message will be cleared. If the
POWER FACTOR LEAD 1(2) RELAY
setpoint is set to
“Aux1”, “Aux2”, or “Aux3,” the respective auxiliary relay deactivates.
•
POWER FACTOR LAG 1(2) RELAY
: Power factor detection can either be disabled, used
as an alarm or as a process control. Set this setpoint to “Off” if the feature is not
required. Selecting “Alarm” activates the alarm relay and displays an alarm message
when the power factor is more lagging than the level set. Selecting “Aux1”, “Aux2”, or
“Aux3” activates the respective auxiliary relay when the power factor is equal to or
more lagging than the level set, but no message will be displayed. This is intended for
process control. A minimum of 20 V applied must exist on all voltage inputs before this
feature will operate.
•
POWER FACTOR LAG 1(2) PICKUP
: When a lagging power factor equals or exceeds the
level set by this setpoint, a Power Factor Lag 1(2) condition will occur.
•
POWER FACTOR LAG 1(2) DROPOUT
: When a lagging power factor drops below this
level, the Power Factor Lag 1(2) condition will drop out.
•
POWER FACTOR LAG 1(2) DELAY
: If the power factor equals or exceeds the
POWER
FACTOR LAG 1/2 PICKUP
setpoint value and remains this way for the time delay
programmed in this setpoint, a Power Factor Lag 1(2) condition will occur.
If the power factor drops below the
POWER FACTOR LAG 1(2) DROPOUT
setpoint value, the
Power Factor 1(2) lag condition will drop out. If the
POWER FACTOR LAG 1(2) RELAY
setpoint
is set to “Alarm”, the alarm relay will deactivate and the
POWER FACTOR LAG 1(2)
ALARM
message will be cleared. If the
POWER FACTOR LAG 1(2) RELAY
setpoint is set to
“Aux1”, “Aux2”. or “Aux3”, the respective auxiliary relay will deactivate.
Содержание PQM II
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights ...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture ...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder ...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...