![GE PQM II Скачать руководство пользователя страница 118](http://html.mh-extra.com/html/ge/pqm-ii/pqm-ii_instruction-manual_128427118.webp)
5–34
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
5.5
S4 Alarms/Control
5.5.1
Current/Voltage Alarms
PATH: SETPOINTS
ÖØ
S4 ALARMS/CONTROL
Ö
CURRENT/VOLTAGE
CURRENT/
[
Z
]
VOLTAGE
DETECT I/V ALARMS
USING PERCENTAGE: NO
Range: No, Yes
MESSAGE
PHASE UNDERCURRENT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
PHASE UNDERCURRENT
LEVEL
≤
100
A
Range: 1 to 12000 A in steps of 1, or
1 to 100% of CT in steps of 1,
set by the
DETECT I/V ALARMS
USING PERCENTAGE
value.
MESSAGE
PHASE UNDERCURRENT
DELAY: 10.0
s
Range: 0.5 to 600.0 s in steps of 0.5
MESSAGE
DETECT UNDERCURRENT
WHEN 0A: NO
Range: No, Yes
MESSAGE
PHASE OVERCURRENT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
PHASE OVERCURRENT
LEVEL
≥
100
A
Range: 1 to 12000 A in steps of 1, or
1 to 150% of CT in steps of 1,
set by the
DETECT I/V ALARMS
USING PERCENTAGE
value.
MESSAGE
PHASE OVERCURRENT
DELAY: 10.0 s
Range: 0.5 to 600.0 s in steps of 0.5
MESSAGE
PHASE OVERCURRENT
ACTIVATION: AVERAGE
Range: Average, Maximum
MESSAGE
NEUTRAL OVERCURRENT
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
NEUTRAL OVERCURRENT
LEVEL
≥
100 A
Range: 1 to 12000 A in steps of 1, or
1 to 150% of CT in steps of 1,
set by the
DETECT I/V ALARMS
USING PERCENTAGE
value.
MESSAGE
NEUTRAL OVERCURRENT
DELAY: 10.0 s
Range: 0.5 to 600.0 s in steps of 0.5
MESSAGE
UNDERVOLTAGE
RELAY: OFF
Range: Alarm, Aux1, Aux2, Aux3, Off
MESSAGE
UNDERVOLTAGE
LEVEL
≤
100
V
Range: 20 to 65000 V in steps of 1, or
20 to 100% of VT in steps of 1,
set by the
DETECT I/V ALARMS
USING PERCENTAGE
value.
MESSAGE
UNDERVOLTAGE
DELAY: 10.0 s
Range: 0.5 to 600.0 s in steps of 0.5
MESSAGE
PHASES REQ’D FOR U/V
OPERATION: ANY ONE
Range: Any One, Any Two, All Three.
Not seen when
VT WIRING
is set
to “Single Phase Direct”
Содержание PQM II
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights ...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture ...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION ...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder ...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE ...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING ...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS ...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY ...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A ...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX ...