SECTION 13—Opening and Closing Speed
The opening speed is modified by moving the spring adjusting
nuts on the opening spring assemblies. A change in opening
speed affects the closing speed. Reference Figure 12.
The operating speeds for a 5 cycle breaker are as follows:
Operation
Operation
Operation
Operation
Feet Per Second
Feet Per Second
Feet Per Second
Feet Per Second
Open
4.3 - 5.6
Close
2.6 – 3.9
V.I. STOP CENTER PHASE
Figure 12 Contact gap adjustment