GE PACSystems RXi Box IPC Скачать руководство пользователя страница 27

Hardware Installation

 

22 

PACSystems* RXi Box IPC 

GFK-2785C

 

5.

Remove the RTC battery from the retaining clip, being careful to not bend the positive
terminal clip.

Warnings 

Use of a different type of battery than that specified here may present a risk of 
fire or explosion. 

Battery may explode if mistreated. Do not recharge, disassemble, heat above 
100°C (212°F) or incinerate. 

Note:

 

For proper disposal, refer to Battery Disposal document 82A1540-MD01. 

6.

Install the new battery in the retaining clip.

The replacement battery must be IC690ACC001 from GE Intelligent Platforms.

Install the battery with the positive (+) side up. That is, with the + side away from the
circuit board.  The coin cell must be inserted at an angle to go under the positive terminal
clip and then slid into the carrier and snapped into place.

7.

Replace and secure the interior lid with four Phillips-head screws.

8.

Replace the front panel on the IPC and hand-tighten the four screws to secure it.

RTC Battery 

Содержание PACSystems RXi Box IPC

Страница 1: ...GE Intelligent Platforms Industrial Computer Products PACSystems RXi Box IPC User s Manual GFK 2785C May 2014...

Страница 2: ...de to be accurate the information contained herein does not purport to cover all details or variations in hardware or software nor to provide for every possible contingency in connection with installa...

Страница 3: ...free 800 option is unavailable Technical Support Email support ip ge com Customer Care Email customercare ip ge com Primary language of support English Europe the Middle East and Africa Online Technic...

Страница 4: ...tallation Guidelines 11 Grounding 12 Mounting Orientation 12 Dimensions and Clearances for Installation 13 Mounting Procedures 14 Mounting the IPC on a DIN Rail 14 Mounting the IPC on a Panel Using a...

Страница 5: ......

Страница 6: ...vity and allows you to maximize application reusability supporting your current and future needs for business growth These small form factor industrial PCs provide a number of features to support comp...

Страница 7: ...m x 81 3mm 7 55 in x 4 55 in x 3 2 in Backplate 226 mm x 137 mm x 12 mm 8 90 in x 5 39 in x 0 47 in Weight IPC without Backplate 1 814 Kg 4 lbs Backplate 0 454 Kg 1 lb Processor 1 0 GHz VIA Eden dual...

Страница 8: ...r than 50 C 122 F the unit must be installed in a restricted access area as defined below Warning If the Box IPC is operating in ambient temperatures greater than 50 C 122 F its exterior temperatures...

Страница 9: ...s RXi Box IPC GFK 2785C RXi Box IPC User Features Power On Off Switch and Status Indicator Indicators SD Card Slot Audio Connector Connectors Blue blinking Booting Blue slow fade S3 Sleep Green solid...

Страница 10: ...te is S1 CPU Stop Clock The default settings send IPC to sleep state S1 ICRXIBN7x000A The ring LED stays green while the IPC is in Sleep State S1 The ring LED turns off while the IPC is in Sleep State...

Страница 11: ...n press if power is cycled without a clean Win7 shutdown For ICRXIBN7x000A CA or earlier unit always operates in Last state despite UEFI setting Sleep Mode Setting Options and Ring LED Status Indicato...

Страница 12: ...are required if you need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessary to transport or ship any part of th...

Страница 13: ...compatible mouse 4 Power up the unit and check whether any concealed damage has been caused by incorrect transportation operating storage conditions or handling For ICRXIBN7x000A CA or earlier units...

Страница 14: ...nnect the IPC to your Ethernet network Note For Ethernet port and cabling information refer to chapter 4 Pinging TCP IP Ethernet Interfaces on the Network PING is the name of a program used on TCP IP...

Страница 15: ...n 2 To completely shut down the IPC turn off or remove the power supplying the IPC Disabling Operating System Shutdown ICRXIBN7xxxxx Models The current On Off button operation requires only a 100ms pr...

Страница 16: ...must be mounted with its cooling fins vertical to ensure adequate airflow The panel should be capable of supporting the weight of the industrial computer without distortion to the panel Adequate airfl...

Страница 17: ...2 and should be as short as possible If using the ICRXIACCBPL to mount the Box IPC add a ground wire from the M8 threaded hole on the metal DIN Backplate M8 screw included to protective earth The fram...

Страница 18: ...ions IPC 191 8 mm x 115 6 mm x 81 3 mm 7 55 in x 4 55 in x 3 2 in Backplate 226 mm x 137 mm x 12 mm 8 90 in x 5 39 in x 0 47 in Minimum clearances for heat dissipation Each side 51mm 2 inches Top and...

Страница 19: ...nit to the Backplate or panel Mounting the IPC on a DIN Rail You will need the following One 2 5mm hex driver included with the RXi IPC One flathead or large Phillips screwdriver One Backplate ICRXIAC...

Страница 20: ...allation GFK 2785C PACSystems RXi Box IPC 15 1 Install the IPC on the Backplate a Place the IPC and Backplate on a flat surface b Loosen the four captive screws on the IPC s front panel and remove the...

Страница 21: ...Backplate static latches on top For Backplate orientation refer to page 14 d Align the IPC s four mounting screws with the mounting holes in the Backplate e Using the hex driver tighten the mounting...

Страница 22: ...ith the top of the unit rotated approximately 20 from the panel b Engage the spring loaded latches at the bottom of the black DIN rail clip attached to the adaptor on the DIN rail c Rotate the unit up...

Страница 23: ...One ICRXIACCBPL Backplate 1 Install the IPC on the Backplate See step 1 on page 14 2 Drill four holes in the panel based on screw selection using the spacing shown in the following drawing if holes ar...

Страница 24: ...29 0 116 drill bit and M4x0 7 tap The IPC has four captive machine screws in its base for attaching the unit to the panel 1 Drill four mounting holes using the spacing shown in the following drawing a...

Страница 25: ...RXi Box IPC GFK 2785C 4 Align the IPC s four mounting screws with the mounting holes in the panel 5 Using the hex driver hand tighten the mounting screws 6 Replace the front panel on the IPC and hand...

Страница 26: ...ons when opening the IPC enclosure Wear a properly functioning antistatic strap and be sure that you are fully grounded Never touch any components inside the IPC unless you are wearing an antistatic s...

Страница 27: ...oper disposal refer to Battery Disposal document 82A1540 MD01 6 Install the new battery in the retaining clip The replacement battery must be IC690ACC001 from GE Intelligent Platforms Install the batt...

Страница 28: ...tting affects only the ability to power down the unit You can still use the On Off switch to power on the unit You will need the following One flat or large Phillips screwdriver 1 Turn off or remove t...

Страница 29: ...Hardware Installation 24 PACSystems RXi Box IPC GFK 2785C...

Страница 30: ...t 2 7 6 m 25 ft Yes1 SD Secure Digital slot Maintenance 3 NA NA Audio Maintenance 3 2 m 6 5 ft No 1 Shielding is required to be in compliance with the standards identified in Appendix A 2 Can be perma...

Страница 31: ...es shielded twisted pair STP cable is required to maintain CE compliance 10BASE T Two pairs of wire are used one for transmission and the other for receive 100BASE TX Two pairs of wire are used one fo...

Страница 32: ...tor shell provides frame ground To reduce interference shielded cables are required The Serial Communication Port connector is mapped as follows ICRXIBN7x000A CA versions and earlier COM2 ICRXIBN7x001...

Страница 33: ...DC 1 10 SGND 11 NC 12 SDA 13 H SYNC 14 V SYNC 15 SCL 1 There is a 1 1A self resetting fuse on the 5V signal pin 9 SD Secure Digital Card Slot The IPC accommodates a user supplied SD card for auxiliary...

Страница 34: ...tem refer to http windows microsoft com for instructions RXi Box IPC Device Drivers The drivers and the instructions for installing them are available on the GE Intelligent Platforms Support website h...

Страница 35: ...etain it in a secure location Use this drive to recover in the event of drive failure The procedure is as follows 1 Power down the RXi system 2 Insert the USB recovery Flash Drive in any available USB...

Страница 36: ...inute Wait for the RXi recovery screen to appear 5 Click the Start WES7 Recovery button Note clicking the Exit the Program button will abort the recovery and reboot the RXi computer 6 A warning messag...

Страница 37: ...Box IPC GFK 2785C 7 The image load process will be displayed as follows 8 When the image load completes the system will prompt to remove the USB drive 9 Remove the USB drive and click OK The system wi...

Страница 38: ...LED will blink on red and then shut off quickly while the entire unit shuts down The Power On Off LED turns off at the same time To recover let the Box IPC cool and then press the Power On Off button...

Страница 39: ...System Recovery 34 PACSystems RXi Box IPC GFK 2785C...

Страница 40: ...tifications and Installation Guidelines for Conformance This appendix describes the compliance markings that appear on PACSystems RXi industrial computer products and the corresponding standards to wh...

Страница 41: ...ccordance with European Directives Refer to Declaration of Conformity found at http www ge ip com for a complete list of approved products Electromagnetic Compatibility Directive European EMC for Indu...

Страница 42: ...1 0 2 0 GHz 1 V m 2 0 2 7 GHz Fast Transient EN 61000 4 4 2 DC Input 2 kV 33 nF direct Video and Ethernet ports shielded 1 1 kV capacitive clamp RS 232 port unshielded 1 1 kV capacitive clamp Surge E...

Страница 43: ...vironment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communica...

Страница 44: ...ining if already used 9 LEDs Ethernet port 5 26 IPC status 5 module 4 power 5 6 Mounting dimensions 13 DIN rail 14 orientation 12 panel direct 19 panel with a Backplate 18 space required 13 Network co...