Hardware Installation
12
PACSystems* RXi Box IPC
GFK-2785C
Grounding
Note:
These grounding connections serve as a path for reducing noise interference and radiated
emissions and are required for the IPC to comply with the standards identified in Appendix A.
The DIN rail or panel the IPC is mounted on must have a safety ground connection to
protective earth. This ground wire must be at least #16 AWG (1.31mm
2
) and should be as
short as possible.
If using the ICRXIACCBPL to mount the Box IPC, add a ground wire from the M8 threaded hole
on the metal DIN Backplate (M8 screw included) to protective earth.
The frame ground connection on the power plug must be a 16 to 28 AWG (1.31to 0.08mm
2
)
wire with shortest possible length. It is recommended that these ground wires terminate in a
star wiring pattern at the same grounding point.
Mounting Orientation
The cooling fins on the back of the IPC must be vertical. However the unit can be mounted with
the front panel connectors oriented either up or down.
Correct
Incorrect