Chapter 3. Configuration
52
PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual
GFK-2571N
3.2
Configuration Tools
Proficy Machine Edition (PME) is the primary tool used to configure an RX3i PROFINET network. In addition, for
the PNC001 module only, certain parameters can be set from a computer through the Command Line Interface
(CLI).
The Command Line Interface can be used to set the non-volatile parameters in the PNC001-Ax module, as
listed below. These parameters are initially set up in the PME configuration. If any of these parameters is
subsequently changed using CLI, the PNC001 module uses the new setting. Regardless of their source, the
PNC001 module retains these settings in non-volatile memory, thus ensuring they can be re-asserted following
a power cycle.
3.2.1
Non-Volatile Configuration Parameters
Parameter
Description
Default
Value
IP Address
IP Address of the PNC001.
0.0.0.0
Subnet Mask
Subnet mask of the PNC001.
0.0.0.0
Default Gateway
Default Gateway for the PNC001.
0.0.0.0
Device Name
PNC001
’s PROFINET
Device Name
. Defaults to empty string -
indicating the PNC001 is not named.
””
Redundant Media Role
Specifies whether media redundancy is disabled, or if it is enabled
as a Client, or if it is enabled as a Manager.
Disabled
Redundant Media Ring
Port 1 ID
Indicates one of the two network ports involved in Media
Redundancy. Valid values are 1 to 4.
1
Redundant Media Ring
Port 2 ID
Indicates one of the two network ports involved in Media
Redundancy. Valid values are 1 to 4.
2
Redundant Media test
interval
Interval for sending test frames on ring ports in millisecond units.
Valid values are 1 to 1000 ms.
20 ms
Redundant Media
monitor count
Indicates the number of consecutive failed test frames before
declaring a ring failure. Valid values are 2 to 10.
3