Chapter 3. Configuration
GFK-2571N
May 2018
53
3.3
Configuring an RX3i PROFINET Controller
3.3.1
Configuring a Rack-Mounted RX3i PROFINET Controller (PNC001)
This section describes one technique to configure the parameters of an RX3i IC695PNC001. The PROFICY
Machine Edition
InfoViewer
describes alternative menus and keyboard operations that can be used to perform
the same functions.
1.
In the
Project
tab of the
Navigator
, expand the
PACSystems Target, the hardware configuration, and the
main rack (Rack 0).
Figure 32: RX3i Configuration showing
PNC001 slot location
2.
Right-click an empty slot and choose
Add Module
. The
Module Catalog opens.
3.
Open the
Bus Controller
tab, select the IC695PNC001
module and click OK.
4.
The PNC001 is displayed as having been placed in the
selected rack/slot location.
-
Its parameters appear in the
Parameter Editor
window.
-
Its communications properties appear in the
Inspector
pane.
-
Edit the PNC001
’s parameters and its
communications properties as described in this
chapter.
3.3.2
Configuring an Embedded RX3i PROFINET Controller
CP400 and CPE330 both support configuring LAN2 as an embedded PROFINET Controller. Instead of
Configuring a PNC001 into a rack/slot location (Figure 32), LAN2 in the target is configured as a PROFINET
Controller (Figure 33).
Figure 33: Embedded PROFINET Controller Configured on LAN2