8
RX3i Ethernet Interface Module IC695ETM001-HW IPI
GFK-2332Y
August 2017
Release History
Catalog Number
Firmware
Version
Date
Comments
IC695ETM001-FT
6.30
Oct. 2014 Firmware version 6.30 Fixes the following issues:
•
In very rare conditions closing Modbus or SRTP
session can result in a 3-5 blink code.
•
With unicast SNTP the ETM could lose server lock
and then (1) never show any server as locked
again and (2) not attempt to switch to another
server. In v6.30, (1) Lock status can be restored
when a server becomes consistent and (2) SNTP
will attempt to switch to another server when the
current server becomes inconsistent.
•
The ETM clock can drift away from the locked-on
server’s time at a several msec/day rate.
•
Removed an extraneous log event. The
extraneous log event would occur (1) on battery-
backed power-up and (2) store of hardware
configuration, when the user configures the ETM
for SNTP, but does not configure the ETM for
daylight savings time correction.
IC695ETM001-FS
6.21
Aug. 2014 Replaces the module’s plastic housing with a metal case,
improving noise immunity, reducing emissions, and
increasing the mechanical robustness of the product. No
change to the module’s firmware or functionality.
IC695ETM001-ES†
6.21
Jan. 2014 Ethernet Firmware version fixes an issue with calculating
DST correction in the European Union when SNTP is
enabled.
IC695ETM001-ER
6.20
Jul. 2013
Adds support in SNTP for local time zones and daylight
savings time and resolves the field issues described on
page 7.
IC695ETM001-EP†
6.14
Jul. 2012
Resolves an issue with a spurious blink code being
displayed during SRTP communications with CIMPLICITY
Plant Edition software.
IC695ETM001-EN
6.13
Apr. 2012 Addresses a field issue and a product security issue. For
details, refer to GFK-2332M.
IC695ETM001-EM
6.12
Dec. 2011
Disables several unnecessary services in the firmware that
otherwise could result in disruption of system operation and/or
data corruption. For details, refer to GFK-2332L.
IC695ETM001-EL†
6.11
Nov. 2011 Resolves an issue with missed EGD samples. For details,
refer to GFK-2332K.
IC695ETM001-EK
6.10
Sep. 2011 For problems resolved, refer to GFK-2332J.
IC695ETM001-EJ
6.00
Sep. 2009 Adds an SRTP inactivity timeout for better recovery from
lost communication with the programmer. For details and
problems resolved, refer to GFK-2332H.
IC695ETM001-EH
5.51
Jan. 2009 Adds new diagnostics capabilities. For details and
problems resolved, refer to GFK-2332G.
Hardware version Ex updates the IC695ETM001 for RoHS
compliance.