RX3i Ethernet Interface Module IC695ETM001-HW IPI

 

11 

August 2017

 

GFK-2332Y 

 

 

Restrictions and Open Issues 

Subject 

Description 

EGD command range failure 

can write partial data to 

controller bit memory  

When an EGD Command attempts a write operation to a bit-mod

reference memory range (%I, %Q; %T, %M, %SA, %SB, %SC) where the 

amount of data to be written exceeds the configured size of that 

reference memory, the command will return failure status but partial data 

may be written into the reference memory. The amount of partial data 

written depends upon the starting bit memory location and the data 

length as follows: 

▪ 

If data starts on a byte boundary (location = (8 

 n) + 1), no partial data 

is written. 

▪ 

If data does not start on a byte boundary (location = (8

n)+1) and data 

exceeds the configured reference memory by 8 or more bits, partial 

data is written from the starting location to the next byte boundary 

after the starting location. 

▪ 

If data does not start on a byte boundary (location = (8

n)+1) and data 

exceeds the configured reference memory by less than 8 bits, partial 

data is written from the stating location to the end of configured 

reference memory. 

For a Write PLC Memory command, this can occur when writing data into 

the target PLC. For Read PLC Memory or Read Exchange commands, this 

can occur when writing data received from the target controller into the 

local CPU memory.  The logic application must not use any data returned 

to the local CPU if the EGD command status indicates failure. 
To avoid writing partial data to the local or remote PLC, be sure bit 

memory data transfers do not exceed the configured reference memory 

sizes at the appropriate PLC.  

Do not operate with CPU in 

incorrect slot 

The operation of the Ethernet interface is disrupted if the RX3i CPU is 

placed in a slot other than the one in which it is configured.  Various 

Ethernet exception log events may occur, such as (Entry = 2, Entry 2 = 30 

or 35 or 39 or 1e or 1f) or (Entry = 8, Entry 2 = b). 

No CPU fault logged when 

Ethernet interface in fatal blink 

code 

The CPU does not log any Controller or I/O Faults when the Ethernet 

Interface has a fatal blink code.  The application should monitor the LAN 

interface OK status bit to detect loss of module. 

EGD I/O has unexpected 

variability under heavy load 

EGD I/O has intermittent unexpected variability under heavy load.  For a 

Produced Exchange, EGD samples may occasionally be delayed by as 

much as a production period or more. 

Clear of large hardware 

configurations may cause log 

event 08/20 

A Log event 08/20 may occur when very large hardware configurations 

are cleared and transfers are active on other Server connections.  This log 

event can be safely ignored. 

Reset pushbutton 

Reset pushbutton action is different from other PACSystems Ethernet 

products.  On the RX3i Ethernet module, the state of the pushbutton when 

the module powers up can change the behavior of the Restart 

pushbutton.  Under normal operation, a pushbutton press produces a 

rising-edge signal that triggers a module restart.  However, if the 

pushbutton is pressed when power is activated (either by pressing the 

pushbutton before turning power on or by continuing to hold the 

pushbutton in after a restart), the functionality of the pushbutton is 

inverted.  When the pushbutton is later released, an "incorrect" rising-edge 

is detected, which triggers an inappropriate module restart.  This does not 

occur on other PACSystems Ethernet products. 

Содержание PACSystems RX3i IC695ETM001-JW

Страница 1: ... data exchange using Ethernet Global Data EGD EGD Commands to read and write controller and EGD exchange memory over the network TCP IP communication services using SRTP Support for SRTP Channels Modbus TCP Server and Modbus TCP Client Built in Station Manager for on line supervisory access to the Ethernet Interface Dedicated Station Manager port Two auto sensing 10Base T 100Base TX RJ 45 shielded...

Страница 2: ...ion Manager Port RS 232 DCE 1200 115 200 bps Refer to the PACSystems RX3i System Manual GFK 2314 for product standards and general specifications Ethernet Interface Status Bits Note Unless LAN Interface OK Status Bit 16 is set the other status bits are invalid LAN Interface Status Bits 1 Port 1A full duplex 2 Port 1A 100Mbps 3 Port 1B full duplex 4 Port 1B 100 Mbps 5 Network Time Locked 6 Redundan...

Страница 3: ... ETHERNET OK LAN OK LOG EMPTY Blink error code Off Off Hardware failure See chapter 11 for blink code definitions ETHERNET OK LAN OK LOG EMPTY Slow Blink Slow Blink Slow Blink All LEDs blink in unison pattern same while awaiting or performing load Firmware Update Field Wiring Station Manager RS 232 Port Pin Assignment Pin No Signal Direction Description 1 DCD IN Data Carrier Detect 2 TX OUT Transm...

Страница 4: ...e enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support For phone numbers and email addresses see the back cover of ...

Страница 5: ...with all RX3i CPU models 1 RX3i rack power may be off or on hot insertion 2 Holding the module firmly align the module with the correct slot and connector then swing the module down until the module s connector engages the backplane s backplane connector Visually inspect the module to be sure it is properly seated 3 Insert the two provided M3x5mm machine screws through the module s bottom bracket ...

Страница 6: ... IC693CMM321 is not supported by the RX3i and should not be placed in an RX3i rack Series 90 30 CPUs with embedded LAN Interface IC693CPU364 and IC693CPU374 like any Series 90 30 CPU should not be placed in an RX3i rack Modbus TCP support Release 3 60 of the PACSystems Ethernet Interface adds Modbus TCP Client Channels capability It supports Modbus Conformance Class 0 function codes 3 and 16 Confo...

Страница 7: ...requiring a power cycle if it was subjected to heavy network storm traffic Reference GE Security Advisory is GE15 09 titled Network Storm Denial of Service In addition to the enhancement there were issues resolved Please refer to the Problems Resolved by This Release section above for more details IC695ETM001 HU 6 31 Nov 2015 Firmware release 6 31 IC695ETM001 HU provides a Field Upgrade Kit to add...

Страница 8: ...change to the module s firmware or functionality IC695ETM001 ES 6 21 Jan 2014 Ethernet Firmware version fixes an issue with calculating DST correction in the European Union when SNTP is enabled IC695ETM001 ER 6 20 Jul 2013 Adds support in SNTP for local time zones and daylight savings time and resolves the field issues described on page 7 IC695ETM001 EP 6 14 Jul 2012 Resolves an issue with a spuri...

Страница 9: ...e connections SRTP connections remain open after IP address changed The Ethernet Interface does not terminate all open SRTP connections before changing its IP address If the local IP address has changed any existing open TCP connections are unable to normally terminate This can leave SRTP connections open until their underlying TCP connections time out If quicker recovery of the SRTP connection is...

Страница 10: ...ult can be safely ignored Unexpected EGD COMMREQ status EGD Commands may return COMMREQ Status 9590H internal error instead of the expected B190H Can t locate remote node when unable to locate a remote device on the network Very heavy EGD production consumption at server may cause EGD command timeouts Very heavy EGD production and or consumption at a server device may cause EGD command timeout err...

Страница 11: ...ference memory sizes at the appropriate PLC Do not operate with CPU in incorrect slot The operation of the Ethernet interface is disrupted if the RX3i CPU is placed in a slot other than the one in which it is configured Various Ethernet exception log events may occur such as Entry 2 Entry 2 30 or 35 or 39 or 1e or 1f or Entry 8 Entry 2 b No CPU fault logged when Ethernet interface in fatal blink c...

Страница 12: ... the parent directory then delete the target directory without specifying a path For example the rmdir dir1 dir2 results in RMDIR Failed dir1 dir2 does not exist Instead first do cd dir1 and then rmdir dir2 Intermittent Ethernet log event 8H 15H after power cycle When starting after a power cycle the Ethernet Interface may intermittently log an exception entry 8H Entry 2 15H Entry 3 0000H Entry 4 ...

Страница 13: ... is disabled until the station manager password is changed to other than the default password The station manager password can be changed using an AUP file Refer to Appendix A Configuring Advanced User Parameters in TCP IP Ethernet Communications for PACSystems User s Manual GFK 2224K Changing the default Station Manager password is strongly recommended GE Intelligent Platforms strongly recommends...

Страница 14: ...ess from a BOOTP server device on the network LAN must be tree not ring The two Ethernet network ports on the PACSystems RX3i Ethernet Interface must not be connected directly or indirectly to the same network device The hub or switch connections in an Ethernet network must form a tree and not a ring otherwise duplication of packets and network overload may result In this situation the RX3i Ethern...

Страница 15: ...tain the underlying network and STRP connection Examples are establishing the TCP connection for a new channel establishing communication with the remote device and TCP retransmissions during Channel operations If the time needed for TCP connection establishment or maintenance exceeds the user specified channel application timeout values an application timeout will occur Channel application timeou...

Страница 16: ...ucts and the Series 90 30 CPU364 EGD timestamps are taken from the Ethernet interface and do reflect CHTIME modifications ENIU Stale Data During Run Mode Store of EGD In a large PPS system running 20 ENIUs when a Run mode Store is performed that deletes the EGD exchanges for 10 of the ENIUs the other ENIUs will see the status on their exchanges indicate consumption timeouts during the RMS At the c...

Отзывы: