Index
GFK-2839B
PAC8000* IO PROFINET Scanner
User’s Manual–September 2017
21
2.2
Cable and Connector Clearance Requirements
You may need to allow more space for installation of cables and connectors than what is
required for heat dissipation. To avoid impacting mechanical reliability and signal quality,
cable installation must comply with the minimum bend radius specified by the cable
manufacturer.
Cable Clearance Example
In this example, an 8516-BI-PN module is installed with a fiber optic cable that has the
following characteristics:
SC-Duplex connector length: 27mm (1.07 inches)
Manufacturer-recommended long-term minimum bend radius: 30mm (1.2 inches)
The minimum clearance required to insert the connector into a port is 57mm (2.27 inches).
Additional clearance is recommended to provide physical access. In the case of the
8516-BI-PN, the space required for cabling will be greater than the space required to meet
thermal ratings.
1
2
Содержание PAC8000 series
Страница 4: ......
Страница 20: ...Contents 20 PAC8000 IO PROFINET Scanner User s Manual September 2017 GFK 2839B ...