NX-1710E Single Door Control
19
L
OCATION
54
WEIGAND FORMAT 1 – P
ARITY
T
YPE
4
(1 segment of decimal data) This location programs the Partity Type 4 for Weigand Format 1. Available options
for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity. Factory default is 0.
L
OCATION
55
WEIGAND FORMAT 1 – P
ARITY
M
ASK
4
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity
bits. It is used in conjunction with Location 54 (Parity Type 4). The factory default is:
Seg 1
Seg 2
Seg 3
Seg 4
Seg 5
Seg 6
Seg 7
Seg 8
--------
--------
--------
--------
-------- -------- -------- --------
L
OCATION
56
WEIGAND FORMAT 1 – P
ARITY
T
YPE
5
(1 segment of decimal data) This location programs the Partity Type 5 for Weigand Format 1. Available options
for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity. Factory default is 0.
L
OCATION
57
WEIGAND FORMAT 1 – P
ARITY
M
ASK
5
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity
bits. It is used in conjunction with Location 56 (Parity Type 5). The factory default is:
Seg 1
Seg 2
Seg 3
Seg 4
Seg 5
Seg 6
Seg 7
Seg 8
--------
--------
--------
--------
-------- -------- -------- --------
L
OCATIONS
58 – 70
WEIGAND FORMAT 2
(T
ECOM
ASC 27
BIT
)
These locations contain the programming for Weigand Format 2. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.
L
OCATIONS
71 - 83
WEIGAND FORMAT 3
(HID1000)
These locations contain the programming for Weigand Format 3. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.
L
OCATIONS
84 – 96
WEIGAND FORMAT 4
(H10304)
These locations contain the programming for Weigand Format 4. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.
L
OCATIONS
97 - 109
WEIGAND FORMAT 5
(40
BIT W
/F
ACILITY CODE
–
C
ASI
4001)
These locations contain the programming for Weigand Format 5. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.
L
OCATIONS
110 - 122
WEIGAND FORMAT 6
(40
BIT W
/
O
F
ACILITY CODE
–
C
ASI
4002)
These locations contain the programming for Weigand Format 6. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.
L
OCATIONS
123 - 135
WEIGAND FORMAT 7
(U
NDEFINED
)
These locations contain the programming for Weigand Format 7. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.
L
OCATIONS
136 - 148
WEIGAND FORMAT 8
(U
NDEFINED
)
These locations contain the programming for Weigand Format 8. Refer to the instructions for Locations 45 – 57
regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory defaults are in the worksheets.