NX-1710E Single Door Control 

18 

USER-DEFINABLE FORMATS 

The following locations are considered to be advanced programming and should 

ONLY be used by installers with a thorough understanding of Weigand Formats.  Do 
not attempt to program these locations if you are not familiar with Weigand packets.
 

 

L

OCATION 

45 

WEIGAND FORMAT 1

 

(S

TANDARD 

26 

BIT

)

 

– D

IGITS 

& B

ITS

 

(5 segments of decimal data)   This is the first location used to program the Weigand Format 1. (Loc 45-57) 

Segment 1 

Number of digits in Facility Code 

Segment 2 

Number of digits in Badge Number 

Segment 3 

Number of bits in Facility Code 

Segment 4 

Number of bits in Badge Number 

Segment 5 

Total number of bits in complete format (including parity bits) 

 

L

OCATION 

46 

WEIGAND FORMAT 1 – B

IT 

D

ESCRIPTORS 

(B

ITS 

1-32) 

(32 segments of hex data)  This location contains the descriptors for bits 1 – 32 of Weigand Format 1.  The 
available options are: 0=Always Zero; 1=Always One; B=Badge number; D=Parity bit; E=End of 
format; F=Facility Code bit. 
 Segment 1 = Bit Descriptor 1; Segment 32 = Bit Descriptor 32. 
 

L

OCATION 

47 

WEIGAND FORMAT 1 – B

IT 

D

ESCRIPTORS 

(B

ITS 

33-64) 

(32 segments of hex data)   This location contains the descriptors for bits 33 – 64 of Weigand Format 1.  
The available options are: 0=Always Zero; 1=Always One; B=Badge number; D=Parity bit; E=End of 
format; F=Facility Code bit. 
 Segment 1 = Bit Descriptor 33; Segment 32 = Bit Descriptor 64. 
 

L

OCATION 

48 

WEIGAND FORMAT 1 – P

ARITY 

T

YPE 

(1 segment of decimal data)  This location programs the Partity Type 1 for Weigand Format 1.  Available options 
for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.  Factory default is 1. 
 

L

OCATION 

49 

WEIGAND FORMAT 1 – P

ARITY 

M

ASK 

(8 segments of binary data)   This location tells which bits to include for the parity count; and includes the parity 
bits.  It is used in conjunction with Location 48 (Parity Type 1).  The factory default is: 

Seg 1 

Seg 2 

Seg 3 

Seg 4 

Seg 5 

Seg 6 

Seg 7 

Seg 8 

12345678 

12345678 

12345678 

------78 

-------- -------- -------- -------- 

 

L

OCATION 

50 

WEIGAND FORMAT 1 – P

ARITY 

T

YPE 

(1 segment of decimal data)  This location programs the Partity Type 2 for Weigand Format 1.  Available options 
for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.  Factory default is 2. 
 

L

OCATION 

51 

WEIGAND FORMAT 1 – P

ARITY 

M

ASK 

(8 segments of binary data)   This location tells which bits to include for the parity count; and includes the parity 
bits.  It is used in conjunction with Location 50 (Parity Type 2).  The factory default is: 

Seg 1 

Seg 2 

Seg 3 

Seg 4 

Seg 5 

Seg 6 

Seg 7 

Seg 8 

12345678 

---45678 

-------- 

-------- 

-------- -------- -------- -------- 

 

L

OCATION 

52 

WEIGAND FORMAT 1 – P

ARITY 

T

YPE 

(1 segment of decimal data)  This location programs the Partity Type 3 for Weigand Format 1.  Available options 
for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.  Factory default is 0. 
 

L

OCATION 

53 

WEIGAND FORMAT 1 – P

ARITY 

M

ASK 

(8 segments of binary data)   This location tells which bits to include for the parity count; and includes the parity 
bits.  It is used in conjunction with Location 52 (Parity Type 3).  The factory default is: 

Seg 1 

Seg 2 

Seg 3 

Seg 4 

Seg 5 

Seg 6 

Seg 7 

Seg 8 

-------- 

-------- 

-------- 

-------- 

-------- -------- -------- -------- 

 

Содержание NX-1710E - Single Door Control Module

Страница 1: ...NetworX Series NX 1710E Single Door Control Installation and Startup Manual...

Страница 2: ...document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of GE Security Please refer to the current GE Security product...

Страница 3: ...ER CARDS 9 VIII PROGRAMMING LOCATIONS 11 IX PROGRAMMING WORKSHEETS 20 X ORDERING INFORMATION 35 XI GLOSSARY 35 XII FCC INFORMATION 36 XIII UNDERWRITERS LABORATORIES INFORMATION 36 XIV SPECIFICATIONS 3...

Страница 4: ...itoring the door zone On board relay with Normally Open Normally Closed and Common terminals for use in switching power on MagLocks or other door locking mechanisms 8Kb of non volatile RAM for storing...

Страница 5: ...NX 1710E Single Door Control 5 II BOARD LAYOUT NetworX bus Programmer Dip Switches see pg 7 for specifics LED is lit during normal operation...

Страница 6: ...e of the power to the door control module POS Connect to NetworX control panel AUX POWER terminal Supplies power to the door control module 12 Power to reader module if required 5 Power to reader modu...

Страница 7: ...35 ON ON ON 143 ON ON ON ON VI PROGRAMMING USING THE LED KEYPAD ENTERING THE PROGRAM MODE Enters the Program Mode Stay Chime Exit Bypass Cancel LEDS will flash Go To Program Code Factory Default is If...

Страница 8: ...will flash If the location is valid the Armed LED will extinguish the Ready LED will illuminate and the zone LED s will show the data for the first segment of this location Do not enter data The next...

Страница 9: ...r Number 2 is used to program user cards so if control is an NX 4 NX 6 or NX 8 if control is an NX 8E Unit is now ready for you to choose one of the User Card Programming modes as if user code 2 Add O...

Страница 10: ...e system will be updated with the new user card information IMPORTANT NOTE Activating De activating Resetting Users If User Number 0 is entered the desired function will be performed on the user assoc...

Страница 11: ...d by the 6 function refer to keypad user manual Segment 1 Single Scan Function Program the functions that are performed when a card is scanned one beep LED1 On to send Code Entry function to the contr...

Страница 12: ...LED3 On to activate the Armed Stay mode LED4 On to send the Disarm function to the control panel LED5 On to send Auxiliary Function 1 to the control panel LED6 On to send Auxiliary Function 2 to the c...

Страница 13: ...gment 1 Option 7 is set Use the following table Default is 2 Function Function performed Function Function performed 0 All units off 4 Dim 1 All lights on 5 Bright 2 On 6 All lights off 3 Off All othe...

Страница 14: ...lt is On LED2 On if driver follows Schedule 2 Default is On LED3 On if driver follows Schedule 3 Default is On LED4 On if driver follows Schedule 4 Default is On LED5 On if driver follows Schedule 5 D...

Страница 15: ...d in 1 100 second increments from 0 to 2 55 seconds Default is 100 1 second Segment 2 Relay Active Time Enter the amount of time the onboard relay is energized once activated This timer is timed in 1...

Страница 16: ...chedule 7 Location 15 Opening Time for Schedule 4 Location 27 Opening Time for Schedule 8 Location 16 Closing Time for Schedule 4 Location 28 Closing Time for Schedule 8 Location 17 Days for Schedule...

Страница 17: ...that user card 240 is active Segment 1 User Cards 121 128 Segment 9 User Cards 185 192 Segment 2 User Cards 129 136 Segment 10 User Cards 193 200 Segment 3 User Cards 137 144 Segment 11 User Cards 20...

Страница 18: ...ARITY TYPE 1 1 segment of decimal data This location programs the Partity Type 1 for Weigand Format 1 Available options for this location are 0 No Parity 1 Odd Parity 2 Even Parity Factory default is...

Страница 19: ...EIGAND FORMAT 3 HID1000 These locations contain the programming for Weigand Format 3 Refer to the instructions for Locations 45 57 regarding the Bit Descriptors Parity Types and Parity Masks 1 5 Facto...

Страница 20: ...with the relay activation 3 On if inverted 5 8 Reserved 5 LED2 RED OPTIONS 1 On to follow Armed status of system 2 On to toggle with the relay activation 3 On if inverted 4 8 Reserved 6 8 RESERVED LO...

Страница 21: ...zone is disabled 4 Reserved 5 On if an RTE from a scanned card is to be logged as Code Entry 6 On if an RTE from a zone or the egress input is to be logged as Code Entry 7 8 Reserved 2 DOOR OPTIONS 1...

Страница 22: ...schedule is active on Tuesday 4 On if schedule is active on Wednesday 5 On if schedule is active on Thursday 6 On if schedule is active on Friday 7 On if schedule is active on Saturday 8 On if schedul...

Страница 23: ...TION 21 OPENING TIME FOR SCHEDULE 6 1 Hour of Opening 24 hr format Default 8 8 AM 2 Minutes after Hour of Opening Default 0 LOCATION 22 CLOSING TIME FOR SCHEDULE 6 1 Hour of Closing 24 hr format Defau...

Страница 24: ...Cards 25 32 25 26 27 28 29 30 31 32 5 User Cards 33 40 33 34 35 36 37 38 39 40 6 User Cards 41 48 41 42 43 44 45 46 47 48 7 User Cards 49 56 49 50 51 52 53 54 55 56 8 User Cards 57 64 57 58 59 60 61...

Страница 25: ...B 31 Bit 31 Descriptor E 16 Bit 16 Descriptor B 32 Bit 32 Descriptor E LOCATION 47 WIEGAND FORMAT 1 BIT DESCRIPTOR 33 64 0 Always Zero 1 Always One B Badge Number Bit D Parity Bit E End of Format F Fa...

Страница 26: ...B 17 Bit 17 Descriptor B 2 Bit 2 Descriptor B 18 Bit 18 Descriptor B 3 Bit 3 Descriptor B 19 Bit 19 Descriptor B 4 Bit 4 Descriptor B 20 Bit 20 Descriptor B 5 Bit 5 Descriptor B 21 Bit 21 Descriptor...

Страница 27: ...5 1 Parity Mask 1 5 Parity Mask 5 2 Parity Mask 2 6 Parity Mask 6 3 Parity Mask 3 7 Parity Mask 7 4 Parity Mask 4 8 Parity Mask 8 WEIGAND FORMAT 3 LOCATION 71 WIEGAND FORMAT 3 DIGITS BITS DECIMAL DAT...

Страница 28: ...arity Mask 4 12345678 8 Parity Mask 8 LOCATION 76 WIEGAND FORMAT 3 PARITY TYPE 2 0 No Parity 1 Odd Parity 2 Even Parity 1 Parity Type 2 1 LOCATION 77 WIEGAND FORMAT 3 PARITY MASK 2 1 Parity Mask 1 1 3...

Страница 29: ...4 Descriptor E 7 Bit 39 Descriptor E 23 Bit 55 Descriptor E 8 Bit 40 Descriptor E 24 Bit 56 Descriptor E 9 Bit 41 Descriptor E 25 Bit 57 Descriptor E 10 Bit 42 Descriptor E 26 Bit 58 Descriptor E 11 B...

Страница 30: ...r F 28 Bit 28 Descriptor B 13 Bit 13 Descriptor F 29 Bit 29 Descriptor B 14 Bit 14 Descriptor F 30 Bit 30 Descriptor B 15 Bit 15 Descriptor F 31 Bit 31 Descriptor B 16 Bit 16 Descriptor F 32 Bit 32 De...

Страница 31: ...AT 6 LOCATION 110 WIEGAND FORMAT 6 DIGITS BITS DECIMAL DATA DESCRIPTION DEFAULT DATA 1 Number of Digits in Facility Code 0 2 Number of Digits in Badge Number 11 3 Number of Bits in Facility Code 0 4 N...

Страница 32: ...345678 7 Parity Mask 7 4 Parity Mask 4 12345678 8 Parity Mask 8 LOCATION 115 WIEGAND FORMAT 6 PARITY TYPE 2 0 No Parity 1 Odd Parity 2 Even Parity 1 Parity Type 2 2 LOCATION 116 WIEGAND FORMAT 6 PARIT...

Страница 33: ...scriptor E 22 Bit 54 Descriptor E 7 Bit 39 Descriptor E 23 Bit 55 Descriptor E 8 Bit 40 Descriptor E 24 Bit 56 Descriptor E 9 Bit 41 Descriptor E 25 Bit 57 Descriptor E 10 Bit 42 Descriptor E 26 Bit 5...

Страница 34: ...E 12 Bit 12 Descriptor E 28 Bit 28 Descriptor E 13 Bit 13 Descriptor E 29 Bit 29 Descriptor E 14 Bit 14 Descriptor E 30 Bit 30 Descriptor E 15 Bit 15 Descriptor E 31 Bit 31 Descriptor E 16 Bit 16 Des...

Страница 35: ...MASK 5 1 Parity Mask 1 5 Parity Mask 5 2 Parity Mask 2 6 Parity Mask 6 3 Parity Mask 3 7 Parity Mask 7 4 Parity Mask 4 8 Parity Mask 8 X ORDERING INFORMATION PART DESCRIPTION NX 1710E Single Door Con...

Страница 36: ...00 L x 1 D OPERATING POWER 12 VDC Supplied by NX 4 NX 4V2 NX 6 NX 6V2 NX 8 NX 8V2 NX 8E or NX 320E CURRENT DRAW 40mA Standby with Green LED 110mA Maximum OPERATING TEMPERATURE 32 to 120 degrees F SHIP...

Отзывы: