NX-6V2-Control Panel

Installation Instructions

8

ANSI/SIA CP-01 requirements

CP-01 feature descriptions and specifications are listed in 

Table 7

. The following are requirements for compliance with ANSI/SIA 

CP-01 standards. 

Note:  

Where a conflict exists, UL requirements take precedence over ANSI/SIA requirements.

• Minimum system requirements: 

• One control panel 
• Two keypads 

• Do not enable remote arming in SIA classified installations.
• Off premise transmission must be in the SIA format.
• Do not exceed 1 minute for the 

abort

 window and

 entry delay

.

Note:  

A call-waiting cancel on a noncall-waiting line prevents successful connection to the central station.

 

Table 7.

CP-01 feature descriptions and specifications 

CP-01 feature description

Feature description as shown in 

manual 

Program 

location

Seg/opt

Default

CP-01 required setting

Exit time

Exit 1 delay

24

2

60

45 to 240 seconds

Exit 2 delay

24

4

60

45 to 240 seconds

Progress annunciation / disable - 

for silent exit

Silent keypad option

93 

a

a.

Refer to your keypad installation manual.

2

All annunciators 

enabled

Allowed (individual keypads 

may be disabled)

Exit time restart (reexit)

This feature is not programmable in the panel.

Enabled

Auto stay arm on unvacated 

premises

Auto bypass

23

1/3

Enabled

Enabled

Exit time and progress annuncia-

tion/disable for remote arm

This feature is not programmable in the panel. Exit time and progress are always enabled.

Enabled (disabled for remote 

arming)

Entry delays 

b

b.

Combined abort window time and entry delay must not exceed one minute.

Entry 1 delay

24

1

30

30 to 240 seconds

Entry 2 delay

24

3

30

30 to 240 seconds

Abort window - for

nonfire zones

Dialer delay

40

8

30

Enabled (may be disabled by 

zone/zone type, but no cancel 

reports will be sent)

Abort window time - for nonfire 

zones

b

Dialer delay

40

8

30

15 to 45 seconds

Abort annunciation

This feature is not programmable in the panel.   Flashing cancel LED goes off when 

disarming.

Enabled

Cancel annunciation

Cancel

23

3/6

Enabled

Enabled

Duress feature

Duress

44

Disabled

Disabled

Cross zoning

Two trips on cross zone

37

5/4

Disabled

Required

Keypad sounds on cross zone trip

39

5

Disabled

Zone type characteristic

111

3/4

Disabled

Programmable cross zoning time

Cross zone time

40

6

5 minutes

Allowed

Swinger shutdown

Swinger shutdown count

38

n/a

Enabled for 1 trip

For all nonfire zones, shut 

down at 1 to 2 trips

Swinger shutdown disable

Swinger shutdown count

38

n/a

Enabled for 1 trip

Allowed

Fire alarm verification

Fire alarm verification time

40

9

Disabled

Required (depends on panel 

and sensors)

Call waiting cancel

Must be programmed as part of the 

phone number

0

n/a

n/a

Required (depends on user 

phone line)

Default changes (from prior 

versions):

Recent closing

23

3/7

Enabled

Exit error

23

3/8 

Enabled

Power up delay

40

3

60 seconds

Technical support

888 GE Security (888.437.3287). Toll-free in the US, Puerto Rico, and Canada. 

503.885.5700 outside the toll-free area or contact your local dealer. 

www.gesecurity.com

  

   

 

Содержание NetworX NX-6V2

Страница 1: ...resistor may be required across the bell terminals when a 12 VDC siren is used If no resistor is used you may experience voltage leakage into the siren which will cause these devices to output a smal...

Страница 2: ...revious location Press the Medical key for the same location 5 To review the data in a specific location repeat the above procedure pressing but with no numeric data entry Each time you press the prog...

Страница 3: ...numerical data Use this loca tion to program the communicator format used to transmit to the receiver connected to phone 1 Refer to your central station receiver documentation to determine which form...

Страница 4: ...eless sensor missing and restore 4 Wireless sensor low battery and restore 5 Expander trouble and restore 6 Fail to communicate 7 Zone activity monitor 8 Reserved Location 18 Custom communicator forma...

Страница 5: ...d no entry or exit delay is being timed It is delayed during entry and exit delay times This zone automatically bypasses if enabled in segment 1 This zone type is used to enable the tamper on a wirele...

Страница 6: ...operate over the voltage range of 11 5 to 12 4 V Compatible listed devices special applications Bell output sirens Wheelock models NS 1215W NS 121575W NS4 1215W NS4 121575W AS 1215W AS 121575W Horn s...

Страница 7: ...e only with a Panasonic LC12V4BP or Yuasa NP4 12 battery There is a risk of explosion if the battery is replaced with an incorrect type WARNING If separate power supplies are necessary to accommodate...

Страница 8: ...are always enabled Enabled disabled for remote arming Entry delays b b Combined abort window time and entry delay must not exceed one minute Entry 1 delay 24 1 30 30 to 240 seconds Entry 2 delay 24 3...

Отзывы: