MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
3–1
MM300 Motor Management System
Chapter 3: Ethernet interface
GE
Grid Solutions
Ethernet interface
The 10/100Base-T Ethernet interface is configured as a Modbus RTU slave. The Ethernet
port has the following characteristics.
•
Configuration: setup using IP address, subnet mask, and gateway address.
•
Supported Modbus function codes: 3, 4, 5, 6, and 16.
•
Supports time/date synchronization via the Network Time Protocol (NTP).
•
Ethernet port 502.
•
Supports a maximum of 5 virtual connections.
The Ethernet interface has the same memory map layout as the serial Modbus RTU
interface.
Network Time Protocol is enabled if the NTP address is non-zero and the source is
detected.
Once connected to the source, the clock is updated every 30 seconds.
NOTE
NOTE:
If the IP address of the relay is changed for any reason, the relay must be powered down
then restarted in order for the new IP address to take effect.