CHAPTER 4: FIELDBUS INTERFACE
DEVICENET PROTOCOL
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
4–57
8.
Click the double arrow (>>)to move the MM300 from the
Available Devices
list to the
Scanlist
. Select
Major Revision
as the part of the electronic key for MM300.
9.
Double-click
MM300
in the Scanlist. The Edit I/O Parameters dialog (shown below)
appears for the MM300.
10. The I/O parameters define the configuration for the device in terms of how much and
what data the device exchanges with the 1747-SDN module. By default, the MM300
will send 38 bytes of input data and will receive 1 byte of ouput data from the poll
connection.
11. Verify that the MM300 parameters are set as shown below:
12. Click
OK
to close the MM300 Edit I/O Parameters dialog.
13. Click
OK
again.