CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
FORMAT CODES
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
2–65
Bit 27
Process ILock I Stop
Bit 28
Process ILock J Stop
Bit 29
HW Stop
Bit 30
Field Stop
Bit 31
MCC Stop
FC192
32 bits
Ctrl Element Status 2
Bit 0
Access Switch
Bit 1
Test Switch
Bit 2
Hard Wired Start A
Bit 3
Hard Wired Start B
Bit 4
Start A
Bit 5
Start B
Bit 6
Field Start A
Bit 7
Field Start B
Bit 8
Contactor A Status
Bit 9
Contactor B Status
Bit 10
Remote Reset
Bit 11
Lockout Reset
Bit 12
UV Restart
Bit 13
Pre-Contactor
Bit 14
MCC Start A
Bit 15
MCC Start B
Bit 16
Bypass Contact
Bit 17
Comm Start A
Bit 18
Comm Start B
Bit 19
Comm Stop
Bit 20
Fuse Fail Inhibit
Bit 21
Phase Reversal Inhibit
Bit 22
Low Aux Voltage Inhibit
Bit 23
UV Restart Inhibit
Bit 24
Drive Available
Bit 25
Drive Available Auto
Bit 26
Drive Available Manual
Bit 27
Reserved
Bit 28
Reserved
Bit 29
PFR Inhibit
Bit 30
PF Restart
FC193
32 bits
Ctrl Status 3 (Reserved)
FC194
32 bits
Ctrl Status 4 (Reserved)
FC212
16 bits
LCD Test Paint Color
0
None
1
Red
2
Green
3
Blue
Code
Type
Definition
Содержание Multilin MM300
Страница 4: ...MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE...
Страница 8: ...1 2 MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES...
Страница 78: ...3 2 MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE CHAPTER 3 ETHERNET INTERFACE...
Страница 154: ...4 76 MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE DEVICENET PROTOCOL CHAPTER 4 FIELDBUS INTERFACE...