2–64
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
FORMAT CODES
CHAPTER 2: RS485 INTERFACE (MODBUS RTU)
Bit 7
FLA Too High
FC188
32 bits
Message Status 2
Bit 0
Internal Temperature High
Bit 1
IO Communication Failure
Bit 2
Metering Failure
Bit 3
Order Code Error
Bit 4
Clock Error
Bit 5
Calibration Error
Bit 6
EEPROM Error
Bit 7
IO Input Read Error
Bit 8
IO 3.3V Error
Bit 9
IO 5V Error
Bit 10
IO -5V Error
Bit 11
IO Input Overvoltage
Bit 12
IO Frequency Error
Bit 13
DPRAM Error
Bit 14
System Health Error
FC189
32 bits
Message Status 3 (Reserved)
FC190
32 bits
Message Status 4 (Reserved)
FC191
32 bits
Ctrl Element Status 1
Bit 0
Any Stop
Bit 1
Thermal Inhibit
Bit 2
AutoMode
Bit 3
Manual Mode
Bit 4
AutoManualMode
Bit 5
Restart Inhibit
Bit 6
Contactor A
Bit 7
Contactor B
Bit 8
Forward Limit
Bit 9
Reverse Limit
Bit 10
Starts/Hr Inhibit
Bit 11
Time Between Inhibit
Bit 12
Level 1 Access
Bit 13
Level 2 Access
Bit 14
Level 3 Access
Bit 15
Comms Ctrl Active
Bit 16
Hard Wired Ctrl Active
Bit 17
Field Ctrl Active
Bit 18
MCC Ctrl Active
Bit 19
Process ILock A Stop
Bit 20
Process ILock B Stop
Bit 21
Process ILock C Stop
Bit 22
Process ILock D Stop
Bit 23
Process ILock E Stop
Bit 24
Process ILock F Stop
Bit 25
Process ILock G Stop
Bit 26
Process ILock H Stop
Code
Type
Definition
Содержание Multilin MM300
Страница 4: ...MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE...
Страница 8: ...1 2 MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE CHAPTER 1 COMMUNICATIONS INTERFACES...
Страница 78: ...3 2 MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE CHAPTER 3 ETHERNET INTERFACE...
Страница 154: ...4 76 MM300 MOTOR MANAGEMENT SYSTEM COMMUNICATIONS GUIDE DEVICENET PROTOCOL CHAPTER 4 FIELDBUS INTERFACE...