S1 745 Setup
745
Transformer Management Relay
Se
tpoints
http://www.GEindustrial.com/multilin
5–24
GE Multilin
S1 745 Setup
Passcode
PATH: SETPOINTS
!
S1 745 SETUP
!
PASSCODE
After installing the setpoint access jumper, a passcode must be entered (if the
passcode security feature is enabled) before setpoints can be changed. When the
745 is shipped from the factory, the passcode is defaulted to 0. When the passcode
is 0, the passcode security feature is disabled and only the setpoint access jumper is
required for changing setpoints from the front panel. Passcode entry is also required
when programming setpoints from any of the serial communication ports.
•
SETPOINT ACCESS
: This setpoint cannot be edited directly. It indicates if
passcode protection is enabled (“Read Only”) or disabled (“Read & Write”).
•
RESTRICT SETPOINT WRITE ACCESS
: This setpoint is only displayed when
setpoint write access is allowed and the current passcode is not “0”. Select Yes
and follow directions to restrict write access. This message is replaced by
ALLOW
SETPOINT WRITE ACCESS
when write access is restricted.
•
ALLOW SETPOINT WRITE ACCESS
: This setpoint is displayed when setpoint
write access is restricted. New setpoints cannot be entered in this state. To gain
write access, select “Yes” and enter the previously programmed passcode. If the
passcode is correctly entered, new setpoint entry is allowed. If there is no
keypress within 30 minutes, setpoint write access is automatically restricted. As
an additional safety measure, the
SELF-TEST ERROR: Access Denied
message
is generated when the passcode is entered incorrectly three consecutive times.
•
CHANGE PASSCODE
: Select “Yes” and follow directions to change the current
passcode. Changing the passcode to the factory default of “0” disables the
passcode security feature.
•
ENCRYPTED PASSCODE
: If the programmed passcode is unknown, consult
the factory service department with the encrypted passcode. The passcode can
be determined using a deciphering program.
Preferences
PATH: SETPOINTS
!
S1 745 SETUP
!"
PREFERENCES
Some relay characteristics can be modified to accommodate the user preferences.
This section allows for the definition of such characteristics.
•
FLASH MESSAGE TIME
: Flash messages are status, warning, error, or
information messages displayed for several seconds, in response to certain key
presses during setpoint programming. The time these messages remain on the
display, overriding the normal messages, can be changed to accommodate
different user reading rates.
!
PASSCODE
[
!
]
SETPOINT ACCESS:
Read & Write
Range: 1 to 8 numeric digits
MESSAGE
RESTRICT SETPOINT
WRITE ACCESS? No
Range: No, Yes
MESSAGE
ALLOW SETPOINT
WRITE ACCESS? No
Range: No, Yes
MESSAGE
CHANGE PASSCODE?
No
Range: No, Yes
MESSAGE
ENCRYPTED PASSCODE:
AIKFBAIK
Range: Factory Default Passcode is "0"
!
PREFERENCES
[
!
]
FLASH MESSAGE TIME:
4.0 s
Range: 0.5 to 10.0 s in steps of 0.5
MESSAGE
DEFAULT MESSAGE
TIMEOUT: 300 s
Range: 10 to 900 s in steps of 1
Содержание Multilin 745