S4 Elements
745
Transformer Management Relay
Se
tpoints
http://www.GEindustrial.com/multilin
5–66
GE Multilin
c) Negative Sequence Instantaneous Overcurrent
PATH: SETPOINTS
!"
S4 ELEMENTS
!"
NEG SEQ OC
!"
W1(3) NEG SEQ INST OC
•
W1(3) NEG SEQ INST OC PICKUP
: Enter the level of negative sequence
current (in units of relay nominal current) above which the Winding 1(3)
Negative Sequence Instantaneous Overcurrent element will pickup and start the
delay timer.
•
W1(3) NEG SEQ INST OC DELAY
: Enter the time that the negative sequence
current must remain above the pickup level before the element operates.
FIGURE 5–28: Negative Sequence Instantaneous Overcurrent Logic
Frequency
a) Main Menu
PATH: SETPOINTS
!"
S4 ELEMENTS
!"
FREQUENCY
The 745 can be used as the primary detecting relay in automatic load shedding
schemes based on underfrequency. This need arises if, during a system disturbance,
an area becomes electrically isolated from the main system and suffers generation
deficiency due to loss of either transmission or generation facilities. If reserve
generation is not available in the area, conditions of low system frequency occur
!
W1 NEG SEQ
[
!
]
INST OC
W1 NEG SEQ INST OC
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
W1 NEG SEQ INST OC
TARGET: Latched
Range: Self-Reset, Latched, None
MESSAGE
W1 NEG SEQ INST OC
PICKUP: 10.00 x CT
Range: 0.05 to 20.00 x CT in steps of
0.01
MESSAGE
W1 NEG SEQ INST OC
DELAY:
0 ms
Range: 0 to 60000 ms in steps of 1
MESSAGE
W1 NEG SEQ INST OC
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled
!
FREQUENCY
[
!
]
!
UNDERFREQUENCY
[
!
]
1
MESSAGE
!
UNDERFREQUENCY
[
!
]
2
MESSAGE
!
FREQUENCY
[
!
]
DECAY
MESSAGE
!
OVERFREQUENCY
[
!
]