QUICK REFERENCE GUIDE
SYSTEM DATA
469 MOTOR MANAGEMENT RELAY – QUICK REFERENCE GUIDE
59
UNDERVOLTAGE TRIP PICKUP
: “0.8 x RATED”
STARTING U/V TRIP PICKUP
: “0.7 x RATED”
UNDERVOLTAGE TRIP DELAY
: “13.0 s”
12.17 Installation:
Now that programming for the sample application is complete, the relay should be in the
Service state. Note that the relay is defaulted to the Not Ready state when it leaves the
factory. A minor self-test warning message informs the user that the 469 Motor
Management Relay has not yet been programmed. If this warning is ignored, protection
will be active, using factory default setpoints. The Relay In Service LED Indicator will be on.
By now, once you have completed all the steps illustrated on this typical example, you
should be able to set the GE Multilin 469 Motor Management relay for a typical feeder
application.
For further technical support, and additional documentation on this, and other GE Multilin
products, please contact us at:
215 Anderson Avenue
Markham, Ontario L6E 1B3
Canada
Telephone: (905) 294-6222
Fax: (905) 201-2098
E-mail: [email protected]
Internet: http://www.GEmultilin.com