48
469 MOTOR MANAGEMENT RELAY – QUICK REFERENCE GUIDE
SYSTEM DATA
QUICK REFERENCE GUIDE
12.5
Control System Requirements
•
All protection elements used are to trip the breaker.
•
Breaker position monitoring via 52b contact only.
•
Only current metering is required.
•
Serial Communication Remote START from RTU.
•
Alarm after 100 s delay from station monitor. This is normally used to signal the
remote center when someone has gained access to the Substation.
12.6
Contact Outputs
•
Trip and close to breaker control circuit (Trip and Auxiliary2 relays).
•
Relay failure alarm to RTU (self-test warning relay, no programming required)
•
Alarm contact (setup in General Sw. A for “Station Monitor”)
•
No data communications to other equipment.
12.7
RTDs
The motor is fitted with the following RTDs:
•
RTD Type: 100
Ω
Platinum
•
6 Stator RTDs, 2 per phase
•
2 Bearing RTDs
•
1 Ambient RTD
The above data will be used to set the output relays to achieve breaker control by setting
digital inputs for breaker status, remote operations, remote status, and alarm indication.
The example assumes that the communications between the station and the Master
Control center will be done by the RTU. Alarms, status indication, and breaker commands
will be hardwired from the relay to the RTU. Similar information could be exchanged
between the RTU and the relay via an RS485 or RS422 Serial Link using Modbus RTU
protocol. Refer to GE Publication GEK-106491: 469 Communications Guide for additional
information.
12.8
Instrument Transformer Data
Voltage Transformers:
3 × Delta connected, ratio = 600:120 V
Motor System Voltage = 575 V
Phase CTs:
The phase CT should be chosen such that the FLC is 50% to 100% of CT primary. Since the
FLC is 347.5A a 350:5 or 400:5 CT may be chosen; 400:5 is a standard available size and so
would probably be selected.
Содержание Multilin 469
Страница 2: ......
Страница 64: ...60 469 MOTOR MANAGEMENT RELAY QUICK REFERENCE GUIDE SYSTEM DATA QUICK REFERENCE GUIDE ...