6.4 SUMMARY OF SETTINGS
Following, is a table containing a summary of all the settings of the MLJ relay. In addition to the
description and the setting code, the allowable values, step and default value (the value the relay
comes with from the factory) are indicated. In the right-hand column, SETTING, a blank space is left so
that the user may note the value the relay has been set at.
TABLE 1 MLJ SETTINGS
SETTING NAME
RANGE
STEP
DEFAULT
SETTING
GENERAL
0-1 Frequency
50/60 Hz
N.A.
50 Hz
PROTECTION
1-1 Voltage difference
2-90 V
0.5 V
15 V
1-2 Angle
2-60º
1º
10º
1-3 Frequency slip
10-500
mHz
10 mHz
20 mHz
1-4 Continuous mode timing
0.1-99-0 s
0.1 s
0.1 s
1-5 Manual mode timing
0.1-99-0 s
0.1 s
10.1 s
2-1 Voltage supervision enable
OFF-ON
N.A.
OFF
2-2 Voltage supervision threshold
10-180 V
1 V
40 V
3-1 Level present of voltage in line (V
L
↑
)
40-245 V
1 V
50 V
3-2 Level absent of voltage in line (V
L
↓
)
10-180 V
1 V
30 V
3-3 Level present of voltage in bus (V
B
↑
)
40-245 V
1 V
50 V
3-4 Level present of voltage in bus (V
B
↓
)
10-180 V
1 V
30 V
4-1 Synchronism unit enable
OFF-ON
N.A.
OFF
4-2 (DLDB) dead line and bus enable
OFF-ON
N.A.
OFF
4-3 (DLLB) dead line live bus enable
OFF-ON
N.A.
OFF
4-4 (LLDB) live line dead bus enable
OFF-ON
N.A..
OFF
5-1 Configuration 1st auxiliary output
see table 2 N.A.
25
5-2 Configuration 2nd auxiliary output
see table 2 N.A.
27
COMMUNICATIONS
6-1 Unit number
1-255
1
1
6-2 Serial port baud-rate (kilobauds)
0.3-38.4
N.A.
9.6
Содержание MLJ1000
Страница 36: ...GEK 105560 35 Figure 1 Logical diagram of Operation 226B2202H2...
Страница 37: ...GEK 105560 36 Figure 2 Nameplate 226B1276H1...
Страница 38: ...GEK 105560 37 Figure 3 Outline and panel drilling 226B6086H1...
Страница 39: ...GEK 105560 38 Figure 4 Rear terminal plate 226B3205H1...
Страница 41: ...GEK 105560 40 Figure 6 Internal settings 301A7408H1...
Страница 42: ...GEK 105560 41 Figure 7 Block Diagram 226B2201H1...