GEK - 105560
30
Going to settings sequence
Going to readout sequence
Note: N.A. Not applicable
TABLE 2 CONFIGURATION OF OUTPUTS
FUNCTION NAME
FUNCTION OPERATION
PEr
Close enable
25
Synchronism
27
Undervoltage
_dL
Dead line
db_
Dead bus
F25
Fail to close
ALA
Alarm
If while in Readout Sequence, the ENTER and “+” buttons, are pressed simultaneously, the word CAL
will appear briefly on the screen, followed immediately by the average value of the line and bus
voltages.
By applying a known voltage, for example 60 RMS, to both the line and bus inputs, the trimmer is
adjusted (see figure 5) until a reading of 60.0 on the display is obtained.
If we now press the ENTER button for a moment, we return to Readout Sequence.