VECTOR V1100 Wireless Adapter
32
GE Oil & Gas
ALERT – Watchdog Reset
Description
:
The microprocessor inside of the VECTOR V1100 has experienced a watchdog reset event.
Corrective Action
:
Clear the alert – report the event.
Timestamps
:
Start: Set when the alert is first detected.
Stop: Not Used
ALERT – Stack Overflow
Description
:
The microprocessor inside of the VECTOR V1100 has experienced a stack overflow event.
Corrective Action
:
Clear the alert – report the event.
Timestamps
:
Start: Set when the alert is first detected.
Stop: Not Used
ALERT – Duplicate HART Master Detected
Description
:
A HART Master has been detected that is configured as the same Master type as the VECTOR
V1100. This prevents the VECTOR V1100 from communicating with connected sub-devices
while the other HART master is present.
Corrective Action
:
If there is another HART Master present, ensure that it and the VECTOR V1100 are configured
for different HART Master types. When using a HART Handheld, ensure that it is not set for the
same Master Type as the VECTOR V1100.
Timestamps
:
Start: Set the first time the duplicate HART Master was detected.
Stop: Set the last time the duplicate HART Master was detected.
Содержание Masoneilan VECTOR V1100
Страница 6: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 37: ...37 HART DD Menu Tree Figure 2 DD Menu Tree ...
Страница 38: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 48: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 50: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 57: ...57 Mechanical Dimensional Drawing Dimensions are in inches millimeters Figure 10 VECTOR Dimensions ...
Страница 58: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 59: ......