27
It this is set to Special Curve, you can enter in data pairs (a loop current value to a
engineering unit value) into the PV Linearization Table. The table needs to have at least two
data pairs and can have up to 32 pairs. When converting the loop current to engineering
units, the VECTOR V1100 uses this lookup table to perform a more accurate linearization.
PV Damping Value
This is the damping value in seconds that is applied to the PV measurement.
PV Upper Range Value (20 mA)
When the Linearization Mode is set to Linear, this is the value in engineering units that
corresponds to the loop current at 20 mA.
PV Lower Range Value (4 mA)
When the Linearization Mode is set to Linear, this is the value in engineering units that
corresponds to the loop current at 4 mA.
Upper Fault Current
This is the value of the loop current in milliamps that above which sets a HART loop current
alarm.
Upper Limit of Proportional Range
This is the value of the loop current in milliamps that above which sets a HART loop current
warning.
Lower Limit of Proportional Range
This is the value of the loop current in milliamps that below which sets a HART loop current
warning.
Lower Fault Current
This is the value of the loop current in milliamps that below which sets a HART loop current
error.
Содержание Masoneilan VECTOR V1100
Страница 6: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 37: ...37 HART DD Menu Tree Figure 2 DD Menu Tree ...
Страница 38: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 48: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 50: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 57: ...57 Mechanical Dimensional Drawing Dimensions are in inches millimeters Figure 10 VECTOR Dimensions ...
Страница 58: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Страница 59: ......