8.9.1
Communication Errors
When firmware and application is downloaded to an I/O module, it can take several minutes to install, restart, and re-establish
communication to the Mark VIe controller. If the ATTN LED is red and flashing at 2 Hz 50%, the IP address has not been
received from the controller. For information on ATTN LED flash codes, refer to the Help file for the specific I/O module and
the section
Diagnostics
.
•
Verify that the terminal board bar code configured in the ToolboxST configuration matches the actual hardware.
•
Verify that the terminal board type, including
HW Form
, in the ToolboxST configuration matches the terminal board in
the actual I/O module.
•
Verify that the network cables and switches to the I/O module are plugged in correctly, and that the Link and Activity
LEDs are active.
➢
➢
To view more troubleshooting information:
from the
Diagnostics
tab, select each diagnostic alarm and press
F1
.
190
GEH-6721_Vol_I_BP
GEH-6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I
Public Information
Содержание Mark VIe
Страница 61: ...Example UCSx Controller Label Control System Overview GEH 6721_Vol_I_BP System Guide 61 Public Information ...
Страница 66: ...Notes 66 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 74: ...Notes 74 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 116: ...Notes 116 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 164: ...Notes 164 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 198: ...Notes 198 GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 201: ......
Страница 202: ...Public Information ...