Perform the following troubleshooting steps if needed:
•
It is not possible to connect to the designated controller if the controllers are set in the dc determination state. Going
online with each individual controllers is required.
•
The ToolboxST application may not display any information in the
Status
tab for the faulty Mark VIe control if it is set
in the
Power on/d0-MASTER_INITIALIZATION
state. The other two controllers are suspended at
d1-State Designated
Controller Determination
state.
•
If the controller halts before d0-MASTER_INITIALIZATION (at power on state), the problem could be with the
controller. If the controller halts at d0-MASTER_INITIALIZATION state, the controller may have lost its IP address.
•
If the controllers halt at the d1-dc_DETERMINATION state, one of the controllers may be unable to communicate to
either IONet 1, 2, or 3 port.
•
If all the controllers halt at the d3-INPUTS_ENABLED state, at least one of the I/O modules configured as a required
module may not be communicating with the controllers.
Troubleshooting
GEH-6721_Vol_I_BP System Guide 183
Public Information
Содержание Mark VIe
Страница 61: ...Example UCSx Controller Label Control System Overview GEH 6721_Vol_I_BP System Guide 61 Public Information ...
Страница 66: ...Notes 66 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 74: ...Notes 74 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 116: ...Notes 116 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 164: ...Notes 164 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 198: ...Notes 198 GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 201: ......
Страница 202: ...Public Information ...