background image

RATINGS 

The  operating  and  restraining  coils  are  con­

tinuous  rated. 

The  tap  setting  used  on  the seal­

in  unit 

is  determined  by  the  current  drawn  by 

the  contact  circuit. 

The  0. 2-ampere  tap  is  for  use  with  circuits 

that  operate  on  currents  ranging  from  0.2  up  to 

2 . 0   amperes  at  the  minimum  control  voltage. 

If 

this  tap  is  used  with  circuits  requiring  more  than 

2  amperes  there  is  a  possibility  that  the  7-ohm 

resistance  will  reduce  the  current  to  so  low  a 

value  that  the  proper  current  may  not  be obtained. 

The 2 .0-ampere tap should  be used with circuits 

that  take  2.0  amperes  or  more  at  minimum  con­

trol  voltage,  provided  the  current  does  not  exceed 

30  amperes  at  the  maximum  control  voltage. 

If 

the  current  exceeds  3 0   a mperes an auxiliary relay 

should  be  used,  the  connections  being  such  that 

the  current  does  not  pass  through  the  contacts 

or  the  target  and  seal-in  coil  of  the  protective 

relay. 

The  current-closing  rating  of  the  contacts  is 

30  amperes  for  voltages  not  exceeding  250  volts. 

The  current  carrying  ratings  are  affected  by  the 

selection  of  the  tap  on the seal-in  coil  as  indicated 

in  the following table: 

Target and  Seal-in  C oil 

Amperes,  A-C or  D-C 

Function 

2-Amp  Tap 

(0. 1 3  ohm) 

0. 2-Amp  Tap 

(7 ohms) 

Momentary  Duty 

30 

Carry  Continuously 

BURDENS 

Burdens  for  the  Type 

IJS 

relays  are  listed 

below.  The  burden 

for 

each circuit varies , depending 

upon  the  phase  displac ement 

of 

the  two  voltages, 

from  a  minimum  at  0  degree  displacement  to  a 

maximum  near  180 degrees  displacement. 

CYCLES 

CIRC UIT 

5-6 

5-6 

1 1 5  

60 

7-8 

7-8 

5-6 

1 1 5  

50 

5-6 

7-8 

7-8 

Synchronism-Check Relays  Type  LJS  GEH- 1791 

CONSTRUCTION 

The  relay  components  are  mounted in  a  cradle 

assembly  which  is  latched  into  a  drawout  case  when 

the  relay  is  in  operation  but  they  can  be  easily 

removed  when  desired. 

To  do  this,  the  relay  is 

first  disconnected  by  removing  the  connection plug 

which  completes  the  electrical  connections  between 

the  case  blocks  and  the  cradle  block.  To test the 

relay  in  its  case  this  connection  block  can  be 

replaced by a  test plug.  The cover, which is attached 

to  the  front  of  the  relay  case,  contains  an inter­

lock  arm  which  prevents  the  cover  from  being 

replaced  until  the  connection  plugs  have  been  in­

serted. 

The  relay  case  is  suitable  for  either  semi­

flush  or  surface  mounting  on  all  panels  up  tc,  2 

inches  thick  and appropriate  hardware  is  available. 

However,  panel  thickness  must  be  indicated on the 

relay  order  to  insure  that  proper  hardware  will 

be  included.  For  outline  and  drilling  dimensions, 

see  Fig.  14. 

RECEIVING,  HANDLING  AND 

STORAGE 

These  relays,  when  not  included  as  part  of  a 

control  panel,  will  be  shipped  in  cartons  designed 

to  protect  them  against  damage.  Immediately upon 

receipt  of  a  relay,  examine  it  for  any  damage 

sustained  in  transit. 

If 

injury  or  damage resulting 

from  rough handling is  evident,  file a  damage  claim 

at  once  with  the transportation company and promptly 

notify  the nearest General  Electric  Apparatus  Sales 

Office. 

Reasonable  care  should  be  exercised  in  un­

packing  the  relay. 

If 

the  relays  are  not to be 

installed immediately,  they should be stored in their 

original  cartons  in  a  place  that  is  free  from 

moisture,  dust,  and metallic  chips.  Foreign  matter 

collected  on  the  outside  of  the  case  may  find its 

way  inside  when  the  cover  is  removed  and  cause 

trouble in  the operation  of  the  relay. 

ACCEPTANCE  TESiZi 

Immediately  upon  receipt  of  the  relay,  an 

inspection  and  acceptanc e   test  should  be  made  to 

insure  that  no  damage  has been sustained in shipment 

and  that  the  relay  calibrations  have  not  been  dis-

PHASE 

VOLTS 

WATTS 

P . F. 

DIFF. 

AMPS 

oo 

3 . 00 

1 1 . 6  

0.258 

1 80° 

3.76 

1 2 . 0  

0.3 13 

oo 

3 . 3 0  

1 0.9 

0.300 

1 80° 

4.07 

1 1 .3 

0.360 

oo 

4.35 

14.2 

0.306 

180° 

5.25 

14.6 

0.359 

oo 

4.75 

1 3 . 3  

0.357 

180° 

5.60 

13.9 

0.403 

www 

. ElectricalPartManuals 

. com 

Содержание IJS51A

Страница 1: ...Types IJS51A and IJS52A INSTRUCTIONS SYNCHRONISM CHECK RELAYS GEH 179111 GE Meter and Control 205 Great Valley Parkway Malvern PA 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...ENS 6 CONSTRUCTION 6 RECEIVING HANDLING AND STORAGE 6 ACCEPTANCE TESTS 7 INSTALLATION PROCEDURE 7 PERIODIC CHECKS AND ROUTINE MAINTENANCE 8 SERVICING 9 Closing Angle Adjustment 9 Time Characteristics 10 RENEWAL PARTS 10 Cover Photo 8007016 2 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 3: ... be considerably out of phase due to load transfer around the loop that is open at the breaker controlled by the relay Forms of the relay are available with a rated calibration range up to 600 but for settings over 200 consideration should be given to the resulting generator stresses at the instant of closure through existing system impedances as in any other situation involving out of phase closu...

Страница 4: ...le is considered standard however other settings may be made as indicated by the voltage phase angle characteristics shown in Figure 1 The time delay characteristics of the Type IJS relay are obtained primariy by the time dial setting The time dial controls the distance the contacts must travel before closure and hence controls the time delay At No 10 time dial setting the travel is maximum wherea...

Страница 5: ... from 0 2 up to 2 0 amperes at the minimum control voltage If this tap is used with circuits requiring more than 2 amperes there is a possibility that the 7 ohm resistance will reduce the current to so low a value that the proper current may not be obtained The 2 0 ampere tap should be used with circuits that take 2 0 amperes or more at minimum control voltage provided the current does not exceed ...

Страница 6: ...e connection plugs have been inserted The relay case is suitable for either semi flush or surface mounting on all panels up to 2 inches thick and appropriate hardware is available However panel thickness must be indicated on the relay order to ensure that proper hardware will be included For outline and drilling dimensions see Figure 15 RECEIVING HANDLING AND STORAGE These relays when not included...

Страница 7: ...tact when the time dial is set at 0 The contact wipe should be approximately 1 3211 3 Check that the control spring is not deformed and that the spring convolutions at No 5 time dial setting are reasonably concentric ELECTRICAL TESTS Connect the relay as shown in Figure 11 and check the following 1 Check that with at least 115 volts 60 cycle single phase source connected to both operating coils th...

Страница 8: ...o studs 5 6 is adjusted until the synchronizing check unit just closes its contact The difference between the two voltages should agree approximately with the voltage given on the curve shown in Figure 14 for the phase angle used i e 24 volts for 200 closing When using connections shown in either Figure 11 or Figure 13 check the operating time at 0 displacement with 115 volts on each coil using th...

Страница 9: ...hould be approximately centered between the poles of the U magnet and drag magnet ELECTRICAL ADJUSTMENTS Closing Angle Adjustment Connect the relay as shown in Figure 11 To make an accurate adjustment of the closing angle a phase shifter and phase angle meter are required along with a means for voltage control Two adjustments are necessary for obtaining a desired closing angle adjustable resistor ...

Страница 10: ...ficient quantities of renewal parts should be kept in stock for the prompt replacement of any that are worn broken or damaged When ordering renewal parts address the nearest Sales Office of the General Electric Company Specify the name of the part wanted quantity required and complete nameplate data including the serial number of the relay If possible give the General Electric requisition number o...

Страница 11: ...nts with Rated Voltage Maintained on One Circuit CONNECTING PLUG AUXIL IARY BRUSH BLOCK TERMINAL BLOCK SHORTING BAR NOTE AF TER ENGAG ING AUXIL IARY BRUSH CONNECTING PLUG TRAVELS 1 4 INCH BEFORE ENGAG ING THE MAIN BRUSH ON THE TERMINAL BLOCK Figure 2 8025039 Cross Section of Drawout Case Showing Position of Auxiliary Brush and Shorting Brush 11 w w w E l e c t r i c a l P a r t M a n u a l s c o m...

Страница 12: ...ic of 60 Cycle Relay 12IJS51A1 With Rated Voltage On Both Circuits With 10 Time Dial Settings Figure 4 8007013 Type IJS51A Relay Unit in Cradle Rear View 9 1 8 1 u J en _ 7 w I 6 0 0 0 0 0 0 50 en 0 z 8 4 w en w 3 I z 2 w a 0 0 0 0 10 0 I i I I c I i lfzo CLOSING ANGLE i I J30 CLOSING ANGLE i I I I j 1 l I u 4 0 gw G v 1 v I i f I f i 1 v J I I v I __ _ V 6oo CLOSING ANGLE i J I 50 40 30 20 10 0 1...

Страница 13: ...age on Both Circuits With 10 Time Dial Settings Sl OUND _j SHADING COILS t l I 1 2 l l 5 6 l 7 I8 OOT REST SHORT F I NGER Figure 9 6305898 3 Internal Connec tions For Type IJS51A Relay Front View I 20 16 12 V 0 0 u I II 8 v 4 v ov 2 i 1 I v I v I v I I I 4 6 TilliE DIAl SETTING i v v 8 10 Figure 8 6400150 2 Operating Time of Type IJS Relay With 200 Closing Angle Time at oo 115 Volts 60 Cycles on B...

Страница 14: ... G CIRCUIT OF oi Hl DEVICE FUNCTION NUMBERS 25 SYNCHRONISM CHECK RE LAY TYPE IJS 278 BUS UNDERVOLTAGE RELAY TYPf HGA14AR 27L LINE UNDERVOLTAGE RELAY TYPF fjGA14AR 52 POWER CIRCUIT BREAKER 52C S CONTROL S ITCH TYPE SB 1 Figure 12 6209561 5 Typical Elementary Diagram of External Connections Type IJS Relays 100 l 90 v i 80 70 I i 0 u 7 t 60 c I __ z I 0 u 50 I 0 _ 1 40 r f 7 I I f __ ll 30 i 20 0 N 7...

Страница 15: ...6MM 4 375T 111MM _L__ l I CUTbUT I I I I I 5 687 144MM 112MM j_ 8 81 223M 2 M I 2 18 r 5MM I I PANEL I FOR PANEL DRILLING SEMI FLUSH MOUNTING FRONT VIE 718 1 8MM TYPICAL DIM 3 0 I 76MM 3 4 DRILL 10 HOLES 19MM PANEL DRILLING FOR SURFACE MOUNTING FRONT VIEW 5 16 18 STUD INCHES MM VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MTG ON STEEL PANELS Figure 15 6209271 8 Outline and Panel Drilling Dimensio...

Страница 16: ...ST 9 93 200 16 Meter and Control Business Department General Electric Company Protection and Control 205 Great Valley Parkway Malvern Pennsylvania 19355 0715 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 17: ...INSTRUCTIONS GEH 1791 E Supersedes GEH 1791 D SYNCHRONISM CHECK RELAYS TYPES IJS51A AND IJS52A GENERAL fj ELECTRIC w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...llel with those of the GES or GXS The IJS is not adaptable to applications in volving continuous loading of the contact circuit since contact welding may result even with contact loadings that are low in relation to the interrupting capacity of the contacts The control should be designed to energize the IJS coils when synchronism is to be checked and to permit the IJS contacts to be the last to co...

Страница 20: ...it energized varies from 3 seconds on the 20 degree setting to 6 seconds on the 6 0 degree setting at the 10 TDS The Model 12IJS51A3 and 12IJS52A7A relays which are designed for use where the closing angle greater than 20 degrees is required provides 20 seconds delay at the 40 degree closing angle setting as shown in Fig 5 It may be adjusted to other closing angles between 20 and 60 degrees with c...

Страница 21: ...Type IJS51A Relay Unit In Cradle Rear View z 9 8 1 w _ 7 Cl Cl z 0 4 u w 3 1 z 2 w 0 0 I 0 I i i 0 0 t t 0 I r I o I l r 0 1 r 0 r r r TTI i I t __j_ ll I I 1 I i I 1 I i i li I i l c u20 CLOSING ANGLE t I I 1 r 1 30 CLOSING ANGLE i lJ I v J I v l _J I I I I I 40 CLOSING ANGLE I i I I I II i I v T I I I H vv l 600 jI I j j J I V CLOSING I ANGLE I I i I I i 50 40 30 20 10 0 10 20 30 40 50 PHASE ANG...

Страница 22: ... SHADING_j l t COILS 1 l I l 1 s v i I 6 TOP RfST l l i l8 BOT REST SHORT FINGER it 8 6305ScJ8 3 Intt mal Connections Fo r Type LTS lA Relay Front View V 0 z o VJ I w 20 1 1 c I f I I lb r 1 i 1 I 12 I r t I I I I 4 rr l t t A 1 I I r J I 1 I _____J_ 4 t r _j I I I I I j tT j I 4 6 10 TIME QiAL SUTING Fig 7 6400150 2 Operatine I ime o Type IJS Relay With 2JO Closing Angle Time At 0 115 Volts 60 Cy...

Страница 23: ...esired To do this the relay is first disconnected by removing the connection plug which completes the electrical connections between the case blocks and the cradle block To test the relay in its case this connection block can be replaced by a test plug The cover which is attached to the front of the relay case contains an inter lock arm which prevents the cover from being replaced until the connec...

Страница 24: ...tion A typical elementary diagram of external con nections is shown in Fig 11 The B contact of 52 in series with only one coil circuit serves to reset the disk and contacts promptly after the circuit breaker closes so that the normal delay is avail able as soon as possible in case the breaker trips again Additional relays undervoltage or reclosing may be considered desirable for prevention of unli...

Страница 25: ...C H E C K R E L A Y T Y P E I J I 2 7 8 BUS U N O E RV O L T AGE R E L A Y T Y PF H A14AR 2 7 L L r N E U N OERVO L T A G E R E L A Y r T Y P flGA 4A l 5 2 POW E R C I RC U I T B R E A KE R 5 Z C S CO N T RO L W I TC H T Y P E 58 l Fig 11 6209561 4 Typical Elementary Diagram Of External Connections Type IJS Relays 100 T I 90 1 80 70 u I 60 1 II 1 I 0 u 50 1 I 5 1 4 0 I l 7 1 3 0 1 f7 I I 20 i 10 I...

Страница 26: ...en the poles of the U magnet and drag magnet ELECTRICAL ADJUSTMENTS Closing Angle Adjustment Connect the relay as shown in Fig 10 To make an accurate adjustment of the closing angle a phase shifter and phase angle meter are required along with a means for voltage control Two adjustments are necessary for obtaining a desired closing angle The right hand adjustable resistor at the top of the frame p...

Страница 27: ...12 223M M 1 5 M M DRI LL El 2 H OLES CUTOUT M AY R EPLACE D R ILLED H OLES O PT I ONAL 2 M M 1 1 6 __ L 7 1 ts Tt tttl t S t3 VIEW SHOWING t8 t A t A ASSEME Y OF HARDwA RE FOR SU RFACE MTG 0 N STEEL PA N EL5 PANEL DRIWNG F SEM J FWSH MOUN TI NG t F RONT VIE W DR I L L 1 0 HOLES 19M M PANEL ORI LUNG FOR 9JRFACE OUNTI NG TF RONT V IE W F i g 14 6 2092 7 1 6 Ou tl i ne And Pa ne l Dr i l l i ng Dimen...

Страница 28: ...N ERA L ELECT R I C COMPANY P O W E R SYST E M S M A N A GEMENT BU SINESS DEPT P HILADELPHIA P A 1 91 4 2 G E N E R A L f j E L E C T R I C 5 80 1 0 6 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: