background image

GEK-49865 

TIME  OVERVOLTAGE  RELAYS 

TYPES 

IFV51AD 

IFV71AD 
IFV71BD 

DESCRIPTION 

The  IFV51AD, 

IFV71AD  and 

IFV71BD  rel ays  are  singl e-phase,  vol tage-operated, 

induction  disk  relays  with  adjustabl e  time  del ay. 

The  I FV71BD  relay  contains  an 

instantaneous  vol tage-operated  unit  in  addition  to  the  induction  disk  unit. 

The  induction  disk  unit  in  the  I FV71AD  and  I FV71BD  relays,  and  the  instantaneous 

unit  in  the  IFV71BD  rel ay  are  frequency  compensated.  The  pickup  o f   these  units  will 

remain  within  7.5%  o f   the  pickup  setting  at  the  rated  system  frequency  over  the 

range  o f   50%  to  150%  o f   system  frequency. 

Each  relay  contains  a  target  seal -in  unit  that  operates  in  conjunction  with  the 

associated  disk  unit.  The  target  seal-in  unit  has  two  electrically-separate  sets  o f  

normally-open  contacts. 

One  set  o f   contacts  is  connected  in  parallel  with  the 

contacts  o f   the  disk  unit,  to  protect  them  and  their  associated  control  spring.  The 

second  set  o f   contacts  is  brought  out  o f   the  relay  through  a  separate  pair  o f   studs. 

This  set  o f   contacts  may  be  used  for  monitoring  or  to  sound  an  alarm,  but  they  are 

not  suitabl e  for  use  as  the  initiating  contact  in  any  circuit  because  they  vdl l 

operate  only  after  the  contacts  o f   the  d isk unit  have  closed. 

The  instantaneous  unit  in  the  IFV71BD  relay  has  two  electrically-separate  sets  o f  

normal l y-open  contacts. 

These  contacts  will  close  when  the  instantaneous  unit 

operates,  and  they  may  be  used  to  initiate  tripping,  to  sound  an  alarm,  or  to 

monitor  operation  o f   the  unit. 

The  instantaneous  unit  has  a  self-contained  target 

that  will  show  after  the  unit  has  opera ted. 

Each  relay  is  mounted  in  a  standard  C1-size  drawout  case,  the  outl ine  and  panel 

drill ing  dimensions  for  which  are  shown  in  Figures  15  and  16. 

Internal  connections 

for  the  relays  are  shown  in  Figures  3,  4  and  5.  Typical  external  connections  are 

shown  in  Figures  6  and  7. 

APPL ICATION 

The  IFV51AD,  IFV71AD  and  IFV71BD  relays  are  single-phase,  voltage-operated  relays 

that  may  be  used  for  the  protection,  or  time  control,  o f   circuits  where  overvoltage, 

or  the  sudden  presence  o f   voltage,  is  the  controlling  factor. 

These  instructions  do  not  purport  to  cover  all  details  or 

variations  in 

equipment 

nor  to  provide  for 

every  possible  contingency  to  be  met  in  connection  with 

in

s

ta

lla

t

i

o

n

operation 

or 

maintenan�•: 

Should 

further  information  be  desired  or  should  particular  problems  arise  which  are 

not  covered  suff1c1entlg  for 

the  purchaser's  purposes,  the  matter  should  be  referred 

to  the  General 

Electric  Company. 

To  the  extent  required  the  products  described  here

in 

meet 

applicable  ANSI, 

IEEE  and 

NEMA 

standards! 

but  no  such  assurance  is  given  with  respect  to  local  codes  and  ordinances  because  they 

vary  greatly. 

www 

. ElectricalPartManuals 

. com 

Содержание IFV51AD

Страница 1: ...TYPES IFV51AD IFV71AD IFV71BD INSTRUCTIONS TIME OVERVOLTAGE RELAYS GENERAL f ELECTRIC GEK 49865A Supersedes GEK 49865 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...ckup and Dropout Test High Seismic Instantaneous Unit INSTALLATION Installation Tests Time Overvoltage Unit High Seismic Target and Seal in Unit High Seismic Instantaneous Unit PERIOD IC CHECKS AND ROUTINE MAINTENANCE Time Overvoltage Unit High Seismic Target and Seal in Unit High Seismic Instantaneous Unit Contact Cleaning System Test SERVICING Time Overvoltage Unit Pickup Tests Time Tests Mechan...

Страница 3: ...ay has two electrically separate sets of normal l y open contacts These contacts will close when the instantaneous unit operates and they may be used to initiate tripping to sound an alarm or to monitor operation of the unit The instantaneous unit has a self contained target that will show after the unit has operated Each relay is mounted in a standard C1 size drawout case the outline and panel dr...

Страница 4: ...e Ohms 68 6 0 73 HIGH SE ISMIC INSTANTANEOUS UNIT The instantaneous unit is frequency compensated over the range o f 50 to 150 of system frequency There are two ranges available 120 200 and 180 300 that are continuously adjustable by means o f a potentiometer located in the rear o f the relay CONTACTS The current closing rating o f the contacts is 30 amperes for voltages not exceeding 250 volts Th...

Страница 5: ...32 0 36 0 85 144 2 20 0 36 0 79 1 4 2 18 0 36 0 78 185 2 15 0 37 0 80 211 2 13 0 39 0 83 250 2 20 0 43 0 95 55 4 75 0 53 2 52 64 4 60 0 48 2 21 I 70 4 55 0 46 2 09 82 4 40 0 42 1 85 93 4 34 0 39 1 69 110 4 29 0 36 1 54 60 128 4 21 0 34 1 43 140 4 20 0 33 1 39 164 4 03 0 33 1 33 186 3 96 0 33 1 31 210 3 89 0 34 1 33 240 3 91 0 35 1 36 IFV71AD BD 280 3 92 0 37 1 45 55 5 45 0 57 3 11 64 5 31 0 52 2 7...

Страница 6: ... 3 12 0 37 1 15 2 38 0 40 0 95 2 38 0 44 1 05 16 61 0 76 12 62 11 59 0 54 6 26 9 46 0 51 4 82 6 68 0 46 3 07 5 11 0 43 2 20 15 00 0 39 5 85 10 75 0 37 3 98 8 86 0 36 3 19 6 19 0 36 2 23 4 70 0 36 1 69 I 3 65 0 37 1 35 2 76 0 39 1 08 2 20 0 43 0 95 23 40 0 80 18 72 16 08 0 56 9 00 13 08 0 47 6 15 I 9 49 0 42 3 99 8 00 0 49 3 92 21 79 0 35 7 63 15 36 0 33 5 07 12 65 0 32 4 05 8 76 0 32 2 80 6 67 0 3...

Страница 7: ...ed to close the contacts for a given voltage The higher the time dial setting the longer the operating time The contacts are just closed when the time dial is set to zero The maximum time setting occurs when the time dial is set to 10 and the disk has to travel its maximum distance to close the contacts HIGH SEISMIC TARGET AND SEAL IN UNIT The target and seal in unit has two tap selections located...

Страница 8: ...t deformed nor its convolutions tangled or touching each other 3 The armature and contacts of the seal in unit as well as the armature and contacts of the instantaneous unit should move freely when operated by hand there should be at least 1 64 inch wipe on the seal in and the instantaneous contacts 4 The targets in the seal in unit and in the instantaneous unit must come into view and latch when ...

Страница 9: ... screw With the contacts just closing at No 0 time setting there should be sufficient gap between the stationary contact brush and its metal backing strip to ensure approximately 1 32 inch wipe The minimum voltage at which the contacts will just close is determined by the tap setting in the tap block at the top of the support structure See CHARACTERISTICS section The pickup of the time overvoltage...

Страница 10: ...ARGET AND SEAL IN UNIT The target and seal in unit has an operating coil tapped at 0 2 and 2 0 amperes The relay is shipped from the factory with the tap screw in the higher ampere position The tap screw is the screw holding the right hand stationary contact To change the tap setting first remove one screw from the left hand stationary contact and place it in the desired tap Next remove the screw ...

Страница 11: ...m dust and well lighted to facilitate inspection and testing The relay should be mounted on a vertical surface The outline and panel drillings are shown in Figures 15 and 16 Figure 15 shows the semi flush mounting and Figure 16 shows various methods of surface mounting The internal connection diagrams for the relays are shovm in Figures 3 4 and 5 Typical external connections are shown in Figures 6...

Страница 12: ... the time tests as described in the INSTALLATION section HIGH SEISM IC TARGET AND SEA L IN UNIT 1 Check that the unit picks up at the values shown in Table VII in the ACCEPTANCE TESTS section 2 Check that the unit drops out at 25 or more o f tap value HIGH SE ISMIC INSTANTANEOUS UNIT Perform a pickup test at system frequency as outlined in the ACCEPTANCE TESTS section CONTACT C LEAN ING For cleani...

Страница 13: ...y means of its adjusting screw With the contacts just closing at No 0 time dial setting there should be sufficient gap between the stationary contact brush and its metal backing strip to ensure approximately 1 32 inch wipe The pickup of the time overvoltage unit is adjusted by means of a spring adjustment ring see Figure 1 The spring adjustment ring either winds or unwinds the spiral control sprin...

Страница 14: ...aring set sere 1 16 inch hex wrench slightly so the upper pivot can move free1 y Do not remove the set screw from the support structure 4 Loosen the jewel bearing set screw as in 3 above 5 Apply a slight downward finger pressure on the upper pivot and turn the jewel bearing screw from the underside of the support structure to position the disk as determined in step 1 above 6 Turn the jewel bearing...

Страница 15: ... a 0 015 0 002 feeler gage and the right contact with a 0 010 0 002 feeler gage HIGH SEISMIC INSTANTANEOUS UNIT The instantaneous unit may be checked the same as the target and seal in unit for contact wipe RENEWAL PARTS Sufficient quantities of renewal parts should be kept in stock for the prompt replacement of any that are worn broken or damaged When ordering renewal parts address the nearest Sa...

Страница 16: ...IFV51AD 25 Figure 9 0275A2074 1 Time Voltage Characteristics for Relay Types IFV71 26 Figure 10 0273A9588 0 Typical Pickup Versus Frequency Characteristic for the IFV71GD Instantaneous Unit 27 Figure 11 0273A9078 0 Test Connections for Testing Pickup and Operating Times of the IFV Relay Time Overvoltage Unit 28 Figure 12 0273A9079 0 Test Connections for Testing the High Seismic Target and Seal in ...

Страница 17: ... STATIONARY 3RUSH AND CONTACT ASSEMBLY GEK 49865 rTOP P VOT TIME OVERVOLTAGE TAP SELECTOR I CONTROL SPRING ADJUSTMENT RING INSTANTANEOUS UNIT MAIN MOVING CONTACT DISK _ _ DRAG MAGNET Figure 1 8043453 Type IFV71BD Relay Removed from Case Front View 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ...E OVERVOLTAGE ITAP SELECTOR I I I I l INSTANTANEOUS VOLTAGE RANGE ADJUSTMENT U MAGNET ASSEMBLY Figure 2 8043454 Type IFV71BD Relay RemGved from Case Rear View 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...2026 0 Internal Connections for Relay Types IFV51AD Front View Figure 4 INDUCTION l JO ERATING s d_ T_ OIL SEAL IN I UNiT rr 0275A2029 0 Internal I r 6 5 Connections 21 n SI rr 12 SHORT FINGER II for Relay Types IFV71AD Front View w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 20: ...r T T t MONITOR TRIP OR ALARM 59 IFV IB SI TARGET SEAL IN TOV TIME OvERVOLTAGE I I N S TA NTA N E 0 U OVERVOLTAGE 52 CIRCUIT BRE KER Figure 7 0273A9039 0 Typical External Connections for IFV71BD Relay 24 t w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 21: ... 6 4 2 zr 1 I _ u __ ____ Ill 0 z 0 u w Vl z I i _ i I 1 0 i w 0 8 E 1 0 6 f 1 1 l _ ____ 0 4 L 4 1 I I i 952 Figure 8 0275A2075 l Time Voltage Characteristics for Relay Types IFV51AD 25 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 22: ...GEK 49865 ll 0 120 130 140 150 160 170 00 IS0200 PERCENT OF TAP VALUE 3 Figure 9 0275A2074 0 Time Voltage Characteristics for Relay Types IFV71 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 23: ...40 I 0 30 UJ cr u I v 20 4 0 I05 110 115 120 12 5 TYPICAL PICKUP VOLTS Figure 10 0273A9588 0 Typical Pickup Versus Frequency Characteristic for the IFV71BD Instantaneous Unit 27 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 24: ...R I t TO INDICATIN G LIGHT WHEN CHEO ING PICK UP EXTERNAL CAPACITOR WHEN NECESSARY 12XCA2BA I RELAY TERMINALS Figure 11 0273A9078 l Test Connections for Testing Pickup and Operating Times of the IFV Relay Time Overvoltage Unit 28 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 25: ...High Seismic Target and Seal in Unit Used lith the IFV Relay VARIABLE VOLTAGE SOURCE A T RATED FREQUENCY RELAY TERMINALS Figure 13 0273A9193 0 Test Connections for Testing the High Seismic Instantaneous Unit Used with the IFV Relay 29 RELAY TERMINALS w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 26: ...N PLUG CONTACT FINGERS RELAY CASE SHORTING BAR ORAWOUT ELEMENT SUPPORT STRUCTURE CASE CONNECTION BLOCK Figure 14 8C42715 Cross Section o f Drawout Case Connections 30 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 27: ...HER 3 062 76M 5 562 141 MM 14 2 i 6 124 156MM t0t Yj010101jljl lololololo o o 1 I I CD 13 _L j ERING I l REAR VIEW TIE SUPPORT OR TIE ANCHOR 8 32 SChEW NUT k CABLE V lEW A HD W 0257A8 549 G 1 IOXI 2 TYPE 8 T T H R EADCU TTl N G T I E If II CAB LE3 SC R EW VIEW 0 Figure 15 0257A8452 Sh l 3 Outline and Panel Drilling for Relay Types IFV51AD 71AD and 7180 31 w w w E l e c t r i c a l P a r t M a n u ...

Страница 28: ...i _YL a H DW 0 2 5 7A8 549 G 2 f 5 244 3 688 rl l 212NM 94MN 2 HOLES I I I I SEE VIEW C T 4 i 469 q 1 2 3 7 r 12HM r i 6 MM t_r 750 EXTERNAL i L f 1_9 1 CONNECTIONS r r 4 750 000 dOOO it0 32 SCREWS 121 IN CD 1h q 000 1 T r r _ 625 _ Q__J MOU llNG j j SMM SURFACE TYPICAL 4 MM SIDE IEW FOR 312 riOLES MOUNTING SUf FAC E WASHER REMOVE KNJCKCUT ENLARGED VIEW c REC SCRFACE MT G FOR 8MM HOW 02 57A8 549 6...

Отзывы: