background image

GEK-49865 

CHARACTERISTICS 

The  IFV51AD  relay  is  an  overvoltage  relay  that  closes  its  contacts  when  the  voltage 

increases  to  the  pickup  value  as  set  on  the  tap  block. 

The  IFV71AD  relay  is  similar  to  the  IFV51AD  relay,  except  that  it  is  frequency­

compensated  to  hold  its  calibration  vJithin  7. 5%  frotn  50%  to  150%  o f   system 

frequency. 

The  IFV71BD  relay  is  similar  to  the  IFV71AD  relay  except  for  the  addition  o f   an 

instantaneous  unit,  which  is  also  frequency-compensated. 

See  Figure  10  for  a 

typical  pickup-versus- frequency  characteristic. 

Pickup  o f   this  instantaneous  unit 

is  determined  by  the  setting  o f   a  poten�iometer  located  in  the  rear  o f   the  relay. 

TIME  OVE RVOLTAGE  UNIT 

Pickup  of  these  relays  is  defined  as  the  voltage  required  to  close  the  contacts  with 

the  relay  set  at  the  0. 5  time-dial  position. 

Tap  settings  are  made  by  means  o f   a 

movable  lead  that  connects  to  the  tap  block  at  the  top  o f   the  support  structure  (See 

Figure  1) . 

The  tap  block  is  marked  A  through  N. 

The  nameplate  on  the  relay 

contains  a  table  that  shows  the  tap  voltage  for  each  tap  setting. 

The  IFV  relays  should  operate  within 

.:!:. 

10%  o f   the  time-voltage  characteristic  or 

.:!:. 

the  time-dial  setting  times  0.010  second,  whichever  is  greater. 

Figures  8  and  9 

show  the  various  time-voltage  characteristics  for  the  IFV  relays. 

The  setting  o f  

the  time  dial  determines  the  length  o f   the  time  required  to  close  the  contacts  for  a 

given  voltage. 

The  higher  the  time-dial  setting,  the  longer  the  operating  time. 

The  contacts  are  just  closed  when  the  time  dial  is  set  to  zero.  The  maximum  time 

setting  occurs  when  the  time  dial  is  set  to  10  and  the  disk  has  to  travel  its 

maximum  distance  to  close  the  contacts. 

HIGH-SEISMIC  TARGET  AND  SEA L-IN  UNIT 

The  target  and  seal-in  unit  has  two  tap  selections,  located  on  the  front  o f   the 

unit.  See  Figure  1. 

HIGH-SEISMIC  INSTANTANEOUS  UNIT 

The  instantaneous  unit  setting  is  determined  by  a  potentiometer  located  in  the  rear 

o f   the  relay.  See  the 

RATINGS 

section  for  the  various  voltage  ranges. 

RECEIVING,  HANDliNG  AND  STORAGE 

These  relays,  when  not  included  as  part  o f   a  control  panel,  will  be  shipped  in 

cartons  designed  to  protect  them  against  damage. 

Immediately  upon  receipt  o f   a 

relay,  examine  it  for  any  damage  sustained  in  transit. 

I f   injury  or  damage 

resulting  from  rough  handling  is  evident,  file  a  damage  claim  at  once  with  the 

transportation  company  and  promptly  notify  the  nearest  General  Electric  Sales 

O f fice. 

Reasonable  care  should  be  exercised  in  unpacking  the  relay  in  order  that  none  o f   the 

parts  are  injured  or  the  adjustments  disturbed. 

I f   the  relays  are  not  to  be  installed  immediately,  they  should  be  stored  in  their 

original  cartons  in  a  place  that  is  free  from  moisture,  dust  and  metallic  chips. 

Foreign  matter  collected  on  the  outside  o f   the  case  may  find  its  way  inside  when  the 

cover  is  removed,  and  cause  trouble  in  the  operation  o f   the  relay. 

www 

. ElectricalPartManuals 

. com 

Содержание IFV51AD

Страница 1: ...TYPES IFV51AD IFV71AD IFV71BD INSTRUCTIONS TIME OVERVOLTAGE RELAYS GENERAL f ELECTRIC GEK 49865A Supersedes GEK 49865 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...ckup and Dropout Test High Seismic Instantaneous Unit INSTALLATION Installation Tests Time Overvoltage Unit High Seismic Target and Seal in Unit High Seismic Instantaneous Unit PERIOD IC CHECKS AND ROUTINE MAINTENANCE Time Overvoltage Unit High Seismic Target and Seal in Unit High Seismic Instantaneous Unit Contact Cleaning System Test SERVICING Time Overvoltage Unit Pickup Tests Time Tests Mechan...

Страница 3: ...ay has two electrically separate sets of normal l y open contacts These contacts will close when the instantaneous unit operates and they may be used to initiate tripping to sound an alarm or to monitor operation of the unit The instantaneous unit has a self contained target that will show after the unit has operated Each relay is mounted in a standard C1 size drawout case the outline and panel dr...

Страница 4: ...e Ohms 68 6 0 73 HIGH SE ISMIC INSTANTANEOUS UNIT The instantaneous unit is frequency compensated over the range o f 50 to 150 of system frequency There are two ranges available 120 200 and 180 300 that are continuously adjustable by means o f a potentiometer located in the rear o f the relay CONTACTS The current closing rating o f the contacts is 30 amperes for voltages not exceeding 250 volts Th...

Страница 5: ...32 0 36 0 85 144 2 20 0 36 0 79 1 4 2 18 0 36 0 78 185 2 15 0 37 0 80 211 2 13 0 39 0 83 250 2 20 0 43 0 95 55 4 75 0 53 2 52 64 4 60 0 48 2 21 I 70 4 55 0 46 2 09 82 4 40 0 42 1 85 93 4 34 0 39 1 69 110 4 29 0 36 1 54 60 128 4 21 0 34 1 43 140 4 20 0 33 1 39 164 4 03 0 33 1 33 186 3 96 0 33 1 31 210 3 89 0 34 1 33 240 3 91 0 35 1 36 IFV71AD BD 280 3 92 0 37 1 45 55 5 45 0 57 3 11 64 5 31 0 52 2 7...

Страница 6: ... 3 12 0 37 1 15 2 38 0 40 0 95 2 38 0 44 1 05 16 61 0 76 12 62 11 59 0 54 6 26 9 46 0 51 4 82 6 68 0 46 3 07 5 11 0 43 2 20 15 00 0 39 5 85 10 75 0 37 3 98 8 86 0 36 3 19 6 19 0 36 2 23 4 70 0 36 1 69 I 3 65 0 37 1 35 2 76 0 39 1 08 2 20 0 43 0 95 23 40 0 80 18 72 16 08 0 56 9 00 13 08 0 47 6 15 I 9 49 0 42 3 99 8 00 0 49 3 92 21 79 0 35 7 63 15 36 0 33 5 07 12 65 0 32 4 05 8 76 0 32 2 80 6 67 0 3...

Страница 7: ...ed to close the contacts for a given voltage The higher the time dial setting the longer the operating time The contacts are just closed when the time dial is set to zero The maximum time setting occurs when the time dial is set to 10 and the disk has to travel its maximum distance to close the contacts HIGH SEISMIC TARGET AND SEAL IN UNIT The target and seal in unit has two tap selections located...

Страница 8: ...t deformed nor its convolutions tangled or touching each other 3 The armature and contacts of the seal in unit as well as the armature and contacts of the instantaneous unit should move freely when operated by hand there should be at least 1 64 inch wipe on the seal in and the instantaneous contacts 4 The targets in the seal in unit and in the instantaneous unit must come into view and latch when ...

Страница 9: ... screw With the contacts just closing at No 0 time setting there should be sufficient gap between the stationary contact brush and its metal backing strip to ensure approximately 1 32 inch wipe The minimum voltage at which the contacts will just close is determined by the tap setting in the tap block at the top of the support structure See CHARACTERISTICS section The pickup of the time overvoltage...

Страница 10: ...ARGET AND SEAL IN UNIT The target and seal in unit has an operating coil tapped at 0 2 and 2 0 amperes The relay is shipped from the factory with the tap screw in the higher ampere position The tap screw is the screw holding the right hand stationary contact To change the tap setting first remove one screw from the left hand stationary contact and place it in the desired tap Next remove the screw ...

Страница 11: ...m dust and well lighted to facilitate inspection and testing The relay should be mounted on a vertical surface The outline and panel drillings are shown in Figures 15 and 16 Figure 15 shows the semi flush mounting and Figure 16 shows various methods of surface mounting The internal connection diagrams for the relays are shovm in Figures 3 4 and 5 Typical external connections are shown in Figures 6...

Страница 12: ... the time tests as described in the INSTALLATION section HIGH SEISM IC TARGET AND SEA L IN UNIT 1 Check that the unit picks up at the values shown in Table VII in the ACCEPTANCE TESTS section 2 Check that the unit drops out at 25 or more o f tap value HIGH SE ISMIC INSTANTANEOUS UNIT Perform a pickup test at system frequency as outlined in the ACCEPTANCE TESTS section CONTACT C LEAN ING For cleani...

Страница 13: ...y means of its adjusting screw With the contacts just closing at No 0 time dial setting there should be sufficient gap between the stationary contact brush and its metal backing strip to ensure approximately 1 32 inch wipe The pickup of the time overvoltage unit is adjusted by means of a spring adjustment ring see Figure 1 The spring adjustment ring either winds or unwinds the spiral control sprin...

Страница 14: ...aring set sere 1 16 inch hex wrench slightly so the upper pivot can move free1 y Do not remove the set screw from the support structure 4 Loosen the jewel bearing set screw as in 3 above 5 Apply a slight downward finger pressure on the upper pivot and turn the jewel bearing screw from the underside of the support structure to position the disk as determined in step 1 above 6 Turn the jewel bearing...

Страница 15: ... a 0 015 0 002 feeler gage and the right contact with a 0 010 0 002 feeler gage HIGH SEISMIC INSTANTANEOUS UNIT The instantaneous unit may be checked the same as the target and seal in unit for contact wipe RENEWAL PARTS Sufficient quantities of renewal parts should be kept in stock for the prompt replacement of any that are worn broken or damaged When ordering renewal parts address the nearest Sa...

Страница 16: ...IFV51AD 25 Figure 9 0275A2074 1 Time Voltage Characteristics for Relay Types IFV71 26 Figure 10 0273A9588 0 Typical Pickup Versus Frequency Characteristic for the IFV71GD Instantaneous Unit 27 Figure 11 0273A9078 0 Test Connections for Testing Pickup and Operating Times of the IFV Relay Time Overvoltage Unit 28 Figure 12 0273A9079 0 Test Connections for Testing the High Seismic Target and Seal in ...

Страница 17: ... STATIONARY 3RUSH AND CONTACT ASSEMBLY GEK 49865 rTOP P VOT TIME OVERVOLTAGE TAP SELECTOR I CONTROL SPRING ADJUSTMENT RING INSTANTANEOUS UNIT MAIN MOVING CONTACT DISK _ _ DRAG MAGNET Figure 1 8043453 Type IFV71BD Relay Removed from Case Front View 19 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 18: ...E OVERVOLTAGE ITAP SELECTOR I I I I l INSTANTANEOUS VOLTAGE RANGE ADJUSTMENT U MAGNET ASSEMBLY Figure 2 8043454 Type IFV71BD Relay RemGved from Case Rear View 20 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 19: ...2026 0 Internal Connections for Relay Types IFV51AD Front View Figure 4 INDUCTION l JO ERATING s d_ T_ OIL SEAL IN I UNiT rr 0275A2029 0 Internal I r 6 5 Connections 21 n SI rr 12 SHORT FINGER II for Relay Types IFV71AD Front View w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 20: ...r T T t MONITOR TRIP OR ALARM 59 IFV IB SI TARGET SEAL IN TOV TIME OvERVOLTAGE I I N S TA NTA N E 0 U OVERVOLTAGE 52 CIRCUIT BRE KER Figure 7 0273A9039 0 Typical External Connections for IFV71BD Relay 24 t w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 21: ... 6 4 2 zr 1 I _ u __ ____ Ill 0 z 0 u w Vl z I i _ i I 1 0 i w 0 8 E 1 0 6 f 1 1 l _ ____ 0 4 L 4 1 I I i 952 Figure 8 0275A2075 l Time Voltage Characteristics for Relay Types IFV51AD 25 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 22: ...GEK 49865 ll 0 120 130 140 150 160 170 00 IS0200 PERCENT OF TAP VALUE 3 Figure 9 0275A2074 0 Time Voltage Characteristics for Relay Types IFV71 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 23: ...40 I 0 30 UJ cr u I v 20 4 0 I05 110 115 120 12 5 TYPICAL PICKUP VOLTS Figure 10 0273A9588 0 Typical Pickup Versus Frequency Characteristic for the IFV71BD Instantaneous Unit 27 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 24: ...R I t TO INDICATIN G LIGHT WHEN CHEO ING PICK UP EXTERNAL CAPACITOR WHEN NECESSARY 12XCA2BA I RELAY TERMINALS Figure 11 0273A9078 l Test Connections for Testing Pickup and Operating Times of the IFV Relay Time Overvoltage Unit 28 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 25: ...High Seismic Target and Seal in Unit Used lith the IFV Relay VARIABLE VOLTAGE SOURCE A T RATED FREQUENCY RELAY TERMINALS Figure 13 0273A9193 0 Test Connections for Testing the High Seismic Instantaneous Unit Used with the IFV Relay 29 RELAY TERMINALS w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 26: ...N PLUG CONTACT FINGERS RELAY CASE SHORTING BAR ORAWOUT ELEMENT SUPPORT STRUCTURE CASE CONNECTION BLOCK Figure 14 8C42715 Cross Section o f Drawout Case Connections 30 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 27: ...HER 3 062 76M 5 562 141 MM 14 2 i 6 124 156MM t0t Yj010101jljl lololololo o o 1 I I CD 13 _L j ERING I l REAR VIEW TIE SUPPORT OR TIE ANCHOR 8 32 SChEW NUT k CABLE V lEW A HD W 0257A8 549 G 1 IOXI 2 TYPE 8 T T H R EADCU TTl N G T I E If II CAB LE3 SC R EW VIEW 0 Figure 15 0257A8452 Sh l 3 Outline and Panel Drilling for Relay Types IFV51AD 71AD and 7180 31 w w w E l e c t r i c a l P a r t M a n u ...

Страница 28: ...i _YL a H DW 0 2 5 7A8 549 G 2 f 5 244 3 688 rl l 212NM 94MN 2 HOLES I I I I SEE VIEW C T 4 i 469 q 1 2 3 7 r 12HM r i 6 MM t_r 750 EXTERNAL i L f 1_9 1 CONNECTIONS r r 4 750 000 dOOO it0 32 SCREWS 121 IN CD 1h q 000 1 T r r _ 625 _ Q__J MOU llNG j j SMM SURFACE TYPICAL 4 MM SIDE IEW FOR 312 riOLES MOUNTING SUf FAC E WASHER REMOVE KNJCKCUT ENLARGED VIEW c REC SCRFACE MT G FOR 8MM HOW 02 57A8 549 6...

Отзывы: