ADJUSTABLE FEATURES 

SX TRANSISTOR CONTROLS

 

 

 

Page 

46

 

 

 

March 2000 

 

 
FUNCTION 18  

STEER PUMP TIME DELAY 

 

( Push CONT 3 )

 

 

This function allows for the selection of steer pump 

contactor pick up input, either seat switch or directional 

switch closing, and adjustment of the time delay for the 

contactor drop out.   

 

??

Pick up steer pump contactor on seat switch closure 

and time delay drop out of steer pump contactor on 

seat switch opening. 

 

 

Range   

1.5 to 65 seconds 

 

Setting   

Between 0 and 128 

 

Resolution 

0.5 seconds per set unit 

 

Example  

Setting of 20  = 11.5 seconds 

 

FUNCTION 19  

MAINTENANCE CODE TENS AND UNITS 
HOURS SET 

 

( Push CONT 4 ) 

 

This function allows for the adjustment of the tens and 

units hours of the maintenance code activation time. 

 

 

Range       

0 to 99 

  

Set 

0 to 99 

  

Example      

9999 Hours 

 

 FUNCTION 20   MAINTENANCE CODE THOUSANDS AND 

HUNDREDS HOURS SET  

 

( Push CONT 5 ) 

 

This function allows for the adjustment of the thousands 

and hundreds hours of the maintenance code activation 

time. 

 

 

Range       

0 to 240  

 

Set         

0 to 240  

 

Example      

9999 Hours 

 

FUNCTION 21  

AUTO REGEN BRAKING C/L 

 

(Push CONT 6) 

This function allows for the adjustment of the Regen 

braking current limit. The higher the current the shorter the 

stopping distance.   

 

Setting greater than 143 disables this function. 

AUTO REGEN

C/L AMPS

= REGEN C/L

VAL

-

FNT 21-51

VAL

-

[(

(

6.50

[

 

 
FUNCTION 23 

REGEN CANCEL 

 

( Push CONT 8 ) 

 

This function adjusts the motor current level for regen 

cancel. 

 

 

Range   

52 – 260 amps 

 

Setting   

0 – 255 amps 

 

Resolution 

0.815 per set unit 

 

 

Example Setting of 20 = (20 x 0.815) + 52 = 68.3 

 

 

FUNCTION 24  

FIELD WEAKENING START 

 

 

( Push CONT 9) 

 

This function allows for setting the armature current at 

which minimum field current will be achieved . 

 

Range   

0 to 414 Amps 

Setting   

0 to 255 

Resolution 

1.625 per set unit 

MOTOR

 FWS = VAL. x 1.625 

 

Example: Setting of 20 = 32.5 amps 

 
FUNCTION 25 

MONITOR 

 

( Push CONT 10) 

 

This function allows the monitoring of certain control 

functions by looking directly at the RAM of the 

microprocessor. Because absolute memory locations need 

to be known, this function should not be used without 

detailed instructions from the GE application engineer.  

 

This function should only be adjusted by the vehicle 
OEM. To ensure optimum operation of the control, this 
function must be left with zero stored in this register.  
 
FUNCTION 26  

RATIO 

 

( Push CONT 11) 

 

This function sets the ratio between armature and field 

current when transitioning from minimum field to maximum 

field current.  The setting represents the quantity of field 

current changed for each 1 amp of armature current 

changed. 

 

Max 

Fld Ref 

Max 

Change 

Set 

Resolution 

Per Unit 

Value 

 

Example If Set at 5 

20 

.24 

0 to 10  0.024 amps 

0.12 amps 

30 

.24 

0 to 10  0.024 amps 

0.12 amps 

40 

.27 

0 to 10  0.027 amps 

0.135 amps 

50 

.48 

0 to 10  0.048 amps 

0.24 amps 

60 

.48 

0 to 10  0.048 amps 

0.24 amps 

 

FUNCTION 28 

STORED STATUS CODE COUNT POINTER

  

 

( Push CONT 13) 

 
This register contains the location of the last stored status 
code recorded of the 16 stored status codes. These stored 
status codes have caused a PMT controller shutdown 
and/or disruption of normal vehicle operation. 

Содержание IC3645SR3R404R2

Страница 1: ...please refer the matter to the OEM vehicle manufacturer through his normal field service channels Do not contact GE directly for this assistance Copyright by General Electric Company March 2000 Section 1 0 INTRODUCTION 4 1 1 Motor Characteristics 4 1 2 Solid State Reversing 5 1 3 Flexible System Application 5 1 4 More Features with Fewer Components 5 Section 2 0 FEATURES OF SX FAMILY OF MOTOR CONT...

Страница 2: ...ule TMM 9 Section 3 0 ORDERING INFORMATION ELEMENTARY AND OUTLINE DRAWINGS 10 3 1 Ordering Information for Separately Excited Controls 10 3 2 Outline SX 2 Package Size 11 3 3 Traction Elementary 12 3 4 Traction Control Input Output List 13 Section 4 0 TROUBLESHOOTING AND DIAGNOSTIC STATUS CODES 14 4 1 General Maintenance Instructions 14 4 2 Cable Routing and Separation 14 4 2 1 Application Respons...

Страница 3: ...X FAMILY GE HANDSET INSTRUCTIONS 41 6 1 General Features 41 6 2 Purpose Setup Functions 41 6 3 Setup Function Procedures 42 6 3 1 Setup Mode 42 6 3 2 Status Code Scrolling 42 6 3 3 SX Handset Plug Connections Outline Drawing 42 6 4 Setup Functions for Traction Controller 43 48 6 5 Summary of Current Limit Adjustments 49 Section 7 0 DASH DISPLAYS 50 7 1 Application 50 7 2 Standard Dash Displays 50 ...

Страница 4: ...rque at low speed characteristic of the series motor is evident In a shunt motor the field is connected directly across the voltage source and is therefore independent of variations in load and armature current If field strength is held constant the torque developed will vary directly with the armature current If the mechanical load on the motor increases the motor slows down reducing the back EMF...

Страница 5: ...by placing a resistor in parallel with the field winding of the motor Bypassing some of the current flowing in the field into the resistor causes the field current to be less or weakened With the field weakened the motor speed will increase giving the effect of overdrive To change the overdrive speed it is necessary to change the resistor value In a separately excited motor independent control of ...

Страница 6: ...ion 2 1 3 Braking Section 2 1 3 a Regenerative Braking to Zero Speed Slow down is accomplished when reversing direction by providing a small amount of retarding torque for deceleration If the vehicle is moving and the directional lever is moved from one direction to the other the regen signal is initiated Once the regen signal has been initiated the field current is increased armature circuit show...

Страница 7: ...ening of the seat switch if a bump is encountered Section 2 2 2 Accelerator Volts Hold Off This feature checks the voltage level at the accelerator input whenever the key switch or seat switch is activated If at start up the voltage is less than 3 0 volts the control will not operate This feature assures that the control is calling for low speed operation at start up Section 2 2 3 Pulse Monitor Tr...

Страница 8: ...ology is used to provide accurate battery state of charge information and to supply passive and active warning signals to the vehicle operator Features and functions Displays 100 to 0 percent charge Display blinks with 20 charge Disables pump circuit with 10 charge Auto ranging for 36 48 volt operation Adjustable for use on 24 to 80 volts Section 2 3 4 a Internal Resistance Compensation This featu...

Страница 9: ...ability to initiate status codes or operator warning codes to be displayed on the Dash Display whenever a normally open switch or sensor wire provides a signal to the Module The TMM Module can be used to display a separate status code indicating over temperature of traction motors hydraulic motors or any other device or system that can activate a switch that closes The TMM Module can also be used ...

Страница 10: ...eries Control Pump SH Separately Excited Control Plugging SR Separately Excited Control Regen to Zero Argument 03 Operating Voltage 1 120 volts 4 48 volts 2 24 volts 5 36 48 volts 3 36 volts 6 24 36 volts 7 72 80 volts Argument 04 Package Size D 6 86 X 6 67 R 6 86 X 8 15 U 8 66 X 8 13 W 8 66 X 10 83 Argument 05 Armature Current 2 characters 22 220 Amps 33 330 Amps 40 400 Amps etc Argument 06 Field...

Страница 11: ...OUTLINE DRAWINGS ELEMENTARY DRAWINGS AND INPUTS OUTPUTS SX TRANSISTOR CONTROL Page 11 Section 3 3 Traction Elementary ...

Страница 12: ... CONNECTION POS L 1A REG BRAKING POTENTIOMETER INPUT REGEN OUTPUT SIGNAL I MOTOR VOLTAGE OUT BDI INTERRUPT KEY SWITCH DIRECT SWITCH P18 P17 P2 P6 P4 P5 P3 P10 P15P11 P13 P1 P7 P9 SEAT SW 3 15 7 24 10 10 10 6 8 13A A2 A1 F1 F2 29 30 50 1A SP 41 13 13 MOTOR CONNECTIONS CUSTOMER SUPPLIED A1 A2 SP STEER PUMP ARM PUMP CONNECTION BATT NEG LINE FU4 TMM7 TMM7 88 43 44 89 Section 3 4 Traction Control Input...

Страница 13: ...NAL 12V 1 PLUG 12 NOT USED 13 RGN BRAKE POTENTIOMETER INPUT 14 NOT USED 15 IMOTOR OUT 16 NOT USED 17 LINE CONTACTOR DRIVER AND SUPPRESSION 18 1A CONTACTOR DRIVER AND SUPPRESSION 19 NOT USED 20 NOT USED 21 NOT USED 22 SERIAL RECEIVE DASH DISPLAY 23 SERIAL TRANSMIT DASH DISPLAY MOTOR PROPORTIONING Y PLUG PIN INPUT OUTPUT DESCRIPTION 1 CLOCK OUT 2 DATA OUT 3 ENABLE OUT 4 NEGATIVE 5 5V SUPPLY 6 CONT S...

Страница 14: ...he vehicle Follow normal battery maintenance procedures recharging before 80 percent discharged with periodic equalizing charges Visual inspection of GE contactors contained in the traction and pump systems is recommended to occur during every 160 hours of vehicle operation Inspection is recommended to verify that the contactors are not binding and that the tips are intact and free of contaminants...

Страница 15: ...st apply the general guidelines section 4 2 3 a outlined below 4 2 3 a General Cable Spacing The following general practices should be used for all levels of cabling All cables and wires of like signal levels and power levels must be grouped together In general different levels must run in separate wire bundles as defined in the different classes identified above Intermixing cannot be allowed unle...

Страница 16: ...ct cleaner and lubricant which provides a high degree of environmental and fretting protection New and re manufactured control plugs are cleaned and lubricated prior to shipment from the factory However in applications where severe vibration or high temperature cycling and excessive humidity such as freezers are present it is recommended that the plug terminals be cleaned and lubricated every year...

Страница 17: ...e last option to correct the problem The same device designations have been maintained on different controls but the wire numbers may vary Refer to the elementary and wiring diagrams for your specific control The wire numbers shown on the elementary diagram will have identical numbers on the corresponding wiring diagrams for a specific vehicle but these numbers may be different from the numbers re...

Страница 18: ...sh Display or Handset Defective Dash Display or Handset Replace Dash Display or Handset NEG FU3 KEY SWITCH P1 P2 FU5 P18 1A L P17 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 01 No seat switch or deadman switch input no voltage to P6 This status code will be displayed when P6 is less than 50 battery volts MEMORY RECALL NO CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuit...

Страница 19: ...ntrol Replace the controller unit NEG FU3 KEY SWITCH P1 P2 FU5 P18 1A SP L P17 P6 SEAT SW P3 START SW P4 FORWARD SW P5 REVERSE SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 03 Reverse directional switch is closed on initial power up This status code will be displayed when P5 is greater than 60 of battery voltage at initial key switch on MEMORY RECALL NO CORRECTIVE ACTION...

Страница 20: ...FORWARD SW P5 REVERSE SW P7 ACC POT P9 NEG TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 06 Accelerator depressed with no direction selected This status code will be displayed when P4 and P5 are less than 60 of battery volts and P7 is less than 2 5 volts MEMORY RECALL NO CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits valid for Traction Controller SYMPTOM Control will ...

Страница 21: ...g in accelerator input circuit Disconnect wire from P7 and measure voltage at wire to negative Should be zero volts for potentiometer type and less than 4 2 volts for solid state type accelerator input P9 P7 ACC POT NEGATIVE TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 08 Accelerator input voltage too low on power up after initial key switch closure This status code will b...

Страница 22: ...volts NEG FU3 KEY SWITCH P1 P2 FU5 P18 1A SP L P17 P6 SEAT SW P3 START SW P4 FORWARD SW P5 REVERSE SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 11 Start switch closed on power up after initial key switch closure This status code will be displayed when P3 is greater than 60 of battery voltage when the key switch is closed MEMORY RECALL NO CORRECTIVE ACTIONS TROUBLE SHOOT...

Страница 23: ...settings Check minimum battery volts at P1 and NEG NEG FU5 P1 NOMINAL BATTERY VOLTAGE MINIMUM LIMIT VOLTS AT 1 95 VDC PER CELL 24 80 48 72 36 23 4 78 0 46 8 70 2 35 1 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 16 Battery voltage is too high or control card is mis adjusted This status code will be displayed when the battery volts are greater than 2 4 volts per cell at ini...

Страница 24: ...C CARD CONNECTIONS L 1A DIRECT SW P18 P17 P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 24 Motor field current is high on start up in the forward direction This status code will be displayed when the current draw in the motor field is too high at start up in the forward direction MEMO...

Страница 25: ...unit NEG FU3 KEY SWITCH P1 P2 FU5 P18 1A L P17 TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 28 Motor field current has remained too high during the run mode This status code will be displayed when the current in the motor field is sustained above a preset limit for longer than 70 seconds MEMORY RECALL YES CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits valid for Tract...

Страница 26: ...5 KEY SWITCH CONTROL POWER CONNECTION POS A1 NEG A2 ARMATURE FU1 LINE A2 A1 1A OSC CARD CONNECTIONS L 1A DIRECT SW P18 P17 P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 42 Motor armature offset voltage is too high This status code will be displayed when the voltage at the current sens...

Страница 27: ...P18 P17 P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 44 Armature transistor did not turn off properly This status code will be displayed when during control operation the armature transistor fails to turn off This will result in a PMT condition MEMORY RECALL YES CORRECTIVE ACTIONS TR...

Страница 28: ... LINE A2 A1 1A OSC CARD CONNECTIONS L 1A DIRECT SW P18 P17 P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 46 Look Ahead test for A2 volts less than 12 of battery volts This status code will be displayed when the voltage at A2 is less than 12 of battery volts MEMORY RECALL NO CORRECTIVE...

Страница 29: ... P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 51 Capacitor volts are low before the line contactor closes This status code will be displayed during key on when the capacitor volts is less than 85 of battery volts at initial key switch on MEMORY RECALL NO CORRECTIVE ACTIONS TROUBLE SH...

Страница 30: ...T SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 64 The line driver input P2 17 is less than 12 of battery volts This status code will be displayed when the control detects that the line driver input P2 17 is less than 12 battery volts when the key switch is turned on MEMORY RECALL NO CORRECTIVE ACT...

Страница 31: ...2 A1 1A OSC CARD CONNECTIONS L 1A DIRECT SW P18 P17 P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 66 The field current exceeds the current limit of the field transistor This status code will be displayed when the field transistor exceeds its specific current limit The line contactor w...

Страница 32: ... P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 76 Capacitor 1C voltage too high This status code will be displayed when the voltage on the capacitor goes above limit voltage during the regenerative braking cycle MEMORY RECALL YES CORRECTIVE ACTIONS TROUBLE SHOOTING DIAGRAM Circuits va...

Страница 33: ...TURE FU1 LINE A2 A1 1A OSC CARD CONNECTIONS L 1A DIRECT SW P18 P17 P2 P6 P4 SEAT SW SP P3 FWD REV P5 ACCEL START SW P1 P7 P9 F1 F2 FIELD F1 F2 ACCEL START SW TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 84 Capacitor voltage is less than 16V for more than 2 5 seconds This status code will be displayed when the capacitor voltage is less than 16 volts for more than 2 5 second...

Страница 34: ... code is displayed immediately additional status codes are displayed in 20 hour intervals P16 SC90 NEG USER SW WHEN SR Series PUMP CONTROL IS USED TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 91 Pump motor temperature has exceeded maximum temperature limit This status code will be displayed when the voltage at the respective terminal of the TMM or Pump Logic Card is at zer...

Страница 35: ...ayed immediately additional status codes are displayed in 20 hour intervals SC93 POS P3 USER SW WHEN SR Series PUMP CONTROL IS USED TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 93 Steering pump motor brush wear indicator has detected worn brush This status code will be displayed when the voltage at the respective terminal of the TMM or Pump Logic Card is at battery volts M...

Страница 36: ...is displayed immediately additional status codes are displayed in 20 hour intervals SC94 POS P5 USER SW WHEN SR Series PUMP CONTROL IS USED TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 94 Traction motor brush wear indicator had detected worn brush This status code will be displayed when the voltage at the respective terminal of the TMM or Pump Logic Card is at zero volts M...

Страница 37: ...layed immediately additional status codes are displayed in 20 hour intervals SC95 POS P8 USER SW WHEN SR Series PUMP CONTROL IS USED TRACTION STATUS CODE DESCRIPTION OF STATUS CAUSE OF STATUS INDICATION 95 Pump motor brush wear indicator has detected worn brush This status code will be displayed when the voltage at the respective terminal of the TMM or Pump Logic Card is at battery volts MEMORY RE...

Страница 38: ...n at a reduced speed CUSTOMER SELECTED SETTING WITH THE HANDSET User defined status code is displayed when the normal hour meter reading exceeds the programmed maintenance alert hours setting selected by the user Maintenance Code Hour Meter Functions 19 and 20 are programmed with the Handset and command the display of status code 99 If desired Maintenance Code Speed Limit Function 13 can be progra...

Страница 39: ...r each input when that point is closed to battery negative or positive as indicated TMM7A Pump Card Control Status Terminal Terminal Code Connect To TB1 P16 90 Neg TB3 P11 91 Neg TB4 P15 92 Neg TB5 P3 93 Pos TB6 P4 93 Pos TB8 P5 94 Pos TB10 P6 94 Pos TB11 P8 95 Pos TB12 P9 95 Pos Status codes 90 and 93 can also be programmed with the Handset to reduce the speed of the truck from 100 to 0 percent o...

Страница 40: ... 10 12 BATTERY POSITIVE PUMP CONTROL CONNECTIONS PL2 16 PL2 11 PL2 15 PL2 3 PL2 4 PL2 5 PL2 6 PL2 8 PL2 9 PL2 13 PL2 20 1 A1 1 A1 2 A2 1 A3 1 A2 2 A3 2 TRACTION PL2 14 TRACTION PL2 20 Section 5 5 TMM7A Outline Drawings 1 3 4 5 6 7 2 8 10 9 11 12 14 13 15 5 8 147 20 6 15 156 20 8 20 3 3 36 85 3 x 1 60 40 6 ...

Страница 41: ...8 volts is auto ranging Selection of Card Operation Type At the transistor control traction card unplug the Y plug if the dash display is in use and plug in the Handset to the plug location Y on the control card After installing the Handset tool plug the battery in and turn the key switch on The following is the start up display sequence that will occur START UP DISPLAY SEQUENCE Key Switch On Veri...

Страница 42: ... either the diagnostics mode the BDI display or a blank display if BDI is not used and there are no fault codes The vehicle can now be operated with the Handset connected or the Handset can be disconnected before operation NOTE You can return to the segment check mode at any time by holding down the ESC key until 8888 appears in the display Section 6 3 2 Status Code Scrolling The SX family of cont...

Страница 43: ...tion stops and the accelerator input is less than 0 5 volts or less than 200 ohms Range 0 1 to 22 0 seconds Set 0 to 255 Resolution 0 084 seconds per set unit Example Setting of 20 1 8 seconds C A and 2 0 1A time FUNCTION 4 ARMATURE CURRENT LIMIT Push 4 This function allows for the adjustment of the armature current limit of the control The rating of the control will determine the range of adjustm...

Страница 44: ...If set at 20 32 240 0 to 255 0 93 amps 50 6 amps 52 468 0 to 255 1 63 amps 84 6 amps 184 600 0 to 255 1 63 amps 216 6 amps FUNCTION 10 MAX FIELD CURRENT FOR REGEN Push 10 This function allows for the adjustment of the maximum field current to be used during the regen braking mode Resolution Example Min Max Set Per unit value If set at 71 0 20 51 to 176 0 16 amps 3 2 amps 0 30 51 to 255 0 16 amps 3...

Страница 45: ...ing distance Note Vehicles equipped with regenerative braking will vary the regen current with pedal position However minimum regen current is fixed at 50 amps The pedal position will vary regen current between 50 amps and the maximum value of regen current set by Function 9 FUNCTION 17 CARD TYPE SELECTION Push CONT 2 This function allows for the selection of the card type used for your vehicle s ...

Страница 46: ...ng 0 255 amps Resolution 0 815 per set unit Example Setting of 20 20 x 0 815 52 68 3 FUNCTION 24 FIELD WEAKENING START Push CONT 9 This function allows for setting the armature current at which minimum field current will be achieved Range 0 to 414 Amps Setting 0 to 255 Resolution 1 625 per set unit I MOTOR FWS VAL x 1 625 Example Setting of 20 32 5 amps FUNCTION 25 MONITOR Push CONT 10 This functi...

Страница 47: ...tting of 20 32 5 amps This FIELD WEAKENING START takes effect when the Mode 1 settings are called for by the Interactive Dash Display FUNCTION 50 MODE 1 MINIMUM FIELD CURRENT Push CONT 3 This function allows the adjustment of the field weakening level in order to set the top speed of the motor Min Max Set Resolution Per Unit Value Example If set at 71 0 20 51 to 176 0 16 amps 3 2 amps 0 30 51 to 2...

Страница 48: ... 58 MODE 3 MINIMUM FIELD CURRENT Push CONT 11 Same as Function 50 This MINIMUM FIELD CURRENT takes effect when the Mode 3 settings are called for by the Interactive Dash Display FUNCTION 59 MODE 3 RATIO Push CONT 12 Same as Function 51 This RATIO takes effect when the Mode 3 settings are called for by the Interactive Dash Display FUNCTION 60 MODE 4 ARMATURE CONTROLLED ACCELERATION AND 1A TIME Push...

Страница 49: ... function sets the armature current at which minimum field current will achieved The ratio setting isadjusted by Function 26 This function sets the ratio between armature and field current when transitioning from minimum field to maximum field current Setting is the value of field current changed for each 100 amps of armature current changed The full load transition point is calculated by the cont...

Страница 50: ...interactive modes consisting of 4 Controlled Acceleration levels 4 Field Weakening Pick Up levels and 4 Speed Limit levels These interactive modes are pre set using the Handset Functions 48 63 or a personal computer Functions 97 112 This feature allows the operator to select the best vehicle performance for changing factory task conditions The Custom Dash Display incorporates all the features and ...

Страница 51: ...Diagnostics Override With Fault Run Mode BDI Display or Blank Display no BDI used Diagnostics Override With Fault Key Switch Off Display Traction Hourmeter For Four Seconds Display Pump Hourmeter For Four Seconds Section 7 5 Outline Drawings g GE Electric Vehicle Motors Controls PY3 PY4 PY2 PY1 PY5 1 2 3 4 5 5 4 3 2 1 PY3 PY4 PY2 PY1 PUMP TRACTION BACK VIEW OF DISPLAY Wiring connections to Y plugs...

Страница 52: ...None 19 20 20 Maintenance Code HM Thou Hun HS or PC None 20 21 21 Auto Regen HS or PC None 21 22 22 Mode Reference HS or PC For DD on power up 22 23 23 Regen Cancel HS or PC None 23 24 24 FW Start HS or PC None 24 25 25 Monitor HS or PC GE Temporary Storage 25 26 26 Ratio HS or PC GE Temporary Storage 26 27 27 N A HS or PC GE Temporary Storage 27 28 28 Fault Count Pointer HS or PC None 28 29 29 Au...

Страница 53: ... Only Reset to Zero Only 66 67 Hours Tens Ones 9 PC Only Reset to Zero Only 67 68 Hours Thou Hun 9 PC Only Reset to Zero Only 68 69 36 Stored Status Code 10 PC Only Reset to Zero Only 69 70 BDI 10 PC Only Reset to Zero Only 70 71 Hours Tens Ones 10 PC Only Reset to Zero Only 71 72 Hours Thou Hun 10 PC Only Reset to Zero Only 72 73 38 Stored Status Code 11 PC Only Reset to Zero Only 73 74 BDI 11 PC...

Страница 54: ...play FWS 3 HS or PC None 106 107 58 Dash Display Ratio2 3 HS or PC None 107 108 59 Dash Display Speed Limit 2 3 HS or PC None 108 109 60 Dash Display CA 4 HS or PC None 109 110 61 Dash Display FWS 4 HS or PC None 110 111 62 Dash Display Ratio2 4 HS or PC None 111 112 63 Dash Display Speed Limit 2 4 HS or PC None 112 113 Secure HM Tens Ones PC Only OEM Read Only 113 114 Secure HM Thou Hun PC Only O...

Отзывы: