background image

The valve is OPEN when 

handle is in the position 

shown

 lock

 ring

fiGUrE 37 

fiGUrE 36 

Inlet valve

Outlet valve

fiGUrE 35 

 3

 

Vertical Systems:

Remove the System Cap using the Cap Wrench. The 

water level should be at least 2” above the Internal Prefilter 

spigot.

If the water level is below 2”, open the Inlet Valve slowly to 

raise the water level. 

 

Close the Inlet and Outlet Valves, leaving the Inlet 

Mini Ball Valve open. Using the Controller, initiate a Manual 

Flush sequence to bring System pressure to close to zero. 

Refer to the instructions in the 

Controller functions

 

section under

 E. inSTallaTiOn inSTrUCTiOnS

 on how 

to perform a Manual Flush sequence. Once the Pressure 

Gauge registers close to zero pressure, stop the Manual 

Flush immediately. 

2

 

 

Ensure that the two Mini Ball Valves are closed 

(To close, turn the handle perpendicular to the Plug/hose 

end). Remove the Plugs from the two Mini Ball Valves by 

depressing the lock ring and pulling on the Plug.  Insert 

a Pressure Gauge from the Integrity Test Kit into the Inlet 

Mini Ball Valve, open valve and observe System pressure.

 

Using the Controller, initiate a Manual Flush 

sequence. Refer to the instructions in the 

Controller func-

tions

 section under 

E. inSTallaTiOn inSTrUCTiOnS 

on how to perform a Manual Flush sequence. Following the 

Manual Flush, open a cold water tap that is downstream of 

the System. Allow water to flow for 15 minutes. The System 

requires a 15-minute flush to remove the food-grade factory 

preservative.

 3

Horizontal-mounted Systems: 

Ensure that there is still 

some water inside the System after the Manual Flush. Do 

not empty the System completely. If water stops coming out 

during the Manual Flush, open the Inlet Valve slowly to fill 

the System again. 

If an External Prefilter is installed, depress the red button 

on the External Prefilter head to allow air to escape from 

the External Prefilter housing. Once water emerges from 

the button, all air has been removed.

For 

Horizontally-mounted Systems

, check to make sure 

that no air comes out from either Air Relief Valve.

cleaning

 

Slowly

 open the Inlet Valve half way, allowing 

water into the System. Avoid opening the Inlet Valve quickly 

as this will introduce air pockets that will take longer to es-

cape.  Keep the Outlet Valve closed. Check for any leaks in 

the plumbing. If present, close the Inlet Valve immediately 

and repair. As pressure builds in the System, air will begin 

to escape from the Air Relief Valve. Once air is no longer 

passing through the Air Relief Valve, the System is pressur

-

ized.

2

 

fiGUrE 38 

19

Содержание Homespring UFC 100

Страница 1: ...8 23 G ANNUAL MAINTENANCE Pages 23 24 H WINTERIZATION Pages 25 27 I TROUBLESHOOTING Pages 28 29 J SPECIFICATIONS Pages 30 31 K FAQ Pages 32 33 L REPLACEMENT PART LIST AND PROCEDURES Pages 34 42 Operat...

Страница 2: ...d when installing or servicing the filtration system System Failure to do may result in System damage serious personal in jury death and or property damage Use of non OEM parts will void the manufactu...

Страница 3: ...ion Bypass Procedure 1 Close Inlet and Outlet Valves If ball valves are installed turn the handles perpendicular to the water pipe 2 Open Bypass Valve If ball valve is in stalled turn the handle in li...

Страница 4: ...e system Models with activated carbon filter option certified for cyst reduction may be used on disinfected waters that may contain filterable cysts The UFC 100 UFC 207 UFC 209 and UFC 211 models All...

Страница 5: ...ndard System with the exception of additional parts which must be installed as shown Additional parts include an Inlet Solenoid Valve Check Valve and External Prefilter Awater softener can be placed e...

Страница 6: ...pre assembled System Base Base Controller Transformer 120VAC Stainless Steel Prefilter Two Stainless Steel Flex Hoses Inside the bubble bag 1 Drain Solenoid Valve Normally Closed 1 Nylon Elbow 2 Bras...

Страница 7: ...ne diverted from the main water line is recommended to be installed upstream of the System for all exterior taps pool or hot tub makeup valves and irrigation systems This set up will help prolong the...

Страница 8: ...The vertical spacing required is 36 from the bottom of the bracket If possible install the System at a height convenient for servicing Installation Drill into the concrete floor or block and anchor th...

Страница 9: ...et up align the top mounting hole on the Bracket assembly with the pre drilled hole on the wall stud and secure the Bracket assembly with one 2 anchoring bolt Do not tighten this bolt completely 4b Th...

Страница 10: ...to the local plumbing code in your area The directional arrow on the Inlet Solenoid Valve must point in the direction of the water flow Do not pressurize the Backpulse Tank to greater than 35psi Highe...

Страница 11: ...all the Drain Solenoid Valve to the Brass Elbow using another Nipple 7b For UFC100 UF100 and UF100 with optional Surface Water Option Kit models connect the Drain Solenoid Valve normally closed to the...

Страница 12: ...n in this manual to install the External Prefilter Connect the Stain less Steel Flex Hose on the Inlet Fitting assembly to the External Prefilter Once finished connect the External Prefilter to the MN...

Страница 13: ...n the connection Take care not to cross thread this connection Fibre Chamber Air Vent Assembly 3 Complete Pre filter Chamber Air Vent Assembly as shown in FIGURE 24a A second Air Relief Valve is provi...

Страница 14: ...A dedicated trap drain must be installed by a li censed plumber due to the complexity of venting sizing and trap installation Improper venting and trap installation can lead to sewer gases backing up...

Страница 15: ...e Controller to the wall by tightening the two screws Use the plastic anchors if necessary 2 Ensure the transformer is not plugged into the electrical receptacle Connect the power supply cable from th...

Страница 16: ...f power failure and will not activate the flushing and draining sequences NOTE Once the Controller is set the Controller will remember the Start Time Program Number and Flush Drain Interval settings i...

Страница 17: ...ncrease frequency of flush drain cycle if the System TMP rises too quickly Increasing the number of Flush Drain cycles per day will prolong the life of the System however morewaterwillbeusedforsystemc...

Страница 18: ...ing the Cap Wrench For models with a Stainless Steel Prefilter a Carbon Pre filter may be purchased separately if desired The Surface Water Option Kit is purchased separately from the System except fo...

Страница 19: ...Controller Func tions section under E INSTALLATION INSTRUCTIONS on how to perform a Manual Flush sequence Following the Manual Flush open a cold water tap that is downstream of the System Allow water...

Страница 20: ...e the flushing is complete open the Outlet Valve and a nearby COLD water tap to flush most of the chlorine from the System Run the tap fully open for at least 10 minutes Further flushing must be perfo...

Страница 21: ...ity Tester into a power supply Press any button twice to turn it on Press the scroll keys until the screen displays Integrity Test Press ENTER and use the scroll keys to choose either Vertical or Hori...

Страница 22: ...cause is a leak in the System from hoses connections or valves Be sure that all connections are tight before beginning the test and the Inlet and Outlet Valves are closed Leaky valves and loose connec...

Страница 23: ...the System to protect your hands At the end of the procedure wash your hands thoroughly with soap and water Do not reuse the gloves Dispose of the gloves in the garbage Complete Paperwork The followi...

Страница 24: ...Installation section under E INSTALLATION INSTRUCTIONS to install a new External Prefilter cartridge 4 Be careful to avoid MC1 cleaning agent coming in contact with skin or clothing Wash the mixing co...

Страница 25: ...by installing a MNPT PVC plug H WINTERIZATION PROCEDURE 4 If an External Prefilter has been installed open the Mini Ball Valve on the bottom of the housing and allow to drain Press the red button on...

Страница 26: ...Reinstall the plug into the Outlet Stainless Steel Flex Hose Fill with approximately 3 US gal 12litres of 58o F 50o C propylene glycol based plumbing antifreeze The UFC 207 UF 207 UFC 209 UF 209 UFC...

Страница 27: ...nlet Valve and Outlet Valve Use the Controller to depressurize the System Use Pressure Gauges to ensure no pressure remains in the System Open Note If the winterization spring start up is combined wit...

Страница 28: ...STALLATION INSTRUCTIONS initiate a manual flush and verify Drain Solenoid Valve is working Replace valve if necessary Water does not flow through System Black cap on Air Vent must be backed off by 1 5...

Страница 29: ...heard from the Drain Solenoid Valve Replace valve if necessary Check connections are installed correctly and transformer is plugged in Inlet Solenoid Valve Doesn t close to allow System to drain On th...

Страница 30: ...8 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres 7 5 19 5 gal 28 4 73 7 litres System efficiency 92 96 92 96 94 97 87 94 4 92 96 4 94 97 4 Controller voltage 24 VAC 24 VAC 2...

Страница 31: ...litres 15 gal 56 7 litres Program 3 4 flush backpulse cycles 2 flush backpulse cycles 1 drain cycle 2 flush backpulse cycles 1 drain cycle Estimated water use US gallons 20 gal 75 6 litres 13 5 gal 5...

Страница 32: ...re removed as the water passes from the outside of the Prefilter to the inside 2 The prefiltered water then passes down into the System to the membrane chamber 3 In the membrane chamber the water trav...

Страница 33: ...he membrane and remain in your water This includes calcium and magnesium which contribute to your hard water and other dissolved solids like essential minerials and flouride How long does the automati...

Страница 34: ...ressurize the System by turning on a tap until no water flows out from the tap 3 Drain the System by activating a Manual Flush sequence Refer to the instructions in the Controller Functions section un...

Страница 35: ...bythehand 33 Reattach the Locking Clip Air Relief Valve Inlet Outlet Drain pipe assemblies Internal Prefilter System Cap External Prefilter if applicable and the Air Vent Assembly Reattach the Metal S...

Страница 36: ...carefully remove and dispose of the Internal Prefilter D EXTERNAL PREFILTER REPLACEMENT Depending on the water quality the External Prefilter may need to be washed or replaced prior to the Annual Mai...

Страница 37: ...37...

Страница 38: ...UFC100 UF100 UF100 with Surface Water Option Kit Series 2 1 3 4 7 6 5 9 8 10 11 15 16 17 14 4 25 26 12 FIGURE 60 18 19 23 20 21 22 13 24 38...

Страница 39: ...rvice Tag X X X 14 23029 Cap Wrench X X X Sub Assembly Kits 15 23117 Installation Sub Assembly Kit Inlet Pipe Assembly Kit Outlet Pipe Assembly Kit Drain Pipe Assembly Kit Air Relief Valve X X X 16 23...

Страница 40: ...1 3 2 6 5 8 8 9 14 15 16 17 23 19 20 18 25 30 31 32 33 UFC 207 UF 207 UFC 209 UF 209 UFC 211 and UF 211 Series 21 24 FIGURE 61 11 10 22 27 26 28 29 7 4 40 13 12...

Страница 41: ...153 System Cap Short X 15 23154 System Cap Long X 16 23214 Loading O ring X X 17 23260 Kit Locking Clip with mounting screw X X 18 23159 System Base X X 19 23172 Thimble Filter X X 20 23221 Plug 1 4 N...

Страница 42: ...3060 Wall Bracket 8 23061 1 to Reducing Bushing 9 23183 Mini Ball Valve Plug 10 23062 Mini Ball Valve 11 23104 Housing Wrench External Prefilter Service Testing Kit Parts 12 23104 Housing Wrench Exter...

Страница 43: ......

Отзывы: