LCD
GRAPHIC
FACTORY
FUNCTION
DISPLAY
SETTING
DESCRIPTION
SETTING
6-21
* 50
FDT HYSTR
FREQUENCY DETECTION HYSTERESIS
1.0
The setting is the offset that FDT will
have from the FDT level. Adjustable from
0.0 to 30 Hz.
* 51
OL WARNING
OVERLOAD EARLY WARNING
RATED
This open collector output is active when
CURRENT
the output current exceeds the OL setting.
This output can be used in conjunction with
a relay unit to allow connection to system
control circuitry. Adjustable from approx-
imately 20 to 135% of drive rated current.
NOTE: This is a timed function similar to
Function Code 08 and 09 (ELCTRN OL).
* 52
53-59
FUNCTION CODE BLOCK DISPLAY
0
This setting determines whether or not
Function Codes 53 through 59 will be displayed
and available for adjustment.
0:
Function Codes 53 through 59 NOT displayed.
1:
Function Codes 53 through 59 displayed.
Output
Frequency
FDT
Signal
FDT Hyster
FDT Level
Hz
0
t
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Fuji Electric AF-300ES
Страница 32: ...3 16 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 55: ...5 9 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 58: ...5 12 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 96: ...7 4 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 122: ...10 6 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 134: ...12 6 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...