4-12
Drive Interface Details
Figure 4-11. AUTOMATIC RESTART CIRCUIT CONNECTIONS
— Timer setting (T
M
) is fixed in software at 5 seconds.
— Timer starts after an initializing time of 2 seconds
maximum when power returns.
— Timer output is selectable from Y1 through Y5. This
function is active when "A" is selected and pro-
grammed into Function Code 47.
— Used to avoid Er6 after power failure, and re-applica-
tion of main AC power.
WARNING:
Personal safety must be considered when activating this
function.
Automatic Restart Circuit Connection
OUTPUT TERMINALS Y1 – Y5
INPUT TERMINAL FWD, REV, X1-X5, HLD, BX, THR, RST
27 VDC MAX
50 mA MAX
0 to +10 VDC
+4 to +20 mA dc
1 - 5K Ohms
2 WATT
22K Ohms
22K Ohms
250 Ohms