4-8
Table 5:
Terminal Identification/Function
Terminal
Terminal
Label
Name
Function
POWER TERMINAL BOARD
L1, L2,
ac Supply Line
Connection for commercial power (200-230 VAC or 380-460 VAC);
L3
Input Terminals
3-phase; 50⁄60 Hz.
U, V, W
Drive Output
Connection for 3-phase induction motor.
Terminals
P+, DB
External Braking
Connection for external braking resistor.
Resistor Terminals
(Only on 10 Hp or less.)
N-, P+
External Braking
Connection for external braking resistor via external braking unit.
Unit Terminals
(Only required on 15 Hp)
P+, P1
DC Reactor
Connection for a dc link reactor on unit rated 100 Hp and greater.
These terminals are jumpered on units rated 75 Hp and less.
E (G)
Ground Terminal
Connection for ground. Note: Be sure to ground the chassis to
prevent electrical shock & to reduce radio noise.
RO, TO
Control Power
Connection point for single-phase, 460 ac power for backing up the
Auxiliary Input
control circuit power when input starter is used (40 Hp and greater.)
U1, U2
Auxiliary Transformer
Factory connection set at U1 for 400 - 460 VAC input.
Taps
Reconnect to U2 for 380 VAC input. (40 Hp and greater)
CONTROL TERMINAL BOARD
Frequency Setting
Common terminal for terminals 12, 13, C1 & V1, and FMA (Do not
11
Common Terminal
connect to CM terminal or electrical noise immunity may be lost.)
12
Frequency Setting
When 0 to +10 VDC (0 to 5V) is input, the maximum frequency is
Voltage Input
reached at +10 VDC (5V) and is proportional to output frequency
down to 0 VDC. Input impedance is 22K ohm. Must be isolated source.
13
Frequency Setting
Reg10 VDC power supply for frequency setting potentiometer,
Voltage Output Term.
10mA or less (13 to terminal 11.)
C1
Frequency Setting
When the input signal is +4 to +20mA dc, the maximum frequency is
Current Input
reached at 20mA and is proportional down to a minimum frequency
setting at 4mA. Input impedance is 250 ohm. Must be isolated source.
V1
Voltage Input
Reaches maximum output frequency at +/- 10 VDC (the output
Auxiliary Terminal
freq. is proportional down to 0 VDC.) Input impedance is 22K ohms.
Must be isolated source.
CM
Control Circuit
Common terminal for control input commands, and FMP pulse
Common Terminal
output signal. (Do not connect to terminal 11.)
FWD
Forward Command
Input Terminal
Forward command via FWD-CM (closed). Reverse command via
REV-CM (closed). When FWD-CM is closed and REV-CM is closed
Reverse Command
at the same time, the drive will decelerate to stop.
REV
Input Terminal
BX
Motor Coast-To-Stop
Motor will coast-to-stop with BX-CM (closed). (For use when
Input Terminal
applying mechanical brake with drive in operation.) Note: If
BX-CM is opened with FWD or REV closed, the drive will start
operating.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Fuji Electric AF-300ES
Страница 32: ...3 16 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 55: ...5 9 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 58: ...5 12 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 96: ...7 4 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 122: ...10 6 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 134: ...12 6 Notes Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...