WIRING
4
•
NOTE:
Make all electrical connections in accordance
with the National Electrical Code and any applicable
local code requirements.
•
NOTE:
Verify that supply voltage is correct by
comparing it to nameplate.
UL Units:
•
Terminals are readily accessible on terminal board
and will accept service leads ranging in size from
AWG No. 16 through No. 6.
• Service leads (See fixture labeling for supply wire
temperature rating) should extend through mounting
bracket approximately 7 inches.
•
Attach service leads to terminal board as shown on
luminaire nameplate.
•
See table below for screw torques (See Table 1).
•
Dimming Control Connections (See Table 2).
•
A wiring diagram is provided on a label in luminaire.
PhOTOELECTRIC CONTROL
5
•
When used, photoelectric (PE) receptacle should be
oriented so that the word “North” is directed toward
true north.
•
This is done by seating a PE control into receptacle,
lifting upward on PE control (which will lift PE
receptacle also), and rotating them clockwise until
word “North” is directed toward true north.
• Then lower PE control and receptacle to firmly seat
them into position. No tools are required to make this
adjustment.
•
Alternatively, PE receptacle can be oriented
before PE control is installed. This is done by lifting up
on rim of the PE receptacle and rotating it until the
word “North” is directed toward true north.
• Lower PE receptacle to firmly seat it in this position.
Then install PE control.
TABLE 1. Terminal Board Torque Table UL Units
Wire Range Copper Aluminum
Torque (in lbs)
10 - 16 SOL, STR
30
8 - 6 SOL, STR
STR6 SOL, STR
45
TABLE 2. Dimming Control Connections
O VDC (-)
Gray Lead
Up to 10 VDC (+)
Violet Lead
IEC Units:
•
Power supply cable and dimming control cable (if
necessary) must be provided by customer.
•
Power supply cable (each conductor: phase, neutral
and ground) should be maximum of 12AWG (2.5mm
2
)
and minimum of 16 AWG (1.5mm
2
) solid or stranded
with an overall cable diameter within the range of 7-12mm.
•
Dimming control cable (0 to 10 VDC) (each conductor:
positive and negative) should be 18 AWG (1.0mm
2
)
solid or stranded with an overall cable diameter
within the range of 5-10mm.
Captive Fastener
Door Latch
Power Door
Terminal Board Connections:
Terminal Board Position
Supply Type
L1
High Line
G
Ground
N/L2
Low Line/Neutral