CHAPTER 5: COMMUNICATIONS
EPM 5100 ELECTRONIC POWER METER – USER GUIDE
5–3
The dynamic value registers contain information relating to variable operating parameters
such as phase current and phase voltage. These registers are read-only and their contents
cannot be changed by the user.
The setpoint registers contain information that configures the device to operate in a user-
defined manner. These registers may be read over the modbus network, but may not be
written over the network. Any changes to the setpoint registers can only be made via the
faceplate.
The command coils (registers) allow you to cause specific control actions to take place at
the device, such as Clear Energy Accumulators.
Addresses designated with L suffix return a Long Signed Integer value concatenated from
two successive registers. Addresses designated with F suffix return a floating point value
concatenated from two successive registers. Addresses designated with Ann suffix return
an array read from nn successive registers.
NOTE
Table 5–2: Modbus Memory Map (Sheet 1 of 3)
Register
Mnemonic
Contents
Range / Units
R/W
Format
Command Coils
R00000
CLEAR_DMND
Clear power demand (watts)
0 to 1
WO
F17
R00001
MTR_INITIALIZE
Initialize meter
0 to 1
WO
F17
R00002
CLEAR_ENERGY
Clear energy (var-hour)
0 to 1
WO
F17
R00003
CLEAR_ERROR
Clear meter errors
0 to 1
WO
F17
Dynamic Value Registers
R31000
PENDING_EVENTS
Number of pending event messages
0 to 8
RO
F1
R31002F
KVA_MAX_TOTAL
kVA max, total of all phases
kVA
RO
F4
R31004F
KW_MAX_TOTAL
kW max, total of all phases
kW
RO
F4
R31006F
KVAR_LG_MAX_TOTAL
kvar lag max, total of all phases
kvar
RO
F4
R31008F
KVAR_LD_MAX_TOTAL
kvar lead max, total of all phases
kvar
RO
F4
R31010F
AMPS_MAX_A
Current Max Phase A
amps
RO
F4
R31012F
AMPS_MAX_B
Current Max Phase B
amps
RO
F4
R31014F
AMPS_MAX_C
Current Max Phase C
amps
RO
F4
R31016F
KVARH_LG_TOTAL
kvarh lag, total of all phases
kVARh
RO
F4
R31018F
KVARH_LD_TOTAL
kvarh lead, total of all phases
kVARh
RO
F4
R31020F
KWH_TOTAL
kWh, total of all phases
kWh
RO
F4
R31022F
KQH_TOTAL
kQh, total of all phases
kqhQ = (
x var + W
) / 2
RO
F4
R31024F
KVAH_TOTAL
kVAh, total of all phases
kVAh
RO
F4
R31026F
PF_AVG
Average power factor since last reset, all phases
---
RO
F4
R31028F
PF_AT_KVA_MAX
Power factor, total of all phases, at maximum kVA
---
RO
F4
R31030F
KVA_DMND_TOTAL
Apparent power demand (kVA), total of all phases
kVA
RO
F4
R31032F
KW_DMND_TOTAL
Real power demand (kW) total of all phases
kW
RO
F4
R31034F
KVAR_LG_DMND_TOTAL
Reactive power demand (kvar lag), total of all phases
kvar
RO
F4
R31036F
KVAR_LD_DMND_TOTAL
Reactive power demand (kvar lead), total of all phases
kvar
RO
F4
R31038F
AMPS_DMND_A
Current demand, phase A
amps
RO
F4
R31040F
AMPS_DMND_B
Current demand, phase B
amps
RO
F4
R31042F
AMPS_DMND_C
Current demand, phase C
amps
RO
F4
R31044F
PF_DMND
Power factor, all phases (over last demand interval)
---
RO
F4
R31046F
KW_A
Real power (kW), phase A
kW
RO
F4
R31048F
KW_B
Real power (kW), phase B
kW
RO
F4
R31050F
KW_C
Real power (kW), phase C
kW
RO
F4
R31052F
KVAR_A
Reactive power (kvar), phase A
kvar
RO
F4
R31054F
KVAR_B
Reactive power (kvar), phase B
kvar
RO
F4
R31056F
KVAR_C
Reactive power (kvar), phase C
kvar
RO
F4
R31058F
KVA_A
Apparent power (kVA), phase A
kVA
RO
F4
3
Содержание EPM 5100
Страница 2: ...Courtesy of NationalSwitchgear com ...
Страница 6: ...4 4 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER4 Courtesy of NationalSwitchgear com ...
Страница 20: ...1 14 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 1 OVERVIEW Courtesy of NationalSwitchgear com ...
Страница 38: ...2 18 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 2 INSTALLATION Courtesy of NationalSwitchgear com ...
Страница 48: ...3 10 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 3 METERING Courtesy of NationalSwitchgear com ...
Страница 68: ...4 20 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 4 PROGRAMMING Courtesy of NationalSwitchgear com ...
Страница 76: ...5 8 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 5 COMMUNICATIONS Courtesy of NationalSwitchgear com ...
Страница 82: ...6 6 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 6 MISCELLANEOUS Courtesy of NationalSwitchgear com ...