5–4
EPM 5100 ELECTRONIC POWER METER – USER GUIDE
CHAPTER 5: COMMUNICATIONS
R31060F
KVA_B
Apparent power (kVA), phase B
kVA
RO
F4
R31062F
KVA_C
Apparent power (kVA), phase C
kVA
RO
F4
R31064F
PF_A
Power factor, Phase A
---
RO
F4
R31066F
PF_B
Power factor, Phase B
---
RO
F4
R31068F
PF_C
Power factor, Phase C
---
RO
F4
R31070F
KVA_TOTAL
Apparent power (kVA), total of all phases
kVA
RO
F4
R31072F
KW_TOTAL
Real power (kW), total of all phases
kW
RO
F4
R31074F
KVAR_TOTAL
Reactive power (kvar), total of all phases
kVAR
RO
F4
R31076F
VOLTS_A
L-N voltage, phase A-N
volts
RO
F4
R31078F
VOLTS_B
L-N voltage, phase B-N
volts
RO
F4
R31080F
VOLTS_C
L-N voltage, phase C-N
volts
RO
F4
R31082F
VOLTS_AB
L-L voltage, phase A-B
volts
RO
F4
R31084F
VOLTS_BC
L-L voltage, phase B-C
volts
RO
F4
R31086F
VOLTS_CA
L-L voltage, phase C-A
volts
RO
F4
R31088F
PF
Total power factor of all phases
---
RO
F4
R31090F
KW_TOTAL_AT_KVA_MAX
Real power (KW), total of all phases at maximum kVA
kW
RO
F4
R31092F
AMPS_A
Current, phase A
amps
RO
F4
R31094F
AMPS_B
Current, phase B
amps
RO
F4
R31096F
AMPS_C
Current, phase C
amps
RO
F4
R31098F
AMPS_N
Neutral current
amps
RO
F4
R31100F
FREQUENCY
Frequency
Hz
RO
F4
R31102
TIME_LEFT
Time left in demand interval
seconds
RO
F1
R31103
NO_OF_RESET
Number of resets
0 to 255
RO
F5
R31104
NO_OF_PWR_FAILS
Number of power failures
0 to 255
RO
F5
R31105
METER_ERROR
Meter error flags
---
RO
F6
R31106
VOLTS_PHASE_ERR
Voltage phase loss errors
---
RO
F7
R31107
LD_LG_PF_TOTAL
Lead/lag qualifier for all phases (instantaneous)
0 to 1
RO
F8
R31108
LD_LG_PF_A
Lead/Lag qualifier for phase A (instantaneous)
0 to 1
RO
F8
R31109
LD_LG_PF_B
Lead/Lag qualifier for phase B (instantaneous)
0 to 1
RO
F8
R31110
LD_LG_PF_C
Lead/Lag qualifier for phase C (instantaneous)
0 to 1
RO
F8
R31111
DATA_RESET_FLAG
Data Resetting flags
---
RO
F9
R31112F
PREV_ACCUM_WH
Previous Accumulated Wh
Wh
RO
F4
R31114F
PREV_ACCUM_VARH_LG
Previous Accumulated varh lagging
varh
RO
F4
R31116F
PREV_ACCUM_VARH_LD
Previous Accumulated varh leading
varh
RO
F4
R31118
DATA_CLR_STATUS
Data Cleared Status
0- Not Cleared1 -
Cleared
RO
F10
Fixed Value Registers
R40000
PRODUCT_ID
Product Id
always 0Eh
RO
F1
R40002
---
Reserved
---
---
---
R40003
MODBUS_ADDR
Modbus Address
33 to 215
RO
F1
R40004L
SERIAL_NUM
Serial Number
---
RO
F2
R40006L
SW_REV
Firmware Revision
00.00 to 99.99
RO
F3
R40008
COC_REV
COC Software Revision
---
RO
F3
R40009
---
---
---
---
---
Setpoint Value Registers
R43000
HOUR
Hour
0 to 23 hrs.
RW
F1
R43001
MIN
Minute
0 to 59 min.
RW
F1
R43002
SEC
Seconds
0 to 59 sec.
RW
F1
R43003
PASSWORD
Password
always 00h
RO
F1
R43005F
PULSE_VALUE_1
Pulse value interval time for pulse KYZ output 1
0 to 999.999999
RO
F4
R43007F
PULSE_VALUE_2
Pulse value interval time for pulse KYZ output 2
0 to 999.999999
RO
F4
R43009
PULSE_UNIT_1
Pulse units for KYZ output 1
---
RO
F11
R43010
PULSE_UNIT_2
Pulse units for KYZ output 2
---
RO
F11
R43011L
CONFIG_FLAG_1
Programming flags
---
RO
F12
Table 5–2: Modbus Memory Map (Sheet 2 of 3)
Register
Mnemonic
Contents
Range / Units
R/W
Format
Содержание EPM 5100
Страница 2: ...Courtesy of NationalSwitchgear com ...
Страница 6: ...4 4 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER4 Courtesy of NationalSwitchgear com ...
Страница 20: ...1 14 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 1 OVERVIEW Courtesy of NationalSwitchgear com ...
Страница 38: ...2 18 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 2 INSTALLATION Courtesy of NationalSwitchgear com ...
Страница 48: ...3 10 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 3 METERING Courtesy of NationalSwitchgear com ...
Страница 68: ...4 20 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 4 PROGRAMMING Courtesy of NationalSwitchgear com ...
Страница 76: ...5 8 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 5 COMMUNICATIONS Courtesy of NationalSwitchgear com ...
Страница 82: ...6 6 EPM 5100 ELECTRONIC POWER METER USER GUIDE CHAPTER 6 MISCELLANEOUS Courtesy of NationalSwitchgear com ...