EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
Install AKD-10—Neutral Rogowski Current Transformer (CT)
•
Turn off all power to switchgear. Tagout
and lockout main source, up-stream or
main breaker.
•
Failure to comply with these instructions
will result in death or serious injury from
severe burns caused by arc flashing that
has exceedingly high temperatures.
•
Always wear personal protection
equipment according to OSHA standards
and appropriate to the severity of
potential burns.
•
Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.
AKD-10—Neutral CT Assembly, Bus Compartment
The AKD-10 EntelliGuard R Circuit Breaker uses an air-core Rogowski Current sensor to measure current
level. Legacy AK and AKR breakers used iron core CTs . For the Retrofill breaker to calculate the current
levels on a 4-wire circuit, the Neutral Iron Core CT in the cable compartment needs to be replaced with a
Rogowski style CT
or
have iron core CT output modified by a neutral CT adapter See
Neutral CT Adapter.
The Rogowski CT comes mounted on copper bars matching the same hole-pattern as the existing neutral
bar. Neutral CT wires from the Rogowski coil to the AKD-10 gray terminal blocks must be run as a “twisted
pair”. Existing wires from the gray block to the 36 pt. secondary disconnect may remain as they are.
Table 10
shows the Rogowski assembly part numbers for AKD-10 Switchgear.
AKD-10—Rogowski Assembly Part Numbers
Table 10. AKD-10—Rogowski Assemblies (Neutral Bus Part Numbers)
Switchgear/Breaker
Rogowski Assembly or
Neutral Bus Bar
Part Number
Figure References for Assembly Drawings
AKD-10 400A
10108266G1
Figure 25
. Neutral Bus Rogowski ASM 10108266
AKD-10 800A
10108266G3
Figure 25
. Neutral Bus Rogowski ASM 10108266
AKD-10 1600A
10108266G6
Figure 25
. Neutral Bus Rogowski ASM 10108266
AKD-10 2000A
10108266G7
Figure 25
. Neutral Bus Rogowski ASM 10108266