EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
Table 9A. WavePro to EntelliGuard R wiring - Continued
WAVEPRO
ENTELLIGUARD R
COMMAND
CLOSE COIL
COMMAND
CLOSE COIL
A9
C9
PH
PH
IMM
CMD
A18
N
COMM
A9
A11
PH
PH
IMM
CMD
A10
N
COMM
SECOND UV
SECOND UV
C5
C14
A13
A12
SECOND I/P
SECOND I/P
SECOND O/P
SECOND O/P
C32
C28
A30
A29
C36
C31
B3
B2
NET WORK
INTERLOCK
C19
C18
C21
C20
SET
(TRIP)
RESET
COMM
COMM
NET WORK
INTERLOCK
A6
A5
A8
A7
SET
(TRIP)
RESET
COMM
COMM
NI STATUS
SWITCH
C30
C29
WAVEPRO
ENTELLIGUARD R
SHUNT TRIP #1 @
(ONLY FOR >120VDC)
A7
A5
A6
A14
A21
A20
A6
A5
B25
B26
SHUNT TRIP #1 @
(ONLY FOR >120VDC)
C5
C14
SHUNT TRIP #2 %
(ONLY FOR >120VDC)
B20
B19
A13
A12
B17
B18
SHUNT TRIP #2 %
(ONLY FOR >120VDC)
A15
NI STATUS
SWITCH
B6
B5
@ - NEED ENTELLIGUARD R 4NO, 4NC AUX
SWITCHES
% - NEED ENTELLIGUARD R 8NO, 8NC AUX
SWITCHES
DASHES INDICATE
EXTERNAL JUMPERS