EntelliGuard R Circuit Breaker Retrofill AKD-10 Installation Manual DEH41550 R06
21.
At the end of 37 rotations, the breaker is in its maximum travel position. At this point, the primary
disconnect fingers have completely engaged with the primary bus stabs.
22.
Remove and store the racking handle in it storage location.
AKD-10—Racked-In
The photo below shows one example of a racked-in AKD-10 Retrofill (
Figure 11
).
Figure 11. AKD-10— Racked-In CB