DR60
43
DR60-TM-EN-
2A
▪
<Edit>: this button edits a selected pre-existing dataset. Clicking on this
button, the dataset parameters will appear for editing.
▪
<Delete>: this button deletes a selected pre-existing dataset. The DigInput1
dataset cannot be deleted.
▪
Functional Constraint: selects the functional constraint that indicates the possible
operating services of a specific DataAttribute. The functional constraints are:
▪
ST: Status Information;
▪
MX: Measurements;
▪
CO: Control;
▪
SP: Setting Point;
▪
SG: Setting Group;
▪
SE: Setting Group Editable
▪
SV: Substitution
▪
CF: Configuration
▪
DC: Description
▪
EX: Extended Definition
▪
Dataset Name: inserts a name for the new dataset. Maximum characters: 32.
Possible characters: a-z, A-Z, a-9, _.
▪
Description: inserts a description for the new dataset. Maximum characters: 64.
Possible characters: except “<” and “>”.
▪
Filter: enables the user to filter the global dataset by DataAttribute names.
Note:
When selecting the data for the dataset, the IEC 61850 name for binary inputs is
DIGITALGGIO and the binary outputs as OUTPUTGGIO.
5.4.3
GOOSE Publisher
To publish GOOSE messages grouped in datasets, it is necessary to create a GOOSE
Control Block (GCB). In the GOOSE Publisher subtab it is possible to create and edit
GOOSE Control Blocks for the GOOSE messages transmission.
Each GCB is associated with one Dataset and the DR60 is able to send up to 16 GCB.
The configurable parameters are described below:
▪
GOOSE Control Block Identification
▪
Message Name: inserts a name for the GOOSE Control Block. The allowed
characters are 0-9, a-z, A-
Z and ‘_’.
Maximum characters: 32.
▪
Description: inserts a description for the GOOSE Control Block. The not
allowed characters are ‘<’ and ‘>’.
Maximum characters: 64.
▪
GOOSE ID: inserts an identification for the GOOSE Control Block. The allowed
characters are 0-9, a-z, A-
Z and ‘_’.
Maximum characters: 129.
▪
Dataset: selects the dataset for this GOOSE Control Block. In this field will
appear all created datasets.