DR60
27
DR60-TM-EN-
2A
LED
Color
Indicator
Meaning
Alarm
Orange
Warning
An alarm event that
does not compromise
the DR60 functions was
detected
Red
Alarm
An alarm event that
compromised DR60
functions was detected
In Service
Green
In Service
DR60 is working in
perfect conditions
Sync
Green
Global
DR60 is synchronized
with the time reference
clock that is
synchronized with
satellite reference
Orange
Local
DR60 is synchronized
with the time reference
clock that is not
synchronized with
satellite reference
Trigger
Green
Trigger
Any trigger occurred
Orange
Re-trigger
Any trigger reoccurred
The table below shows which events are considered alarms and warnings.
Alarms
Data Name
Description
Sync NOT OK
BSE/ALARMSGGIO1.Alm1
Card not detected, invalid
or incompatible
BSE/ALARMSGGIO1. Alm2
Happens when there are
discrepancies between the
installed boards and the
device CORTEC
Internal voltage
BSE/ALARMSGGIO1. Alm3
Internal voltage
automonitoring alarm
Internal temperature
BSE/ALARMSGGIO1. Alm4
Internal temperature is
abnormal (Out of -10°C to
60ºC)
No communication
Ethernet interface 1
BSE/ALARMSGGIO1. Alm5
Loss of communication
with ethernet interface 1
Содержание DR60
Страница 12: ...12 DR60 TM EN 2A ptpd internal BSD ...
Страница 24: ......
Страница 78: ......
Страница 93: ...DR60 93 DR60 TM EN 2A Binary inputs and outputs of the B2 board 8 BO 6 BI ...
Страница 106: ......