DR60
47
DR60-TM-EN-
2A
▪
Dataset: Associates the PMU stream with a PMU dataset. The PMU dataset is
created automatically when the PMU is activated for a circuit in the
Analog
configuration tab and it can be edited in the
Communication>Dataset
tab.
▪
Frame Rate: Selects the frame rate for the respective stream. 60 fps at 60 Hz
and 50 fps at 50 Hz are available.
▪
Communication Mode: Configures the communication or operation mode of
the stream. The configurations available are: Commanded, Spontaneous
Unicast or Spontaneous Multicast.
▪
Protocol: Choses between the UDP/IP or TCP/IP transmission protocols.
▪
Source Port: Chooses the source port of the respective stream. Each stream
needs to have an exclusive port number. Multiple streams cannot be sent with
the same port number.
▪
Destinations Address: Configure the destination IP address and port number
for the spontaneous transmissions.
▪
Output Interface: In case the destination address is not in the same submask
as one of the ethernet ports, the streams will be sent through the Ethertnet 1
interface
5.4.7
DNP3
The DR60 provides DNP3 implementation level 2 for outstation equipment via both
Ethernet or serial communication.
This tab allows the configuration of the communication parameters of the DNP3
streams.
The following configuration parameters are available:
▪
Enabled: Turn on or off the DNP3 streaming.
▪
DNP3 Communication: Selects the physical interfaces that will send DNP3.
Ethernet, Serial port 1 or serial port 2.
▪
Master IP Address: IP address of the equipment reading the DNP3.
▪
Outstation Address: DNP3 address of the DR60 being configured. Range 0 to
65534.
▪
Outstation port: Port number for the DR60 being configured. 20000 is the
default and the port number registered for DNP3 use with the IANA (Internet
Assigned Numbers Authority).
▪
Application Timeout: The timeout for an application layer confirmation in
seconds. Range 0,01 to 40 s.
▪
Link Layer Timeout: The timeout for a data link layer confirmation in seconds.
Range 0,01 to 40 s.
▪
Enable Unsolicited Reporting:
▪
Server address to report to: DNP3 address of the server
(master)show
▪
Class 1, 2, 3
▪
Max Delay: Maximum time the outstation waits until sending the
data pertaining to each class in case no data state change or DNP3
threshold is exceeded.