6. OPTIONS
6.1
EXTENDED RUN-TIME VERSIONS
Extended run-time versions are equipped with additional batteries to increase the autonomy
time of the unit.
These additional batteries are housed in a separate battery cabinet.
Additional batteries will increase the recharging time for the unit.
All other operational information is the same.
If a battery cabinet is connected, the UPS must be informed about the new total battery
capacity to allow a reliable recalculation of the available runtime. Please contact your dealer.
Dependent of the charge condition of the new batteries the new autonomy calculations may
temporarily be unreliable.
Connecting an external charger may cause damage to the UPS. As the batteries are not
galvanically separated from the mains input, the external charger must be galvanically
separated from the mains.
Using an external charger will cause a false autonomy prediction during charging time, the
correct autonomy will be shown 10 hours after reaching battery float charge.
Battery packs can be connected in parallel to increase the autonomy.
All the necessary protection and connection material is included in the delivery.
LP 31
: 8 kVA
10 kVA
15 kVA
20 kVA
Extension
1
:
7Ah
7Ah
14Ah
14Ah
Total capacity
: 14Ah
14Ah
28Ah
28Ah
Typical autonomy 100% / 50% load, minutes : 36/78
25/58
33/75
25/58
Number of packs required
:
*
*
1
1
Extension
2
:
14Ah
14Ah
28Ah
28Ah
Total capacity
(7Ah in
LP 31
/ 10 kVA)
:
21Ah
21Ah
42Ah
42Ah
Autonomia tipica a 100% / 50% load, minutes : 58/120
40/92
55/120
41/96
Number of packs required
: 1
1
2
2
Extension
3
:
14Ah
14Ah
Total capacity
(14Ah in
LP 31
/ 10 kVA)
:
28Ah 28Ah
Typical autonomy 100% / 50% load, minutes : 80/162
58/125
Number of packs required
: 1
1
Extension
4
:
28Ah
28Ah
Total capacity
(7Ah in
LP 31
/ 10 kVA)
:
35Ah
35Ah
Typical autonomy 100% / 50% load, minutes : 101/204
78/156
Number of packs required
: 2
2
Extension
5
:
28Ah
28Ah
Total capacity
(14Ah in
LP 31
/ 10 kVA)
:
42Ah 42Ah
Typical autonomy 100% / 50% load, minutes : 123/256
96/188
Number of packs required
2
2
*
Can be placed in standard UPS cubicle
6.2
SNMP INTERFACE CARD
A plug-in UPS network interface card, making the UPS “SNMP manageable”:
it allows communication between UPS and network.
When this option is installed the ComProt communication link is no longer available to the user.