OPM_LPS_31E_8K0_20K_1GB_V010.doc
37/40
Operating
Manual
LP 31
/ 8-10-15-20
kVA
7.4
SAFETY
WARNING!
When the
LP 31
is operating, all parts of the electronics are directly connected to the mains
and high voltages are present on all internal parts, including the battery.
Even after disconnection from the mains, all parts inside the UPS, including the battery,
conduct dangerous voltages (except the ComConnect output).
For your safety,
only authorised service personnel
may remove the cabinet cover
7.5 STORAGE
Always store the UPS in a cool, dry location with the batteries in a fully charged state.
Storing the unit for a period exceeding 3 months can reduce the life of the batteries.
To maintain their normal life expectancy, the batteries must be recharged periodically.
Connect the unit to a mains supply and switch on all MCBs at the front panel for a period of
approximately 48 hours a minimum of every 3 months.