© 2016 General Electric Company. All rights reserved.
Remote Setpoint Change Options
• The SM-1000 series motors accept a 24 VDC or 120 VAC input.
The SM-1100 series motors accept a 4-20 MA signal and
require a separate 24 VDC or 120 VAC power connection.
• The total motor rotation is adjustable. The maximum number
of motor rotations possible coupled with the spring rate
determines the total setpoint range.
VRP-B-CH Pilot Selection Chart
Model Number
Control Range
(psig/kPa)
Spring Color
(Part Number)
Setpoint Change per
Revolution of
Setpoint Screw
Setpoint Range
Discrete Remote
Control (SM-1100)
Setpoint Range
Analog (4-20 mA)
Remote Control
(SM-1000)
VRP-B-175-CH
(1)
3 - 10
psig
20 - 69
kPa
Gold
(25-8236)
0.57 psig
3.9 kPa
3.1 psig
21 kPa
9
psig
62.1 kPa
7 - 30
psig
48 - 207 kPa
Beige
(25-8238)
2.0 psig
13.7 kPa
11 psig
75.8 kPa
23 psig
159 kPa
15 - 50
psig
103 - 345 kPa
Burgundy
(25-8239)
3.0 psig
21 kPa
16.5 psig
114 kPa
35 psig
241 kPa
20 - 85 psig
138 - 596 kPa
Pink
(25-8240)
6.4 psig
44 kPa
35.2 psig
243 kPa
65 psig
448 kPa
50 - 175 psig
345 - 1207 kPa
Yellow
(25-1306)
23 psig
157 kPa
125 psig
862 kPa
125 psig
862 kPa
VRP-B-600-CH
5 - 40 psig
34 - 276 kPa
Gold
(25-8236)
2.1 psig
14.6 kPa
11.5 psig
79 kPa
35 psig
241 kPa
25 - 140 psig
172 - 965 kPa
Beige
(25-8238)
7.4 psig
51 kPa
41 psig
283 kPa
115 psig
793 kPa
50 - 175 psig
345 - 1207 kPa
Burgundy
(25-8239)
11.3 psig
78 kPa
62 psig
427 kPa
125 psig
862 kPa
135 - 300 psig
931 - 2069 kPa
Pink
(25-8240)
24 psig
164 kPa
132 psig
910 kPa
165 psig
1138 kPa
275 - 600 psig
1896 - 4137 kPa
Yellow
(25-1306)
85 psig
586 kPa
425 psig
2930 kPa
425 psig
2930 kPa
VRP-B-1000-CH
550 - 1000 psig
3792 - 6895 kPa
Yellow
(25-1306)
143 psig
990 kPa
700 psig
4826 kPa
700 psig
4826 kPa
VRP-B-1500-CH
800 - 1300 psig
5516 - 8964 kPa
Grey
(25-1562)
227 psig
1565 kPa
850 psig
5860 kPa
850 psig
5860 kPa
900 - 1500 psig
6205 - 10342 kPa
Violet
(25-8073)
276 psig
1903 kPa
950 psig
6550 kPa
950 psig
6550 kPa
(1)
These models should only be used for applications that require high gain. Consult GE prior to selecting these models.