32
Logging and Alarms Menu
1. Limit Alarms
In some applications the valve may need to stay inside a specific prescribed region of operation. For this situation
the DNGP can be configured to give alarms when these limits are reached. To set the upper and lower limit alarms
follow the procedure given below.
▼
▼
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
▼
▼
Logging & Alarms
Limit Alarms
Remote Indicator
Reset Solenoid Cnt
▼
▼
Limit Alarms
Adjust Upper Limit
Adjust Lower Limit
Press UP or DOWN button
to select LOGGING &
ALARMS then press ENTER
button
Press UP or DOWN button
to select LIMIT ALARMS
then press ENTER button
Press UP or DOWN
button to select
ADJUST UPPER then
press ENTER button
Press UP or DOWN
button to select
ADJUST LOWER
then press ENTER
button
Upper Limit Alarm
98%
Lower Limit Alarm
2%
Press UP or DOWN
button to adjust
value then press
ENTER button
Press UP or DOWN
button adjust value
then press ENTER
button
2. Remote Indicator
The DNGP remote indicator function can be selected to function in solenoid counter mode,
or standby/manual mode. In counter mode the indicator pulses whenever either solenoid
activates. In standby/manual mode, the indicator is active whenever the DNGP is in standby
or manual modes.
▼
▼
Input Config
Valve Actions
Logging & Alarms
Utilities/Firmware
▼
▼
Logging & Alarms
Limit Alarms
Remote Indicator
Reset Solenoid Counter
▼
▼
Remote Indication
Solenoid Counter
Press UP or DOWN button
to select LOGGING &
ALARMS, then press
ENTER button
Press UP or DOWN button
to select INPUT SELECT
then press ENTER button
Press UP or DOWN button
to make option selection
then press ENTER button