© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
Masoneilan SVi1000 Positioner Quick Start Guide
=
|
67
Minimum current to maintain HART
®
3.4 mA
HART
®
Command#3 Mapping
HART
®
4-20 mA input signal
PV= Valve Position, 0-100%
SV = N/A
TV = Reserved
QV = Reserved
Table 9:
Input
Signal and Power, Specifications
Power Supply
Loop powered from 4-20 mA control signal
Compliance Voltage Rating
9.0 V at 20 mA, 11.0 V at 4.0 mA
Minimum Current Signal to Start Up
3.2 mA
Minimum Input Span for Split Range
Operation
5 mA
Upper Range Value for Split Range
Operation
8 mA to 20 mA
Lower Range Value for Split Range
Operation
4 mA to 14 mA
Wire Size
12/28 AWG
Strip Length
0.43 in / 11 mm
Digital Communication
HART
®
Communication protocol revision 5
(firmware version 2.2.1) and 7 (firmware ver-
sion 3.1.1 and later).
Table 10: Construction Material Specifications
Housing and Cover
Low Copper Aluminum Alloy
Weight
SVi1000: 3.2 lbs./ 1.451 kg
SVi1000 SW/G/IM: 4.1 lbs./ 1.860 kg
Relay
Nitrile diaphragms, Polycarbonate
I/P Motor
430 stainless steel, Low Copper Aluminum Alloy, 300 series
stainless steel, nitrile diaphragm
Magnet Holder
Corrosion Protected Anodized Aluminum 6061 T6
Table 8: Operational Specifications (Continued)
Содержание BAKER HUGHES Masoneilan SVi 1000
Страница 1: ...Masoneilan SVi 1000 Positioner Quick Start Guide Rev L BHGE Data Classification Public...
Страница 8: ...This page intentionally left blank...
Страница 18: ...This page intentionally left blank...
Страница 38: ...This page intentionally left blank...
Страница 56: ...This page intentionally left blank...
Страница 86: ...This page intentionally left blank...
Страница 87: ......