Setting Aggressiveness

While the SVi1000 DTM and the DD allow you to set 
Aggressiveness, the pushbuttons do not. In all three 
methods, however, the Aggressiveness value is inher-
ited from any previously performed tuning (Autotune or 
manual). Once Aggressiveness, and other tuning values 
are determined, they are stored in NVRAM.
The SVi1000 provides a user define Aggressiveness 
Level for auto-tuning, the allowable range varies from 
-9 to +9 where 0 (Zero) is consider normal tuning. The 
Aggressiveness Level influences stroking speed and 
over-shoot. A negative value will SLOW stroking speed 
and help minimized over-shoot. A positive value will 
INCREASE stroking speed and may add some 
over-shoot. The recommended values for Aggressive-
ness is 0 for control valves without volume boosters.
In applications with volume boosters and/or quick 
exhaust valves are used the Aggressiveness Level is 
not as influential. For Auto-tuning it is usually between 
0 and 3. Reduce the volume boosters sensitivity by 
opening the integral bypass needle valve about 1 to 2 
turns. Use caution when adjusting the needle valve so 
as to not to damage the seat, close gently to seat and 
then open 1 or 2 turns.

Aggressiveness Dynamic

Lower values of aggressiveness lead to lower PID val-
ues and slower response and less overshoot.
Higher values lead to higher PID values and quicker 
response and more overshoot.
Once you have a preferred aggressiveness and you 
tune once, all future autotunes automatically use that 
same value, until user-changed.

© 2019 Baker Hughes, a GE company, LLC. All rights reserved.

40 | 

=

BHGE

Notes on Aggressiveness

Содержание BAKER HUGHES Masoneilan SVi 1000

Страница 1: ...Masoneilan SVi 1000 Positioner Quick Start Guide Rev L BHGE Data Classification Public...

Страница 2: ...IDED THESE INSTRUCTIONS ASSUME THAT OPERATORS ALREADY HAVE A GENERAL UNDERSTANDING OF THE REQUIREMENTS FOR SAFE OPERATION OF MECHANICAL AND ELECTRICAL EQUIPMENT IN POTENTIALLY HAZARDOUS ENVIRONMENTS T...

Страница 3: ...Assembly 30 Step 2 Connecting the Tubing and Air Supply 31 Step 3 Wiring the SVi1000 32 Wiring Guidelines 33 Wiring an SVi1000 Unit 34 4 Check Out and Configuration 39 Overview 39 Step 1 Inspect the...

Страница 4: ...C 04 2012 Updated ES 761 to Rev D D 05 2013 Updated Rotary Kit Components all E 09 2013 Updated load limits switch drawing and added a reference to that section in installation Added polarity caution...

Страница 5: ...or other important information Read the instructions carefully before installing and maintaining your instrument Total compliance with all WARNING and CAUTION notices is required for safe operation In...

Страница 6: ...on Under normal operation compressed supply gas is vented from the SVi1000 to the surrounding area and may require additional precautions or specialized installations Intrinsically Safe Installation P...

Страница 7: ...nnel asphyxiation Use only genuine replacement parts which are provided by the manufacturer to guarantee that the products comply with the essential safety requirements of the European Directives Chan...

Страница 8: ...This page intentionally left blank...

Страница 9: ...ician efficiently in stall and setup an SVi1000 If you experience problems that are not documented in this guide refer to the SVi1000 Instruction Manual call your local representative go to valves bhg...

Страница 10: ...nnectors Optionally you can order a unit configured with two digital switches or a 4 20 mA position re transmit output Figure 1 shows the standard interface board Figure 1 Operator Controls Standard A...

Страница 11: ...board and optional gauges Figure 2 Optional Digital Switches and Gauges Figure 3 shows the optional position retransmit interface board and optional gauges Figure 3 Optional Position Retransmit Solid...

Страница 12: ...Auto Find Stops This function automatically sets the lower and upper stops See Auto Find Stops on page 43 for this procedure Open Stop Adjustment Use the Open Stop Adjustment screw to perform an upper...

Страница 13: ...ation activity Normal Mode In this mode the valve follows the 4 20 mA input signal HART Override mode In HART override mode the local user interface buttons are disabled until any button is pushed the...

Страница 14: ...ing then the unit requires a reset after correcting the failsafe condition Commission Processes These are temporary states activated when a local user interface issued command dictates their use When...

Страница 15: ...sent an LED being active and dashes represent the LEDs off The pattern shown recurs as long as that condition exists Figure 5 Example LED Pattern Table 1 LED Light Patterns and Troubleshooting Indicat...

Страница 16: ...sufficient Process Failure Pattern depends on which process failed and repeats until Cancel button is pushed Setting out of range If a setting is out of range the associated Green LED flashes at twice...

Страница 17: ...C All rights reserved Masoneilan SVi1000 Positioner Quick Start Guide 17 Major Components Figure 6 shows the unit s major components for reference Figure 6 SVi1000 Major Components Electronics Module...

Страница 18: ...This page intentionally left blank...

Страница 19: ...ed in this manual may cause loss of life and property Before installing or using this instrument READ THE INSTRUCTIONS CAREFULLY Refer to Hazardous Location Installation and Declaration of Conformity...

Страница 20: ...uit unless the controller is HART compatible or has a HART filter Loss of control or a process upset may occur if the controller output circuit is not compatible with a HART signal 2019 Baker Hughes a...

Страница 21: ...Necessary Precautions To avoid injury or the process being affected when installing or replacing an SVi1000 positioner on a control valve ensure that If the valve is located in a hazardous area ensur...

Страница 22: ...on rotary control valves that have less than 60 rotation such as the Camflex Figure 7 shows the kit components Figure 7 Rotary Kit Components Figure 8 shows a side view of a Camflex actuator the SVi10...

Страница 23: ...tension shaft to the valve position take off shaft Figure 10 Figure 10 Extension Shaft to the Valve Position Take off Shaft Long Side Mounting Holes Mounting Bracket Mount the long end of the mounting...

Страница 24: ...g retains it in that position Vacuum service The valve shaft is drawn into the body by the vacuum acting on the shaft but the magnetic coupling must be assembled flush with the mounting bracket 3 Perf...

Страница 25: ...ura tions Any amount of rotation Clockwise or counter clockwise 0 50 Travel Mid Stroke 0 1000 2019 Baker Hughes a GE company LLC All rights reserved Masoneilan SVi1000 Positioner Quick Start Guide 25...

Страница 26: ...ontact with the skirt around the alignment ring on the SVi1000 Figure 11 CAUTION Do not carry the positioner by the alignment ring Figure 11 Camflex V Seal Align the end of the magnet holder assembly...

Страница 27: ...required 7 16 Combination Wrench 2 required 3 8 Combination Wrench 1 2 Combination Wrench Phillips Head Screw Driver M4 Hex Key M3 Hex Key 1 Mount the standard reciprocating mounting bracket to the v...

Страница 28: ...right position Table 3 Reciprocating Valve Mounting Hole and Turnbuckle Length Actuator Size Masoneilan 87 88 Stroke Mounting Hole Lever Hole Turnbuckle Length 6 and 10 0 5 0 8 12 7 20 32 mm A A 1 25...

Страница 29: ...rod end to the bracket using four M5 X 10 mm flat head screws 8 Attach the left hand threaded rod end to the take off rod with 1 4 20 UNC nut and thread the left hand lock nut onto the rod end 9 Move...

Страница 30: ...ure Position Linearity 13 Mount the SVi1000 to the bracket and secure with four M6 socket head cap screws Integrated Magnet Assembly The IM Integrated Magnet assembly kit is an optional assembly inten...

Страница 31: ...ubing to the air supply port Minimum tubing diameter 1 4 Figure 17 Figure 17 Air Ports 2 Pipe the output air from the output pressure port to the actuator Minimum tubing diameter 1 4 NOTE The SVi1000...

Страница 32: ...bove the spring range of the actuator but may not exceed the rated actuator pressure Refer to the valve or actuator instruction manual Step 3 Wiring the SVi1000 WARNING Comply with current national an...

Страница 33: ...se that would interfere with the HART tones with the shield grounded Shield must be properly grounded in only one place For details and calculation methods for wiring resistance and capacitance and fo...

Страница 34: ...ctors To connect CAUTION For proper operation maintain signal polarity and respectively CAUTION You must read Appendix B Optional Switch Load Limits on page 59 before proceeding The load across these...

Страница 35: ...wires fully in to the appropriate terminal Loosen the terminal screw if required to insert the wire Refer to the label next to each screw terminal to determine the function of the terminal and correct...

Страница 36: ...itches Unit To troubleshoot control loop connections 1 Connect a DC voltmeter across the input terminals For an input current between 4 and 20 mA the voltage varies between 11V and 9 V respective If v...

Страница 37: ...ceeds 11 V check that polarity is correct If the polarity is correct but the voltage is less than 8 05 V then the current source voltage is not compliant 2 Verify that source can supply 20 mA to SVi10...

Страница 38: ...This page intentionally left blank...

Страница 39: ...de 1 Step 1 Inspect the Actuator Linkages or Rotary Adapter on page 41 2 Step 2 Verify Mounting and Linkage Adjustment on page 41 3 Step 3 Checking the Magnet on page 41 4 Step 4 Checking the Air Supp...

Страница 40: ...nded values for Aggressive ness is 0 for control valves without volume boosters In applications with volume boosters and or quick exhaust valves are used the Aggressiveness Level is not as influential...

Страница 41: ...tep 2 Verify Mounting and Linkage Adjustment Inspect the mounting and make any needed adjustments before running the positioner and checking the digital configuration Step 3 Checking the Magnet There...

Страница 42: ...Closed the value should be between 1000 and 1000 for a reciprocating valve or a 60 rotation rotary valve At mid travel the value should be between 1000 and 1000 for a greater than 60 rotation rotary v...

Страница 43: ...tions Prior to changing the SVi1000 configuration check the existing configuration Use the proce dures that follow to run auto stops run open stop adjustment and perform preset or auto tune WARNING Th...

Страница 44: ...stment button for two to seven seconds until green LED 2 illuminates then release Green LED 2 flashes 2 Move the valve to the desired location via the Open Stop Adjustment Screw Figure 21 Figure 21 Op...

Страница 45: ...un Auto Tune Auto Tune on page 48 PID Settings The third method is to manually tune PID settings for fine tuning if desired See the online help Preset Tune Preset tuning is done according to valve act...

Страница 46: ...C All rights reserved 46 BHGE To use preset tuning values Use the Configuration Selection Switch to select a preset tuning value Figure 23 Figure 23 Configuration Selection Switch Configuration Select...

Страница 47: ...Actuator Size Examples 1 9 Small 1 4 5 Camflex 7 15 SR 2 A 2 6 Camflex 7 15 SR 3 B 3a 6 87 ATC 3 15 SR 3b 6 88 ATO 11 23 SR 3c 10 87 ATC 3 15 SR 3d 10 88 ATO 11 23 SR 4 C 4s 6 87 ATC 6 30 SR 4b 6 88 A...

Страница 48: ...0 for an ATO valve Air to Open application 8 for an ATC valve Air to Close application Figure 24 Configuration Selection Switch 2 Press the Autotune button until green LED 3 lights then release appro...

Страница 49: ...t available during normal ValVue operation Contact BHGE or a channel partner for more information ValVue and SVi1000 DTM Trial Version You must download the ValVue software and the SVi1000 DTM softwar...

Страница 50: ...port or Bluetooth A HART modem and appropriate cables Masoneilan Software For ValVue 3 or DTM registration you must run the frame application i e ValVue 3 PACTware etc as Administrator For instance f...

Страница 51: ...ce Library https valves bhge com resource center and enter ValVue in the search field arrow in Figure 25 Figure 25 Download Center Search for Valve 3 The results appear red box in Figure 25 2 Click Do...

Страница 52: ...u have a previous install of ValVue 3 you are prompted to uninstall first and then you must run the installer again to finish the upgrade NOTE If you are upgrading from ValVue 2 x you must update the...

Страница 53: ...all the SVi1000 DTM 1 Go to the Resource Library https valves bhge com resource center and enter SVI1000 DTM in the search field red arrow in Figure 28 Figure 28 Download Center Search for SVi1000 DTM...

Страница 54: ...ve the download file to your laptop PC Don t install from the website 4 Open Windows Explorer and click the Windows Downloads folder NOTE If you have a previous install of the SVi1000 DTM you are prom...

Страница 55: ...user interface checkout and configuration can also be performed using the standard HART communications interface Connect the HART Handheld Communicator HHC to the SVi1000 as shown in Figure 30 Refer t...

Страница 56: ...This page intentionally left blank...

Страница 57: ...provides interoperability with leading control systems suppliers SVi1000 Setups A typical system setup is shown in Figure 31 General Purpose Installation schematic Wiring diagrams are generalized actu...

Страница 58: ...he intrinsic safety barrier The case grounding screws are located on the outside of the case The case is isolated from all circuitry and can be grounded locally in accordance with applicable codes Com...

Страница 59: ...tly across the power source the current will be limited only by the capacity of the power source and the switch can be damaged This section discusses the necessary precautions when configuring a syste...

Страница 60: ...s on closed the external voltage must be dropped across the load Figure 33 The load must be designed such that the current in the circuit is 1 A at all times Some 3rd party devices such as incandescen...

Страница 61: ...en the connection is shown in Option 2 The barrier must have adequate resistance to limit inrush current as the fuse cannot limit inrush current see Wiring Option 2 Power source can be part of DCS PLS...

Страница 62: ...the valve position by outputting a 4 20mA analog signal If the positioner stops working due to lose of loop power or malfunctioning the retransmit output stays at around 3 2 mA This section discusses...

Страница 63: ...ner self regulates voltage as current flows through it Additionally it also doesn t confirm what system voltage is available under load conditions Therefore if com pliance testing needs to be done it...

Страница 64: ...VDC This is the available system voltage at the maximum output Table 6 lists some compliance voltage readings at positioner terminals at several currents Table 6 Expected Voltage Range at Positioner T...

Страница 65: ...o 100 non condensing Humidity Effect Less than 0 2 after 2 days at 104 F 40 C 95 Rela tive Humidity Electromagnetic Compatibility Electrostatic IEC 61514 Industrial Process Control systems methods of...

Страница 66: ...ition Auto Tune SVi1000 performs automatic determination of the optimal valve position control param eters In addition to P I D the position algo rithm uses damping symmetry for exhaust and fill time...

Страница 67: ...n 5 mA Upper Range Value for Split Range Operation 8 mA to 20 mA Lower Range Value for Split Range Operation 4 mA to 14 mA Wire Size 12 28 AWG Strip Length 0 43 in 11 mm Digital Communication HART Com...

Страница 68: ...T Physical Device Type Positioner HART cmd rev 5 or 7 Device type 204 0x00cc DD Registered with the Field Comm Group Yes Integration with HART Host software ValVue standalone ValVue AMS SNAP ON applic...

Страница 69: ...supply Air Capacity flow coefficient Loading CV 0 30 Venting CV 0 40 Air Consumption 0 19 scf min 5 4 L min at 30 psi 2 1 bar supply 0 30 scf min 8 5 L min at 60 psi 4 2 bar supply 0 40 scf min 11 4...

Страница 70: ...mbly with position retransmit SVi1000 PR G Assembly with position retransmit and gauges With Integrated Magnet SVi1000 IM Assembly with integrated magnet SVi1000 G IM Assembly with gauges and integrat...

Страница 71: ...000 SVi1000 Housing Cover Replacement Part Number 720045085 999 000 SVi1000 Position Retransmit Terminal Board Electronic Assembly Part Number 720045084 999 000 SVi1000 Switch Terminal Board Electroni...

Страница 72: ...ration of Conformity The following pages provide the agency approved installation procedure for hazardous locations which is followed by the Declaration of Conformity WARNING The installation procedur...

Страница 73: ...t to return upon demand REV Description Date A Initial Release Dec 15 2010 B ADR 003590 Oct 18 2011 C ADR 003639 Feb 7 2012 D ADR 003652 March 5 2012 E ADR 003853 Jun 03 2013 F ADR 004045 Dec 15 2015...

Страница 74: ...RE TYPE 5 4 TEMPERATURE CODE 5 5 NOTES RELATED TO INTRINSIC SAFETY 6 INTRINSICALLY SAFE INSTALLATION WIRING REQUIREMENTS 6 1 MODELS SVI1000ABC WHERE A SW OR NONE INSTALLATION 6 2 MODEL SVI1000ABC WHER...

Страница 75: ...mosphere Adherence to these requirements assures that the SVi1000 will not cause ignition of the surrounding atmosphere Hazards related to control of the process are beyond the scope of this manual Fo...

Страница 76: ...pe depends on wiring glands the glands must be certified for the type of protection required The metal housing is a die cast alloy which is predominately aluminum X Marking on label Since the SVi1000...

Страница 77: ...es are SVi1000 abc Where a none SW or PR b none or G c none or IM MODEL DESCRIPTION SVi1000 SVi1000 Assembly SVi1000 SW SVi1000 Assembly with switches SVi1000 G SVi1000 Assembly with gauges SVi1000 SW...

Страница 78: ...d trade secret This document and all information herein is the property of Dresser LLC It is confidential and must not be made public or copied and is subject to return upon demand For operation in ha...

Страница 79: ...D T4 Ta 40oC to 85oC Class I Zone 2 AEx nC IIC T4 Gc T4 Ta 40oC to 85oC Ingress Protection NEMA 4X IP66 Canada Approvals FM Canada Approved FM17CA0046X Intrinsically Safe Temperature Classification Cl...

Страница 80: ...Pressure 100 psig Clean instrument air and natural gas are the typical supply sources 5 2 4 Current 4 to 20mA 5 3 Enclosure Type NEMA 4X Type 4X IP66 5 4 Temperature Code T4 Ta 85 C 5 5 Notes Related...

Страница 81: ...ZARDOUS LOCATION UNSPECIFIED EXCEPT THAT BARRIERS MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN EXCESS OF 250 VOLTS RMS OR 25...

Страница 82: ...RIERS MUST NOT BE SUPPLIED FROM NOR CONTAIN UNDER NORMAL OR ABNORMAL CONDITIONS A SOURCE OF POTENTIAL WITH RESPECT TO EARTH IN EXCESS OF 250 VOLTS RMS OR 250 VOLTS DC 1 2 3 4 Optional Hand Held Commun...

Страница 83: ...he barrier earthing requirements must comply with the installation requirements of the country of use Factory Mutual requirements USA ANSI ISA RP12 6 Installation of Intrinsically Safe Systems for Haz...

Страница 84: ...indicated on the associated apparatus If the optional Hand Held Communicator is used on the Hazardous Area side of the barrier then the capacity and inductance of the communicator must be added and t...

Страница 85: ...rings are in place and not damaged and all wires are securely connected When installing the main cover ensure the gasket is seated in the cover flange groove the flange area is not corroded and the s...

Страница 86: ...This page intentionally left blank...

Страница 87: ......

Страница 88: ...5 1276 Fax 88 7 495 585 1279 Houston Texas Phone 1 281 671 1640 Fax 88 1 281 671 1735 INDIA Mumbai Phone 91 22 8354790 Fax 88 91 22 8354791 SAUDI ARABIA Phone 966 3 341 0278 Fax 88 966 3 341 7624 New...

Отзывы: